TTF300
Field-mount temperature transmitter
Further information
Additional documentation on TTF300 is available to download
free of charge at www.abb.com/temperature.
Alternatively, scan this code:
Manufacturer
ABB Automation Products GmbH
Process Automation
Schillerstr. 72
32425 Minden
Germany
Tel: +49 571 830-0
Fax: +49 571 830-1806
WARNING
The signal word "WARNING" indicates an imminent danger.
Failure to observe this information may result in death or
severe injury.
CAUTION
The signal word "CAUTION" indicates an imminent danger.
Failure to observe this information may result in minor or
moderate injury.
NOTICE
The signal word "NOTICE" indicates useful or important
information about the product.
The signal word "NOTICE" is not a signal word indicating a
danger to personnel. The signal word "NOTICE" can also
refer to material damage.
- -
A B A10096
Fig. 3
A Transmitter B Supply isolator / DCS input with supply / Segment
coupler
A
J
B C A10128
Fig. 6 A
A Sensor B Transmitters TTF300 C Supply isolator [Ex ib] B C A10130
D Interface for LCD display Fig. 8
A Sensor B Transmitters TTF300 C Supply isolator
The input for the supply isolator must have an [Ex ib] design. D Fuse, 32 mA E Interface for LCD display
As the user, it is your responsibility to ensure that the sensor
instrumentation meets the requirements of applicable The power supply circuit of the transmitter must be limited by
explosion protection standards. The sensor can be installed in an upstream fuse with a fuse current rating of 32 mA. This is
Zone 0, Zone 1, or Zone 20. not required if the power supply unit is intrinsically safe with an
When using the transmitter in Zone 1, make sure that [Ex ia] design.
impermissible electrostatic charging of the temperature
transmitter is avoided (observe the warnings on the device).
NOTICE
Ex relevant specifications must be taken from the EC-type
examination certificates and other relevant certificates that
apply in each case.
3.3 Commissioning
The commissioning and parameterization of the device may
also be carried out in potentially explosive atmospheres using
a handheld terminal that has been approved accordingly under
consideration of an intrinsic safety installation check.
Alternatively, an Ex modem can be connected to the circuit
outside the potentially explosive atmosphere.
WARNING
Risk of explosion!
The device must not be used in areas in which process-
related electrostatic charging of the housing may occur.
The device must be maintained so that any dangerous
electrostatic charge is avoided.
measurement. k
However, recent advances in technology now mean that j
maximum measuring accuracy can be achieved where 9
necessary by carrying out individual sensor error adjustment. 8
7 6 5 4
Sensor characteristic curves are optimized by using a Pt100 A11236
polynomial in accordance with IST-90 / IEC 751, and Fig. 14: HART name plate (example)
EN 60150, and by applying A, B, C, or Callendar-Van Dusen
coefficients.
The DTM or EDD can be used to set and store these sensor
coefficients (Callendar-Van Dusen) in the transmitter as a CVD
characteristic curve. Up to five different CVD characteristic
curves can be stored for HART and PROFIBUS PA, and up to
two can be stored for FOUNDATION Fieldbus. A11237
Fig. 15: PROFIBUS PA name plate (example)
5 Product identification
5.1 Name plate
A11238
5
4
3
2
A11239
Fig. 17: Special data plate for explosion-protected devices
(example)
1 Model number 2 Temperature class explosion-proof design
3 CE-symbols (EU conformity) and specified designations of the
quality assurance 4 Safety class explosion-proof design 5 Ex-
marking
NOTICE
Potential adverse effect on the IP rating
— Check the O-ring gasket for damage and replace it if
necessary before closing the housing cover.
— Check that the O-ring gasket is properly seated when
closing the housing cover.
NOTICE
The signal cable wires must be provided with wire end
sleeves.
The slotted screws of the connection terminals are tightened
with a size 1 screwdriver (3.5 or 4 mm).
Supply voltage
— Maximum cable outer diameter: 12 mm (0.47 inch)
— Maximum wire cross-section: 2.5 mm2 (AWG 16)
Change from two to one column
8
9
1 2 3 4 6 7
8 A10273
Fig. 21: The shielding of the sensor connection cable and the shielding of the power supply cable are separate and each grounded at one
end
1 Temperature sensor 2 Shielding to the sensor insulated 3 Sensor connection cable 4 Shielding over transmitter housing grounded
5 Transmitter housing grounded 6 Shielding of transmitter housing insulated 7 Supply voltage cable 8 Grounding point 9 Supply
isolator / Distributed Control System (DCS) DCS-entry
Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing grounded
The shielding of the sensor connection cable is grounded via the grounded sensor housing. This shielding of the power supply
cable is insulated from the transmitter housing.
The shielding of the power supply cable is grounded at the supply isolator / DCS input directly. This shielding is insulated from
the transmitter housing.
The shielding of the power supply cable and the shielding of sensor connection cable must not be connected to one another.
Make sure that the shielding is not connected to ground anywhere else.
8
9
1 2 3 4 6 7
8 8 A10274
Fig. 22: The shielding of the sensor connection cable and the shielding of the power supply cable are separate and each grounded at one
end
1 Temperature sensor 2 Shielding over the sensor insulated 3 Sensor connection cable 4 Shielding of transmitter housing insulated
5 Transmitter housing grounded 6 Shielding of transmitter housing insulated 7 Supply voltage cable 8 Grounding point 9 Supply
isolator / DCS-entry
1 2 3 6
4
7 A10272
Fig. 23: The shielding of the sensor connection cable and the shielding of the power supply cable are connected electrically via the
transmitter housing and grounded at one end
1 Temperature sensor 2 Shielding to the sensor insulated 3 Sensor connection cable 4 Shielding over transmitter housing electrically
connected 5 Transmitter housing not grounded 6 Power supply cable 7 Grounding point 8 Supply isolator / DCS-entry
8
9
1 2 3 4 6 7
8 8 A10274
Fig. 24: The shielding of the sensor connection cable and the shielding of the power supply cable are separate and each grounded at one
end
1 Temperature sensor 2 Shielding over the sensor grounded 3 Sensor connection cable 4 Shielding of transmitter housing insulated
5 Transmitter housing grounded 6 Shielding of transmitter housing insulated 7 Supply voltage cable 8 Grounding point 9 Supply
isolator / DCS-entry
3 max. Ø 12 (0.47)
4
8 (0.31)
1 1 1 1 1 1 1 1 1
I 2 2 2 2 2 2
J J
J J J
3 3 3 3 3 3 3 3 3
+
K
4 4 4 4 4 -
J
J 5 5 L
J
6 6 6 M
A10254-01
Fig. 26
A Potentiometer, Four-wire circuit B Potentiometer, Three-wire circuit C Potentiometer, Two-wire circuit D 2 x RTD, Three-wire circuit1)
E 2 x RTD, Two-wire circuit1) F RTD, Four-wire circuit G RTD, Three-wire circuit H RTD, Two-wire circuit I Sensor 1 J Sensor 21)
K 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus L Interface for LCD-indicator and Service M Grounding brackets for sensor
and supply / signal line - shielding
1 – 6 Sensor connection (of measuring inset)
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
1 1 1 1 1 1 1 1
- - - -
H + + + +
2 2 2 2 2 2 2
J
J J
3 3 3 3
+
J
4 4 -
5 5 + 5 +
5 +
5 5 K
+ +
I - - - - -
6 6 6 6 6 6 L A10255-01
Fig. 27
A 2 x Voltage measure 1) B 1 x Voltage measure C 2 x Thermocouples element1) D 1 x Thermocouples E 1 x RTD, Four-wire circuit
and thermocouple 1) F 1 x RTD, Three-wire circuit and thermocouple 1) G 1 x RTD, Two-wire circuit and thermocouple1) H Sensor 1
I Sensor 21) J 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus K Interface for LCD-indicator and service L Grounding
brackets for sensor and supply / Signal line - shielding
1 – 6 Sensor connection (of measuring inset)
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
Change from one to two columns
Sensor short circuit < 5 Ω (for resistance thermometers) Sensor error signaling
— Thermocouple: wire break
Sensor wire break — Linear voltage measurement: wire break
— Measuring range: 0 ... 500 Ω > 0.6 ... 10 kΩ
— Measuring range: 0 ... 5 kΩ > 5.3 ... 10 kΩ Functionality input
Free style characteristic curve / 32-point -sampling point table
Corrosion detection in accordance with NE 89 — Resistance measurement up to max. 5 kΩ
— Three-wire resistance measurement > 50 Ω — Voltages up to max. 1.1 V
— Four-wire resistance measurement > 50 Ω
Sensor error adjustment
Sensor error signaling — Via Callendar-Van Dusen coefficients
— Resistance thermometer: Sensor short circuit and sensor — Via value table of 32 reference points
wire breakage — Via single-point adjustment (offset adjustment)
— Linear resistance measurement: Sensor wire break — Via two-point adjustment
Input functionality
— 1 sensor
— 2 sensors:
mean measurement,
differential measurement,
sensor redundancy,
Sensor drift monitoring
Block structure
— Physical Block
— Transducer Block 1 – temperature
— Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
— Analog Input 1 – Primary Value (Calculated Value1))
— Analog Input 2 – SECONDARY VALUE_1 (sensor 1)
— Analog Input 3 – SECONDARY VALUE_2 (sensor 2)
— Analog Input 4 – SECONDARY VALUE_3 (reference
junction temperature)
— Analog Output – optional HMI display (Transducer Block 2)
— Discrete Input 1 – enhanced diagnosis 1 (Transducer Block 3)
— Discrete Input 2 – enhanced diagnosis 2 (Transducer Block 3)
1) Sensor 1, sensor 2 or difference or mean
US = 11 ... 30 V DC
U1min: Minimum supply voltage on the transmitter
Max. permissible residual ripple for input terminal voltage U2min: Minimum supply voltage of the supply isolator /
— During communication in accordance with HART FSK DCS input
"Physical Layer" specification. R: Line resistance between transmitter and supply
isolator
Undervoltage detection on the transmitter R250: Resistance (250 Ω) for HART functionality
— If the terminal voltage on the transmitter falls below a
value of 10 V, this may lead to an output current of Ia ≤ Standard application with 4 ... 20 mA functionality
3.6 mA. When connecting these components, observe the following
condition:
Maximum load U1min ≤ U2min - 22 mA x R
— RB = (supply voltage – 11 V) / 0.022 A
Standard application with HART functionality
By adding the resistance R250 , the minimum input terminal
voltage U2min: U1min ≤ U2min - 22 mA x (R + R250) can be
increased.
NOTICE
Transmitter communication and configuration via HART,
PROFIBUS PA, and FOUNDATION Fieldbus H1 are
described in separate documentation ("Interface
description").
NOTICE
Unlike configuration using the DTM or EDD, the functionality
of the transmitter can only be changed to a limited extent if
the LCD indicator is used.
1 2 Menu name 3
On 4
1 2
2
5 Exit Select 5
Process display
Configuration level
Device Setup
Device Info
Display
Process Alarm
Communication
Calibrate
Diagnosis
Process display
The process display shows the current process values.
Configuration level
The configuration level contains all the parameters required for device commissioning and
configuration. The device configuration can be changed on this level.
Process display
Process display
The process display shows the current process values.
Information level
The information level contains the parameters and information that are relevant for the operator.
The device configuration cannot be changed on this level.
Configuration level
The configuration level contains all the parameters required for device commissioning and
configuration. The device configuration can be changed on this level.
Change from one to two columns
25.7
the bottom of the process display.
2
°C Process display
PV 100%
3 4 3 Application F72
A11124
Fig. 32: Process display (example)
1 Measuring point tagging (device TAG) 2 Current process values The diagnostic messages are divided into the following groups
3 "Button function" symbol 4 "Parameterization protected" in accordance with the NAMUR classification scheme:
symbol
Symbol - Description
The process display appears on the LCD display when the Letter
device is switched on. It shows information about the device I OK or Information Device is functioning or information
and current process values. is available
The way in which the current process values are shown can C Check Function Device is undergoing maintenance
be adjusted on the configuration level. (e. g. simulation)
The symbols at the bottom of the process display are used to S Off Specification Device or measuring point is being
indicate the functions of the operating buttons and , in operated outside of the
addition to other information. specifications
M Maintenance Request service to prevent the
Symbol Description Required measuring point from failing
Call up information level. F Failure Error; measuring point has failed
Call up configuration level.
The device is protected against changes of the parameter The error can then be read in plain-text format on the
settings. "Diagnostics" information level.
Range Description
Electronics Diagnosis for device hardware.
Sensor Diagnosis for sensor elements and connection
lines.
Installation / Diagnosis for communication interface and
Configuration parameterization / configuration
Operating conditions Diagnosis for ambient and process conditions.
NOTICE
For a detailed description of the errors and information on
troubleshooting, see chapter "Possible HART error
messages" on page 45.
Electronics
1. Open the using Operator Menu.
The error messages are divided into four groups in
accordance with the NAMUR classification scheme. The group Operator Menu
assignment can only be changed using a DTM or EDD: Diagnosis
Operator Page 1
Symbol Description Operator Page 2
Error / failure
Back Select
Function check
2. Select the desired submenu using / .
Outside of the specification 3. Confirm the selection with .
Next OK
Menu name
Parameter name
Currently set value 3. Use to select the decimal place to change.
4. Use / to set the desired value.
5. Use to select the next decimal place.
Next Edit 6. If necessary select and set additional decimal places in
accordance with steps 3 to 4.
1. Select the parameters you want to set in the menu. 7. Use to confirm your setting.
2. Use to call up the list of available parameter values. This concludes the procedure for changing a parameter value.
The parameter value that is currently set is highlighted.
NOTICE
This overview of parameters shows all the menus and parameters available on the device. Depending on the version and
configuration of the device, not all of the menus and parameters may be visible in it.
Diagnosis 7 Looptest
Device status
Temp. of Electronics
Sensor 1 process data
Sensor 2 process data
NOTICE
This overview of parameters shows all the menus and parameters available on the device. Depending on the version and
configuration of the device, not all of the menus and parameters may be visible in it.
Sensor 2
Display 5 Language
Contrast
Operator Page 1 Line 1
Operator Page 2
Line 1
Line 2
1) PROFIBUS PA only
… / … / Device temperature
min Drag indicator: minimum device temperature
max Drag indicator: maximum device temperature
… / … / Sensor 1
min Drag indicator: minimum sensor temperature, sensor 1
max Drag indicator: maximum sensor temperature, sensor 1
… / … / Sensor 2
min Drag indicator: minimum sensor temperature, sensor 2
max Drag indicator: maximum sensor temperature, sensor 2
… / … / Operator Page 1
Line 1 Selects the value displayed
— Calculated value
— Sensor 1
— Sensor 2
— Device temperature
— AO Block
NOTICE
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
NOTICE
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
Change from one to two columns
16 Declaration of conformity
NOTICE
Declarations of conformity of the device are available in the
download center of ABB at www.abb.com/temperature.
They are additionally enclosed with the device for ATEX
certified devices.
Trademarks
® HART is a registered trademark of FieldComm Group, Austin, Texas,
USA
® PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS
& PROFINET International (PI)
® FOUNDATION Fieldbus is a registered trademark of FieldComm Group,
Repair and / or maintenance work will only be performed on devices and components if a statement form has been completed
and submitted.
Otherwise, the device / component returned may be rejected. This statement form may only be completed and signed by
authorized specialist personnel employed by the operator.
Customer details:
Company:
Address:
Contact person: Telephone:
Fax: E-Mail:
Device details:
Typ: Serial no.:
Reason for the return/description of the defect:
Was this device used in conjunction with substances which pose a threat or risk to health?
Yes No
If yes, which type of contamination (please place an X next to the applicable items)?
Biological Corrosive / irritating Combustible (highly / extremely combustible)
Toxic Explosiv Other toxic substances
Radioactive
We hereby state that the devices / components shipped have been cleaned and are free from any dangerous or poisonous
substances.
Notes
Notes