AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
5 6
7 8
Constructability Four principles of constructability
Simplicity = Economy
Constructability defines the ease with Least weight does not always = Least cost
which structures can be built.
Fewer pieces = Greater economy
Constructability = Economy
Efficient connection design = Reduced cost
Copyright © 2012
American Institute of Steel Construction
2
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
9 10
Show the reactions Show the reactions
Tip #1 Tip #1
11 12
Show the reactions Show the reactions
Do not require connection strength to be based on
the Table 3-6 maximum uniform load values.
Tip #1 Tip #1
Copyright © 2012
American Institute of Steel Construction
3
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
13 14
Show the reactions Provide moments & axial forces
Copyright © 2012
American Institute of Steel Construction
4
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
17 18
Allow use of bearing bolt strength values where Allow use of bearing bolt strength values where
permitted by the building code permitted by the building code
Avoid notes such as this on your drawings:
Avoid notes such as this on your drawings: “The following connections must be slip-critical:
- Connections within 3 feet of columns
- Connections directly supporting columns
“All bolted connections shall be designed as - Hanger connections
slip-critical connections.” - Stair connections
- Cantilever connections
- Bracing connections
- All connections supporting 50k or more
- Connections to plate girders
Slip-critical connections are generally only required Bearing bolt shear strength values can be used for
when over-sized or slotted holes are used with loads all of the above when STD or SSL holes are used
parallel to the slots with loads perpendicular to the slot. (Bolts may
have to be pre-tensioned.)
Tip #5 Tip #5
19 20
AISC 341-10, Section D2.2
AISC 360-10, Section J1.10 2. Bolted Joints
Limitations on Bolted and Welded Connections Bolted joints shall satisfy the following requirements:
Joints with pretensioned bolts or welds shall be used for the following (1) The available shear strength of bolted joints using standard holes shall be calculated as
that for bearing-type joints in accordance with Specification Sections J3.6 and J3.10. The
connections: nominal bearing strength at bolt holes shall not be taken greater than 2.4dtFu.
(1) Columns splices in all multi-story structures over 125 ft in height (2) Bolts and welds shall not be designed to share force in a joint or the same force component in a
(2) Connections of all beams and girder to columns and any other beams connection.
and girders on which the bracing of the columns is dependent in (3) Bolt holes shall be standard holes or short-slotted holes perpendicular to the applied load.
structures over 125 ft in height. Exception: For diagonal braces specified in Sections F1, F2, F3 and F4, oversized holes are
(3) In all structures carrying cranes over 5-ton capacity: roof truss splices permitted in one connection ply only when the connection is designed as a slip-critical joint for the
and connections of trusses to columns; column splices; column required brace connection strength in Sections F1, F2, F3 and F4.
bracing; knee braces; and crane supports. (4) All bolts shall be installed as pretensioned high-strength bolts. Faying surfaces shall satisfy
(4) Connection for the support of machinery and other live loads that the requirements for slip-critical connections in accordance with Specification Section J3.8 with a
produce impact or reversal of load. faying surface with a Class A slip coefficient or higher.
Copyright © 2012
American Institute of Steel Construction
5
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
21 22
Permit the use of one-sided connections Permit the use of any size & type of bolt
(single angle and single-plate connections)
Tip #6 Tip #7
23 24
Permit the use of short-slotted holes in shear Delegate connection design to the
connections fabricator
From AISC 303-10:
Example of what not to specify:
3.1.2. The owner’s designated representative for design shall
“All bolts shall be ¾” diameter. All holes shall be indicate one of the following options for each connection:
13/16” diameter.”
(1) The complete connection design shall be shown in the
Most fabricators require short-slotted holes holes in shear structural design drawings;
connections to accommodate tolerances and facilitate (2) In the structural design drawings or specifications, the
steel erection. (SSL holes are needed when beams are connection shall be designated to be selected or completed by an
cambered.) experienced steel detailer; or,
(3) In the structural design drawings or specifications, the
AISC connection design procedures permit the use of SSL connection shall be designated to be designed by a licensed
holes with snug-tightened bolts for most types of shear professional engineer working for the fabricator.
connections
Tip #8 Tip #9
Copyright © 2012
American Institute of Steel Construction
6
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
25 26
Delegate connection design to the Delegate connection design to the
fabricator – but do so properly fabricator
When option (2) or (3) above is specified, the owner’s designated representative
for design shall provide the following information in the structural design Possible note for delegating connection design when R=3,
drawings and specifications:
(a) Any restrictions on the types of connections that are permitted; “Structural steel connections shall be designed in
accordance with the requirements of the building code and
(b) Data concerning the loads, including shears, moments, axial forces and
transfer forces, that are to be resisted by the individual members and their
with AISC 360-10 using connection design procedures
connections, sufficient to allow the selection, completion, or design of the documented in publications such as the AISC Engineering
connection details while preparing the shop and erection drawings; Journal, the AISC Steel Construction Manual, 14th Edition
(c) Whether the data required in (b) is given at the service-load level or the and the AISC Steel Construction Manual Design
factored-load level; Examples.”
(d) Whether LRFD or ASD is to be used in the selection, completion, or design of
connection details; and,
27 28
Frame girders to column flanges; beams to webs Size columns to eliminate need for stiffeners
Copyright © 2012
American Institute of Steel Construction
7
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
29 30
Where column stiffeners can’t be avoided, Use deepest practical column; avoid W8
make opposing beams the same depth columns with connections to web
31 32
Orient columns to minimize skewed Orient columns in braced frames square
connections
Copyright © 2012
American Institute of Steel Construction
8
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
33 34
Orient columns in braced frames square to the Frame members with very large reactions square
beams and braces (preferably to the column flanges) to columns - preferably to the flanges.
35 36
Configure framing so that no more than one Configure framing so that no more than one
beam frames to any one side of a column beam frames to any one side of a column
Do not do this!
Copyright © 2012
American Institute of Steel Construction
9
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
37 38
Head off steeply skewed connections Configure framing to minimize skewed
connections
40
Favor pipe columns over square/rectangular HSS when Watch out for connection interference where
there are skewed connections beams are slightly offset from columns
Copyright © 2012
American Institute of Steel Construction
10
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
41 42
Increase beam depth to avoid web reinforcement Beams with flange-bolted moment
connections must have sufficiently wide
flanges to install bolts
43 44
Size members to have sufficient strength at
the net section
Rule-of-thumb:
Max. recommended
stress ratio at gross =
Required strength
Usable strength
= 0.75 (max.) Questions?
section
Tip #24
Copyright © 2012
American Institute of Steel Construction
11
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
45 46
Here’s what can happen when you don’t anticipate,
Communicate and coordinate coordinate and communicate…
Ask your client in writing for the information that you need
and give dates for when that information is needed.
47 48
Do not delegate design of reinforcing around Provide sufficient information on the drawings to
beam web openings minimize uncertainty among bidders
Copyright © 2012
American Institute of Steel Construction
12
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
49 50
Do not delegate design of plate girder welds Think about how the connections will be
detailed even when connection design is
delegated to the fabricator
51 52
Configure HSS framing to simplify connections Some welding tips to enhance
constructability
Copyright © 2012
American Institute of Steel Construction
13
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
53 54
Select efficient diagonal braces Select efficient diagonal braces
55 56
Configure slopes of diagonal braces at Configure slopes of diagonal braces at
35 to 55 degrees 35 to 55 degrees
Copyright © 2012
American Institute of Steel Construction
14
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
57 58
Verify that framing can be installed Configure framing to minimize the
number beams
Copyright © 2012
American Institute of Steel Construction
15
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
61 62
Orient columns in moment frames for strong Strong axis beam-to-column moment connections are generally
axis bending less complex than weak axis beam-to-column moment
connections
63 64
Run heavy moment-connected girders Run cantilevered roof beam over tops of columns
through columns to simplify flow of moment
through the columns
Copyright © 2012
American Institute of Steel Construction
16
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
65 66
Minimize the “gingerbread” Selectively turn slab spans to reduce
“gingerbread”
- Brace angles
- Relieving angles
- Bent plates
-Stiffeners
-Web doubler plates
-Little beams
connections
Copyright © 2012
American Institute of Steel Construction
17
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
69 70
Simplify base plates and anchor rod details Some constructability tips for hangers
71 72
Understand fabricator preferences regarding Avoid torsion in W shape beams
preferred connection details
Copyright © 2012
American Institute of Steel Construction
18
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
73 74
Camber intelligently Summary
- Do not camber beams in moment frames & braced frames To enhance constructability,
- Do not camber short beams (< 25’ long)
- Do not camber light beams (< 19 plf) - Think about the connections
- Do not over-camber (camber for 75% of slab + steel weight) - Show the reactions, moments & axial forces
- Specify additional concrete be poured to achieve level floor - Do not impose arbitrary constraints on connection design
- Include ponded concrete load in design - Delegate connection design
- Do not specify camber < ¾” - Strive to keep connections square
- Do not specify that camber be measured after erection. - Use R=3 for seismic design (when permitted).
- Compare camber cost to material cost - Understand fabricator preferences
- Permit alternative connection details
For more information, go to presentation on AISC website, - Minimize the number of structural framing members
“Specifying Camber: Rules-of-Thumb for Designers” - Minimize the “gingerbread”
www.aisc.org/elearning found under “Boxed Lunch” - Communicate & coordinate
presentations
Tip #50
75 76
• OR…
Copyright © 2012
American Institute of Steel Construction
19
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
77 78
• Go to:
http://www.wynjade.com/aiscfall12/webinarCEU.
• 14th Edition Manual Seminar
Username: Your Web ID (on your registration receipt)
Password: Your Last Name
– Nearly 30 cities in Fall 2012
– Opportunity to purchase the Manual for only
$100
• Completely fill out online form. Don’t forget to check
the boxes next to each attendee’s name!
• Questions? Please email us at webinars@aisc.org. • Listen to the Steel – Duane Miller on
Welding
www.aisc.org/seminars
79 80
www.aisc.org/elearning
www.aisc.org/webinars
Copyright © 2012
American Institute of Steel Construction
20
AISC Live Webinar 50 Tips for Designing Steel Framed Buildings
September 27, 2012
81
Thank You!
Copyright © 2012
American Institute of Steel Construction