Professional Documents
Culture Documents
The trip valves in the turbine protection system must be tested for correct function at
intervals given in the section Periodic Attention.
The test will not interfere with the normal operation of the turbine.
The three Channel Overspeed Protection Module has an on board frequency generator that
can generate a test signal for testing the overspeed protection function. This function and
associated relay outputs are used during the trip valve test.
Conditions
The test is performed during operation or at turning gear operation
We reserve all rights in this document and in the information
Conditions (among others) if the test is to be performed with turning gear in operation:
contained therein. Reproduction, use or disclosure to third
Performing
The test function is invoked by selecting the actual trip channel to be tested.
Only one module in the Overspeed Protection Group may be in Test Mode at any
Time.
When the test is invoked, the simulated speed will start at a predefined level and then
slowly be raised above the tripping speed level (110%).
Note! If indication for tripped tripping valve does not appear at item 2,
interrupt the test and begin fault tracing.
Note! the open position is calculated from the 1 of 3 test pressure AND
the measured feedback voltage from the feeding end of the trip
valve solenoid (There is no physical position indication
feedback from the trip valve).