05
Replaces: 08.98
1/8
Typ VT-PVNR-1
Series 1X
H5484_d
Further information:
– Commissioning instruction for VT-PVNR1, see RE 30138-B
Card holder:
– Type VT 3002-2X/48, see RE 29928 Plug-in card holder
without power pack
Power pack:
– Type VT-NE30-1X, see RE 29929
Power pack 115/230 VAC → +25 VDC, 60 W (smoothed) and
+24 VDC, 25 W (regulated)
2/8 Bosch Rexroth AG Hydraulics VT-PVNR-1 RE 30138/12.05
Ordering code
VT-PVNR-1 1X *
Technical Data (For applications outside these parameters, please consult us!)
Functional description
The closed loop control electronics PVNR-1 can be used to The following can be adjusted on the front panel:
run electro-hydraulic rotary drives either in the open or closed Offset actual value: Zero point adjustment of the speed
loop control mode. The operating modes „open loop control“ commmand value
or „closed loop control“ are fed forward via a PLC-compatib-
le input. Via differential input [2], and optionally via a time ramp Offset nominal value: Zero point adjustment of the actual
[6], the analog command value for the closed loop speed con- speed value
trol circuit, and via the differential input [1] the actual value, is
fed to the P-controller [3] and the I-component [5]. The actu- Ramp slope for increasing and decreasing command
al value can be added to the output signal of the PI-controller values by means of rotary switches
using a derivative unit [4]. In addition, it is possible to apply the
command value to the output of the PID-controller [9]. All the PL Adjustment of the P-component for the controller
controller parameters can be set by means of rotary switches using rotary switches (fine adjustment)
at the front. For valves with positive overlap a step function ge-
nerator [7] can be used to compensate for the overlap. PH Adjustment of the P-component for the controller
using rotary switches (rough adjustment)
The output signal of the PVNR-1 is fed to the optional plug-in
card PVE1 for the control of valves. Moreover, a 20z connec-
I Adjustment of the I-component for the controller
tion is available for valves with integral electronics.
using rotary switches
A further, optional plug-in board converts digital-incremental
signals from rotary pulse encoders into an analog, normalized D Adjustment of the D-component for the controller
voltage for the closed loop control. using rotary switches
If the deviation of the actual speed value from the speed com-
mand value is smaller than a settable threshold [8], this is sig- The following can be adjusted on the electronic card:
nalled by an LED on the front panel and by a PLC output S1.1 and S1.2 Command value application
(connection 14d). (33 %; 66 %; 100 %)
The following measuring sockets are available at the front panel: S1.3 Firm setting "on"
Measuring socket 1: Actual speed value (nominal value drive speed) S1.4 and S1.5 Threshold for "Speed reached"
Measuring socket 2: Actual speed value (actual value drive speed) (50 mV to 500 mV)
Measuring socket 3: Valve command value (nominal value valve) S1.6 to S1.9 Actual speed value gain (1 to 2)
Measuring socket 4: Actual valve value (actual value valve)
Measuring socket 5: Integrator For valves with positive overlap a command value jump can be
Measuring socket ⊥: Measuring zero set in dependence upon the direction using potentiometers
The following is signalled by LEDs on the front panel: R200 and R201 to compensate for the spool overlap.
LED "ol" (yellow): Operating mode "OPEN LOOP CONTROL"
LED "cl" (yellow): Operating mode "CLOSED LOOP CONTROL" [ ] = Reference in the block circuit diagram
LED "en" (green): Enable of PVNR-1
LED " " (yellow): Speed reached
Rotary encoder
analog / PVNR-1 Actual valve value analog /
incremental
f/U- incremental
converter Output stage
n
(optional) PID- u
controller ±10 V
Speed command Comm. value Motor
(optional)
value ±10 V generation
A D A B
Enable integrator
a b
Enable valve command value
Open/closed loop control P T
I/O
PLC +24 V Speed reached =24 V
Speed controller active =24 V
Cable break =0 V
4/8
Rexroth
Jump
R200 R201
KB BEG P IST
Bosch Rexroth AG
1 2 3 4 5 6 7 8 9 1 2
ol Offset actual value
Hydraulics
F012
CDE
34 5 6
B
78
9A
F012
CDE
34 5 6
B
9A
78 PL
F012
Position of adjustment and indicator elements
CDE
34 5 6
B
78 PH
9A
F012
CDE
34 5 6
B
9A
78 I Plug-in card PVE1
X4
X3
CDE
34 5 6
B
9A
78 D VT-PVNR-1-1X/DX
1 2 1 nominal value drive speed (option)
2 actual value drive speed
3 4 3 nominal value valve
4 actual value valve X2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
5 ⊥ 5 Integrator 1 9
ol open loop
cl closed loop
9
10
11
12
en enable
PVNR-1
VT-PVNR-1
RE 30138/12.05
F
X1 2 X1
F
offset 8z
actuel value Actual speed value (test output)
10z
Actual speed value 2b 1 S1.6 - 1.9 16 D 16 F UA2
12z
(±10 V) u
4 UA2 Rotary pulse encoder
10b
UA1 (input)
RE 30138/12.05
u 12b
– 2,5 V + 2,5 V UA1
4b F 8b
1 S1.1/2 4
Reference potential 9 ⊥ –15 V+15 V Actual speed value ±10 V (output)
6b X2 1 2 3 4 5 6 7 8 9
Shield
7 11
P 16
L
offset F F
P 16
VT-PVNR-1
X4 Valve enable
VTS 0021 10 26z
F
X3 1 2 3 4 5 6 7 8 9 28z
6 Shield
30db + 15 V ⊥ +24V
+ 24 V =
GND 24d –
32db Connec-
GND = 22d + Solenoid A
– 15 V tions for
F 22b
cl 1 Position proporti-
24b
26b
2 measu- onal valve
⊥ ring
6d 28b System type 4WRE
Enable integrator + 15 V Shield (series 1X)
28d
Enable integrator –
26d
Enable valve 4d S1.4/5 4 + Solenoid B
75 mV – 500 mV
command value Enable valve 20d
Speed reached & +24 V (PLC)
Open/closed loop 8d comm. value
F Imax = 15 mA 14d
Open/closed loop F
control en Speed reached
control 8
F Imax = 15 mA 12d
18d ol Speed controller active
GND (PLC) Cable break
Imax = 15 mA 16d Message cable break (0 V = fault)
position measuring system/rotary
1, 2 Differential amplifier
pulse enconder
Hydraulics Bosch Rexroth AG
X2
Enable valve 10
comm. value
1
1 23 6
TTL HTL
J3 S1/2 – S1/5
4 bit
UA2
1 2
2 UA1 1 J1
UA2 1:1 f Actual
3 2 4 5
UA1 1:2 speed
4 UA2 3
UA1 1:4 U value
4
1
=1
6 – +
GND
S1/1
7 Supply
– 15 V 3
8 voltage
+ 15 V
5
1 Line driver
2 Signal evaluation
3 Detection of direction
4 Frequency/voltage converter
5 Sign selection for actual speed value
6 Cable break monitoring
Functional description
X4 X3
8 8
+ 15 V GND
7 9
– 15 V 24 V
6
⊥
1
u
i 2
b
Command 1 4WRE 6
value + PID 7 or
3
4WRE 10
1 2 6 a
u
3 i 7
Comm. value u
4 i
optional
& 4
Enable comm. 9
value
5
Cable break
6
3
Actual valve 2 = 5 1 8
value ≈
4 2
5
Functional description
The auxiliary electronics PVE1 allow to control directly con- inductive position transducer [8].
trolled proportional directional valves type 4WRE 6 ..-1X or In the case of a fault or if the command value enable is not ap-
4WRE 10 ..-1X (see ordering code). plied, solenoids "a" and "b" are de-energized.
The plug-in card basically offers the following function
modules:
[ ] = Reference in the block circuit diagram
– Self-pulsing output stages
– Oscillator and demodulator for inductive position
On the auxiliary card no adjustments or settings are
measurement of the valve spool
required!
– PID-controller
– Cable break detection of the position transducer cable
– Enable logic
The command value is fed to the PID valve controller [2] via
the analog switch [1]. The oscillator/demodulator [5] is used
to determine the actual value, which is proportional to the val-
ve spool position. The controller is optimized for valve types
4WRE 6 or 4WRE 10 and controls the self-pulsing valve out-
put stage [3] in dependence upon the command/actual value
difference.
The cable break detection [6] monitors the connection to the
8/8 Bosch Rexroth AG Hydraulics VT-PVNR-1 RE 30138/12.05
Note! Electrical signals generated via control electronics (e.g. actual value) must not be used for
switching safety-relevant machine functions!
(see also the European standard "Safety requirements for fluid power
systems and components - Hydraulics", EN 982)
The commissioning of the PVNR-1 control electronics is comprehensively described in the brochure RE 30138-B
(separate order)!
Rexroth
34 5 6
78
B
9A
3HE (128,4)
F012
C DE
PL
34 5 6
78
B
9A
F012
100
89
PH
C DE
34 5 6
78
B
9A
F012
I
C DE
34 5 6
78
B
9A
F012
D
C DE
34 5 6
78
B
9A
cl closed loop
en enable
PVNR-1
8TE (40,3) 2
10 165
184
Bosch Rexroth AG © This document, as well as the data, specifications and other
Hydraulics information set forth in it, are the exclusive property of Bosch Rexroth
Zum Eisengießer 1 AG. Without their consent it may not be reproduced or given to third
97816 Lohr am Main, Germany parties.
Telefon +49 (0) 93 52 / 18-0 The data specified above only serve to describe the product. No
Telefax +49 (0) 93 52 / 18-23 58 statements concerning a certain condition or suitability for a certain
documentation@boschrexroth.de application can be derived from our information. The given information
www.boschrexroth.de does not release the user from the obligation of own judgement and
verification. It must be remembered that our products are subject to a
natural process of wear and aging.