1.

Location : Control Room /CRP Panel

Feeder Name : Bus section Control panel

2. Name plate details:

Type of meter Ammeter MFM Meter


Make AE AE
250 / 1 A& 132
CT Ratio/PT Ratio 250 / 1 A
KV/110 V

3. Secondary Injection Test:

3.1. MEASUREMENT:

AMMETER:

Ref Applied Sec Current (A) Measured Current At Meter (A)


R 1.0 250
Y 1.0 250
B 1.0 250

MFM Meter:

At 0.8 Pf lag

Ref Applied Sec Applied Sec Measure MW at Measure MVAR Measure MVA
Current (A) Voltage (V) Meter at Meter at Meter
R .5 63.5 22.8 16.53 28.5
Y .5 63.5 22.8 16.53 28.5
B .5 63.5 22.8 16.53 28.5

4. RESULT : Meter Found Healthy.