Table of Contents
WELCOME TO THE WINDOWS® 7 OPERATING SYSTEM MANUAL INSTALLATION INSTRUCTIONS ..............3
1.1 Begin Installation..............................................................................................................................................4
1.2 Remove existing partitions...............................................................................................................................4
1.3 Load mass storage device driver.....................................................................................................................4
1.4 Create partitions...............................................................................................................................................5
1.5 Install Windows 7 .............................................................................................................................................5
1.6 Setup for first user............................................................................................................................................5
1.7 Setup Desktop Icons........................................................................................................................................6
1.8 Complete the Disk Partitioning Properties .......................................................................................................6
1.9 Set up Advanced System Properties ...............................................................................................................7
1.10 Disable User Account Control..........................................................................................................................8
1.11 Change Action Center Settings .......................................................................................................................8
1.12 Download Drivers.............................................................................................................................................8
1.13 Install Drivers ...................................................................................................................................................8
1.14 Configure the Display Properties .....................................................................................................................9
1.15 Configure the Network Interface Cards (NICs) ................................................................................................9
1.16 Set Power Options .........................................................................................................................................11
1.17 Disable Windows Firewall ..............................................................................................................................12
1.18 Enable the Administrator Account .................................................................................................................12
1.19 Configure the Administrator Account .............................................................................................................13
1.20 Configure the Default Profile..........................................................................................................................13
1.21 Activate Windows...........................................................................................................................................15
SPECIAL INSTRUCTIONS ........................................................................................................................................16
2.1 DeltaV NIC Binding Order..............................................................................................................................16
2.2 DeltaV NIC Binding Order continued .............................................................................................................17
2.3 Joining an Active Domain ..............................................................................................................................18
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 2 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
IMPORTANT: Installation of the operating system should be done using an Emerson provided
Windows 7 image. These instructions are ONLY supported when the operating system is being
installed on a supported computer ordered from the Emerson price book where it is not possible to
use the Windows 7 image recovery disk on that computer (for example, legacy hardware). It is not
supported to use these instructions on any other computer and, if done, is at the customer's risk as a
non-standard, unsupported installation.
Check the hardware compatibility table before starting this procedure. Hardware not listed for Windows 7
is not supported and may not function correctly with Windows 7 or DeltaV. Hardware listed but having no
drivers on the Resource DVD are compatible but may have limited functionality.
NOTE: The Product Key is your license to use Windows 7. It is located on a sticker inside the plastic
container for your DVDs. DO NOT DISCARD THE CONTAINER, PRODUCT KEY, OR THE DVDs!
DISCARDING THESE ITEMS WILL PREVENT YOU FROM REINSTALLING WINDOWS 7.
NOTE: Some platforms require a mass storage device driver pre-loaded during installation (for
example, SATA, RAID, and so forth). Before beginning the procedure copy and unpack the driver to
a floppy disk or flash key and insert the floppy disk or flash key.
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 3 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 4 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 5 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
NOTE: If you do not have the EmersonPM1.bmp file, you can get it at:
FTP://FTP.Emersonprocess.com/Pickup/FRStech/EmersonPM1.zip (size 24kb)
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 7 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
NOTE: If no folders exist on the FTP site for your platform, skip this section
and skip the Install Drivers section. The drivers are native to the operating
system.
NOTE: DO NOT use a live LAN cable already connected to a DHCP server as
this will assign an IP address.
On a computer with two integrated NICs, use the first add-in NIC.
5. Observe which Local Area Connection becomes active (No red X).
6. Right click the active Local Area Connection.
7. Click Rename.
8. Rename that Local Area Connection 'Plant LAN'.
9. Disconnect the LAN cable from the Plant LAN NIC.
10. Plug a LAN cable into the first add in NIC.
NOTE: On computers with two integrated NICs, USE the first integrated NIC.
11. Observe which Local Area Connection becomes active (No red ‘X’).
12. Right click on the active Local Area Connection.
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 9 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
17. Observe which Local Area Connection becomes active (No red X).
18. Right click on the active Local Area Connection.
19. Click Rename.
20. Rename that Local Area Connection 'DeltaV Secondary'.
21. Disconnect the LAN cable from the DeltaV Secondary NIC.
22. Right click on the DeltaV Primary NIC.
23. Click Properties.
24. Click Configure.
25. Click the Power Management tab.
26. Uncheck Allow this device to wake the computer.
27. Uncheck Allow the computer to turn off this device to save power.
28. Click OK.
29. Repeat the above for the DeltaV Secondary and Plant LAN NICs.
30. Right-click the DeltaV Primary NIC.
31. Click Properties.
32. Uncheck Internet Protocol Version 6 (TCP/IPv6).
33. Highlight Internet Protocol Version 4 (TCP/IPv4).
34. Click Properties.
35. Click the Use the following IP address radio button.
36. Enter an IP address of '10.4.0.1'.
37. Enter a Subnet mask of '255.254.0.0'.
38. Click OK.
39. Click Close.
40. Repeat the process for the DeltaV Secondary NIC using an IP address '10.8.0.1' and Subnet mask of
'255.254.0.0'.
41. Repeat the process for the Plant LAN NIC using an IP address of '192.168.1.1' and a Subnet mask of
'255.255.255.0'.
42. If a fourth NIC exists, repeat the process for the spare NIC using an IP address of '192.168.10.1' and a
Subnet mask of '255.255.255.0' or any appropriate address.
NOTE: An other appropriate IP address and subnet mask can be used on the Plant LAN as required.
43. Press the ALT key.
44. Click Advanced.
45. Click Advanced Settings.
46. Highlight one of the NICs in the Connections box and use the UP and DOWN arrow keys to arrange
the NICs to provide a binding order of 1) DeltaV Secondary, 2) Plant LAN 3) DeltaV Primary, 4) Spare
or Remote Access connections. Refer to the section 2.1 - DeltaV NIC Binding Order for the exact order.
47. Click OK.
48. Click the X in the upper-right hand corner of Network Connections to close it.
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 10 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 11 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 12 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
NOTE: This concludes the Windows 7 Installation. Restart the system and log
on normally
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 14 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 15 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
SPECIAL INSTRUCTIONS
2.1 DeltaV NIC Binding Order
Windows® 7 binds communication protocols to the physical Network Interface Cards (NIC) in a particular order.
That order can affect the performance of engineering a DeltaV system. The following is a listing of the NIC
configurations and the binding order that will optimize your DeltaV system.
A PC with redundant Control Network and a plant LAN not configured as an RDS (3 NICs -
default).
1. DeltaV Secondary
2. Plant LAN
3. DeltaV Primary
A PC with simplex Control Network and a plant LAN, not configured as an RDS (2 NICs).
1. DeltaV Primary
2. Plant LAN
A PC with redundant Control Network configured as a Remote Data Sever (RDS) with a
simplex remote network (3 NICs).
1. DeltaV Secondary
2. Remote Primary
3. DeltaV Primary
A PC with simplex Control Network configured as an RDS with a simplex remote network (2
NICs).
1. DeltaV Primary
2. Remote Primary
A PC with redundant Control Network and configured as an RDS with a redundant remote
network (4 NICs).
1. DeltaV Secondary
2. Remote Secondary
3. DeltaV Primary
4. Remote Primary
Revision 20100901
© Emerson Process Management, 2010, All Rights Reserved
Page 16 of 18
Win7_Manual_Installation.PDF
Emerson Process Management 2010
A Redundant Batch system (the Application Station) on a simplex ACN using Direct Link
Ethernet connection. (Note that the Direct Link connection is always last in the order.)
1. DeltaV Primary
2. Direct Link
A Redundant Batch system (the Application Station) on a redundant ACN using Direct Link
Ethernet connection. (Note that the Direct Link Connection is always last in the order.)
1. DeltaV Secondary
2. DeltaV Primary
3. Direct Link