You are on page 1of 2

Why true-rms?

Non-linear loads need a true-rms


current clamp for accurate readings Application Note

can usually be separated into


one of three categories:
1. Too much current.
2. Too much heat in the
electrical enclosure.
3. Faulty circuit breaker
(or fuse).
Your first instinct will probably
be to measure the current with
a current clamp while the load
is on. If the current is within
the circuit rating, you may be
tempted to replace the circuit
breaker.

Figure 1. One current—two readings. Which do you trust? The branch circuit above feeds a
non-linear load with distorted current. The true-rms clamp reads correctly but the average
responding clamp reads low by 32 percent.
Figure 2. A computer load.

Non-linear loads that cause


Introduction measurement errors.
Troubleshooting the electrical lower cost. They give correct
service feeding adjustable readings for linear loads such
speed motor loads can be diffi- as standard induction motors,
cult if you don’t have the right resistance heaters, and incan-
tools. New solid state motor descent lights. But when loads
drives and heating controls are non-linear, containing
often conduct non-sinusoidal semiconductors, the average
(distorted) current. In other responding meters typically
words, the current occurs in read low. Worst case non-
short pulses rather than the linear loads include small
smooth sine wave drawn adjustable speed drives (5 hp
by a standard induction motor. or less) connected line to line
The current wave shape can across two phases of a 480 V,
have a drastic effect on a three-phase system, solid state
current clamp reading. heater controls connected
Basically, there are two single phase to 240 V, or
types of current clamps computers connected to 120 V.
commonly available: “average When troubleshooting a branch
responding” and “true-rms.” circuit that suffers from circuit
The average responding units breaker tripping (or fuse blow-
are widely used and are usually ing), the cause of the trouble
Figure 3. An adjustable speed motor load.

From the Fluke Digital Library @ www.fluke.com/library


What is true-rms? Before you do that, make
two other observations: First,
analyze the load. If the load
“RMS” stands for root-mean- rms value. In other words, the contains power semiconduc-
square. It comes from a value they display is not a tors, rectifiers, SCRs, etc., be
mathematical formula that true value, but rather is a suspicious of the current clamp
calculates the “effective” value calculated value based on an reading. Second, look at the
(or heating value) of any ac assumption about the wave front panel of your current
wave shape. In electrical terms, shape. The average respond- clamp—does it say true-rms?
the ac rms value is equivalent ing method works for pure If you can’t find
to the dc heating value of a sine waves but can lead to the words true-
particular waveform—voltage or large reading errors up to rms on the front
current. For example, if a resis- 40 percent, when a wave- panel, then you
tive heating element in an form is distorted by non- probably have
electric furnace is rated at linear loads such as adjustable an average
15 kW of heat at 240 V ac rms, speed drives or computers. responding
then we would get the same The table below gives some current clamp. Figure 4. The true-
amount of heat if we applied examples of the way the two (See Figure 4.) rms clamp is labeled
240 V of dc instead of ac. different types of meters If you are on the front panel.
Electrical power system respond to different wave trying to meas-
components such as fuses, bus shapes. ure current drawn by a
bars, conductors, and thermal Current clamps come in non-linear load containing
elements of circuit breakers are two physical styles. The most semiconductors, without a true-
rated in rms current because common type is the integral rms meter, you are likely to
their main limitation has to do clamp which has the jaws, make the wrong conclusion;
with heat dissipation. If we readout, and measuring that the problem is a faulty
want to check an electrical circuit built into a stand alone circuit breaker. Replacing the
circuit for overloading, we need unit. Examples include Fluke breaker won’t help. You’ll get a
to measure the rms current and Models 335, 336, and 337. call-back with some unpleas-
compare the measured value to Look for the words true-rms ant words from your customer.
the rated value for the compo- on the front panel. To avoid this, read the sidebar
nent in question. The second style consists about true-rms, find your local
If a current clamp is labeled of a current transformer (CT)- Fluke distributor and get your-
and specified to respond to the type accessory which works self a true-rms current clamp or
true-rms value of current, it with a digital multimeter. meter that will give correct
means that the clamp’s internal Examples include Fluke readings regardless of the type
circuit calculates the heating Models i200s, 80i-400, and of load or current wave shape.
value according to the rms 80i-600A. The jaws of the If your reputation depends
formula. This method will give clamp enclose the conductor on accurate current readings
the correct heating value being measured which acts then it won’t take you long
regardless of the current wave as a transformer primary of to decide that a true-rms multi-
shape. one turn. The secondary coil meter or current clamp is the
Certain low-cost current has 1,000 turns which only reasonable choice. For
clamps which don’t have true- divides the measured current additional information call
rms circuitry, use a short cut by 1,000; i.e., the measured 1-800-443-5853 (U.S.) or
method to find the rms value. current is converted from your Fluke distributor.
These meters are specified to amps to milliamps. When the
be “average responding-rms clamp’s output leads are
indicating.” These meters plugged into the DMM’s ac
capture the rectified average of milliamp jacks, the display Fluke. Keeping your world
an ac waveform and scale the decimal reads correctly for up and running.
number by 1.1 to calculate the amps in the jaws.

Multimeter Response to Response to Response to Response to Fluke Corporation


type sine wave square wave single phase 3 ∅ diode PO Box 9090, Everett, WA USA 98206
diode rectifier rectifier Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
Average Correct 10 % high 40 % low 5-30 % low In the U.S.A. (800) 443-5853 or
responding Fax (425) 446-5116
True-rms Correct Correct Correct Correct In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
Figure 5. A comparison of average responding and true-rms units In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com/
©2002 Fluke Corporation. All rights reserved.
Printed in U.S.A. 5/2002 1260729 A-ENG-N Rev D

You might also like