Professional Documents
Culture Documents
transmitter is to amplify and convert Field Wiring field wiring for SCADA systems is kept
this raw electrical signal into the signal In addition to the 4-20 mA current separated from power wiring, especially
type that controllers in a SCADA loop, there are a variety of other types high voltage cables, to reduce the
control panel can use. Common types of signals that are used between field chance of interference.
of output signals from transmitters devices and SCADA control panels.
are 4-20 mA current loops, pulse These include hardwired on/off signals, SCADA Control Panels
outputs, and digital communications pulse signals, and a variety of field- and Controllers
busses. These days most transmitters busses. Traditional signals types, such The next set of components after the
are electronic and can also implement as the on-off signals or current loops, field wiring is the SCADA control
signal processing such as offsets, typically allow one type of informa- panels. In SCADA control panels,
damping, error correction, and basic tion to be transmitted per pair of the field wiring is terminated into
calculations. Many transmitters also wires. Field-level networks, which run terminal blocks, which in turn are
have local measurement readouts on protocols such as MODBUS, HART, then wired to the I/O terminals on the
them as well. or Profibus, allow controllers to talk SCADA system’s controllers. You may
The 4-20 mA current loop is a directly to devices or instruments; this have heard any number of acronyms
commonly used output signal from allows a single pair of wires to be used to describe the typical controller;
transmitters so it is worth explaining to transmit multiple pieces of data in PLC, RTU, PAC or perhaps you have
why this signal type is used. The mA both directions, just like between two a distributed control system (DCS)
in this case refers to milli-amperes, a computers on a network. as opposed to a traditional SCADA
measure of current. In a current loop, The ‘field wiring’ is the actual system. You can get lost in a sea of
the current signal is proportional to wiring that conveys the signals from acronyms trying to understand the
the value being transmitted. Thus if field devices to the SCADA control difference between controller types
a flow meter is set up to measure panels. Field wiring can take many but for our purposes they are all
0-500 L/s, and it is transmitting a forms, but it is usually run in conduit, just flavours of the same thing: a
250 L/s signal, the output signal would as armored cables, or in cable trays. specialized computer that is used to
be 50% of the 4-20 mA, which is For on/off signals, a combination read-in, interpret, process, and output
12 mA. Likewise for a 0 L/s reading of 120-volt and 24-volt signals is electrical signals to/from the field.
in the example, the output would be typically used. The 120-volt control If we use our flow meter example,
4 mA; and for a reading of 125 L/s, wiring is more often seen in motor the reading of the flow meter is read
the reading would be 8mA. Notice control circuits, whereas 24-volt wires into the controller via the field wiring
how the current loop is set up as commonly used for field devices such as and converted into a value (e.g., 50 L/s)
4-20 mA, not 0-16 mA, so it uses a pressure switches. For analog signals, it that is stored in a ‘memory register’
‘live zero’ signal of 4mA for a zero is best to use shielded cables which have within the controller. This register is
reading. Thus, if the signal ever drops the inner wires twisted to minimize essentially an address, like a house’s
down to 0 mA, it is immediately electromagnetic interference. Special address within a neighborhood. It
apparent that there is a broken wire. care also needs to be taken to ensure allows the controller to find a piece of
information whenever it is requested.
There are now numerous things
that can be done with a stored number
in a controller. If we use our flow
meter example, the flow reading can
be used in the controller’s automatic
control logic to ramp up the speed of
a variable frequency drive (VFD) if
the flow is too low, or cause another
process to stop if the flow exceeds a
preset value. This is where the second
part of SCADA controllers comes
into play. In addition to the controller
hardware, SCADA controllers also
need to each have a custom logic
program that has to be written for
each application. This is called the
control code, or in the case of a PLC,
the ‘PLC program.’
This type of control code is written
by a systems integrator based on a
process engineer’s description of how
Figure 4 – Interior of a typical SCADA control the process should run (referred to as
Figure 3 – Photo of SCADA Control Panels in a panel. Note the two SCADA controllers located at the Process Control Narrative) and
Motor Control Centre the top of the panel backplane is what allows the process to operate
the visualization of the process in real For example, if a pump is shown as of the process is operating abnormally
time, provided by screens, that shows ‘running’ on an HMI screen that means and requires an operator response. An
device statuses, process values, alarms a ‘running’ status signal has been sent example, would be a high level in the wet
and trends. It is also where the user can from the pump controller, via the field well at a wastewater lift station. In this
adjust process control setpoints and wiring, to a SCADA controller which case, the SCADA system would generate
modify the operation of equipment in conveyed that signal via the SCADA an alarm that would notify an operator
the real world from the comfort and network to a SCADA server. On the that corrective action is required.
safety of the control room. SCADA server, the memory register The HMI software is part of the
In a nutshell, the HMI consists of from the controller is being read into a overall SCADA software package and
a series of screens and scripts that are live tag database, which in turn is read runs on a computer terminal, often
programmed by a Systems Integrator by the software module that shows referred to as a ‘client.’ These clients
to animate icons or show alarms based the running status on the HMI screen. are served information by the SCADA
on the values present in the SCADA This status can then be conveyed by a Servers and take process setpoints from
database. Each of these screens must combination of colours (say red running, the User via the HMI to send down
be carefully designed so that there is green for stopped), animations and/or to the controllers. The system as a
enough information available to allow text status indicators on the screen. whole operates continuously by passing
a user to easily discern the current The other major task that the HMI information through its various layers
status of the process, but not be so undertakes is to generate SCADA to provide the operator with a real-time
detailed that the user is overwhelmed alarms. In the SCADA system, alarms are representation of what is happening in
by information overload. configured to notify the operator if part the plant, along with looking after all
of the automatic control details in
the background.
Call 905-544-0444
www.terratecenvironmental.com
sales@terratecenvironmental.com