You are on page 1of 2

CAPACITOR CALCULATION FOR DETUNE FILT

** Enter 4 value **
Capacitor rated : 50 Kvar
System voltage : 400 Volt
% detuned reactor : 6 %
Frequency : 50 Hz

Detuned Capacity Detuned Capacitor Detuned Capacitor Detuned Inductance


of Capacitor Voltage Current of Reactor

75 Kvar 506 Volt 85.77 Amp 0.650 mH.

Maximum of Hamonic Limit U1 = 6 % , U3 = 0.5 % , U5 =

CAPACITOR RATED WITH DETUNE FILTER = 525 Volt 81 Kvar

* Norminal capacitor current is summed with maximum harmonic current through capacitor.
** Norminal system voltage is summed with maximum harmonic voltage across capacitor.
N FOR DETUNE FILTER

Detuned Reactor Max Current of Max Voltage


Current Capacitor including across
Harmonic Current * Capacitor **
88.83 Amp 84.60 Amp 506 Volt

U1 = 6 % , U3 = 0.5 % , U5 = 5 % , U7 = 5 %

REMARK : FOR CAPACITOR RATED STANDARD


400V, 440V , 480V , 525V
580V , 690V , 790V , 1000V