The Mini-Pak™ 3000 Injector uses the EIA-485 standard for communications. A converter is required to enable communications with peripheral devices such as modems or personal computers which use the EIA-232 interface standard. Honeyw Enraf can provide an EIA-485 to EIA-232 converter if your application requires one. Communications via modem requires a modem to be installed at each end of the communications link, and an appropriate converter (if required). The modem must be programmed to Auto Answer, and the cabling must be designed to provide auto-answer capabilities on the terminal end. Although often overlooked, proper system wiring is critical to the reliable operation of serial communications interfaces. Improper wiring can cause high data error rates and reduce data throughput. Although exact wiring requirements vary depending on the type of interface used, each of the following is important to the overall success of a communications system: Cable lengths and types Shielding Twisted Pair Wiring EIA 485 interfaces are typically used in multi-drop configurations. The system wiring can become very complex. When installing a 2-wire cable for use with the Mini-Pak™ 3000, receive and transmit share the same conductor pair. The wires must be a twisted pair. Wiring for EIA 485 must be designed as a daisy chain. Cable stubs are permitted so long as they are 15 feet or less in length. Conductor pairs must be terminated with a 100 ohm resistor at the most distant end to ensure proper line impedance for maximum signal reception. Using the recommended cable (Belden Cable 9841 for 2-wire) an EIA 485 interface may support multiple devices (stations) over a maximum wire length of 3600 feet.
5.1.1 Communication Settings
Communication with the Mini-Pak™ 3000 Injector may be achieved by two methods. The Hand-Held Controller (HHC) and its keypad access the Mini-Pak™ 3000 via an infrared port, through the explosion-proof enclosure window, in much the same manner as a television remote control. Use of the HHC offers the convenience and safety of on-site communications with the unit in a hazardous environment, without having to remove the cover and exposing potentially explosive electrical connections.
Part No.: 4418200 - Revision 0 Mini-Pak™ 3000 5-1
Installation & Operation Manual Communications
The other method of communications takes place through a hard-wired,
serial communications port which supports EIA 485 standards, and is connected to the master via a data communications line. Protocol selection is determined by setting Parameter # 190, with the options being: Disable serial port (0) Type I – FMC Smith (1) Type II – Brooks (2) Type III – Not currently used (3) Type IV - Modbus RTU ASCII protocol (4) Refer to the Communications Specification for complete details regarding your specific protocol. The settings for all of the communication protocols are as follows: Baud rate 1200/2400/9600/19,200 Data Bits 8 Stop Bit 1 Parity None
5.2 Accessing Mini-Pak™ 3000 Parameters Via Communications
How to read the tables: Code = Parameter code or Task code Register Description = the meaning or purpose of the register/task code Range = the minimum and maximum values that the register can hold Format = the exact format of the value as it is transmitted or received N - ASCII character between 0 and 9 (30 hex - 39 hex) A - an ASCII alphanumeric character (32 hex - 7A hex) ; - Semi-colon (3B hex) is reserved and not allowed B - ASCII character representation of a binary value (0 or 1) H - ASCII hex character representation of a binary value HH:MM:SS - Standard time format hours: minutes:seconds MM/DD/YY - Standard date format months/days/years