GENERAL NOTES :
STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUNCTION WITH ARCHITECHTURAL
DRAWINGS.
2 REINFORCED CONCRETE SHALL HAVE A
MINIMUM COMPRESSIVE STRENGTH OF
3000 Psi AT 28 DAYS.
A) REINFORCING STEEL SHALL HAVE A MINIMUM
YIELD STRENGTH OF 60000 psi EXCEPT
STIRRUPS=40000 psi( MUGHAL SUPREME
STEEL RECOMMENDED)
B) PROVIDE TORTIONAL STEEL AT CORNERS OF
SLAB.
3. MINIMUM CLEAR COVER TO REINFORCEMENT
SHALL BE.
) SLABS = 3"
) COLUMNS =!
) BEAMS =
Iv) LINTELS = 1
V) FOOTINGS=2
4, PROVIDE HANGAR BARS #3@12"C/C IN ADDITION
O STEEL CHAIRS TO SUPPORT THE TOP STEEL
OF SLAB.
a
6.
WHERE REQUIRED A LAP OF 48 TIMES BAR
DIAMETER SHALL 8E PROVIDED FOR
REINFORCEMENT UNLESS OTHERWISE
MENTIONED ON THE DRAWINGS.
(a) MIX 1/2" AND #' AGGREGATES — IN EQUAL
PROPORTIONS.
(8) MIX DUNE AND HARROW SAND IN EQUA\
PROPORTIONS.
SLAB THICKNESS=6'' EXCEPT MENTIONED |N
DRAWINGS AND USE |.5'' SIZE AGGREGATE FOR
BLINDING CONCRETE
F THERE IS BATH OVER BATH THEN SUNKEN
HE GROUND FLOOR SLAB OF BATH 6" TO I2"
VARRIES AND PROVIDE STEEL #3 @ 9" C/C
B/S WHERE NOT PROVIDED.
SHUTTERING MUST BE RAISED |'' FOR I5
FEET SPAN AND CHECKED BEFORE
CONCRETING.
. ALL EXCAVATED SURFACES SHOULD BE
TERMITE PROOFED.
BEARING OF LINTEL MUST BE GREATER THAN
DEPTH OF LINTEL.
GENERAL NOTES.