You are on page 1of 6

Reference of Infrared Thermography Inspection

"
"
U{oogvtkecn"Nqcf"
"
Fkhhgtgpvkcn"Vgor0"5∅
∅"
"
" >"7£E" 7£E"/"32£E" 33£E"/"42£E" 43£E"/"62£E" @"62£E"
Oczkowo"Vgor0"5∅

>"82£E >"97£E PQTOCN" NQY" OGFKWO" JKIJ" ETKVKECN"

"
KPHQTOCVKQP"
82£E"⁄" 97£E"⁄" QH" OGFKWO" JKIJ" ETKVKECN" ETKVKECN"
322£E"" 322£E"" QXGTNQCFKPI"
"
"
KPHQTOCVKQP"
@"322£E" @"322£E" QH"JKIJ" ETKVKECN" ETKVKECN" ETKVKECN" ETKVKECN"
QXGTNQCFKPI"
"

c" d" "

Table 1(a): Symmetrical Load


Reference of Infrared Thermography Inspection

"
Tghgtgpeg"Eqpfkvkqpcn"Gzrncpcvkqp"
"
Pq0" Pqvg"
Use specific notice from vendor as temperature limit base reference.
Cutler-Hammer use minimum 75OC insulation. (See Table 3).
30"
All equipment connection including busbar, contactor, breaker, cable, capacitor,
motor and transformer exceeds its minimum temperature limit will deteriorate its
insulation.
For general reference, use:
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
40" a. 110.14(C)(1)(a) for circuits rated 100 amperes or less (14 AWG through 1
AWG conductors).
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
b.
110.14(C)(1)(b) for circuits rated over 100 amperes (larger than 1 AWG)
Termination/conductor life time will be halved at exceeding 10OC in the limit
50" temperature. The limit temperature = 60OC (if refer to point 2(a) above), or 75OC (if
refer to point 2(b) above),
Use NEC Handbook (National Electrical Code, NFPA 70) 2005 Table 310.16
60"
Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts.
70" Four level severity in infrared inspection :
Tgswktgu"oqpkvqtkpi"cpf"c"ejgem/wr"cv"vjg"
NQY"
gctnkguv"eqpxgpkgpv"vkog
OGFKWO" Tgswktgu"cvvgpvkqp

JKIJ" Tgswktgu"cvvgpvkqp"cu"uqqp"cu"rquukdng

ETKVKECN" Tgswktgu""koogfkcvg"cvvgpvkqp

80" Critical case should inform related section immediately

90" Critical case also include the happen of melting in connection

:0" Determine the level of severity, in the back ground temperature about 30OC

Table 1(b): Reference Conditional Explanation of Symmetrical Load


Reference of Infrared Thermography Inspection
"
"
Pqp/u{oogvtkecn"Nqcf"
"
Fkhhgtgpeg"Vgor0"
Dgvyggp"
Vqr"⁄"Dqvvqo"
Eqppgevkqp" >"7£E" 7£E"/"32£E" 33£E"/"42£E" 43£E"/"62£E" @"62£E"
"
"
Oczkowo"Vgor0"5∅

>"82£E >"97£E PQTOCN" NQY" OGFKWO" JKIJ" ETKVKECN"

"
KPHQTOCVKQP"
82£E"⁄" 97£E"⁄" QH" OGFKWO" JKIJ" ETKVKECN" ETKVKECN"
322£E"" 322£E"" QXGTNQCFKPI"
"
"
KPHQTOCVKQP"
@"322£E" @"322£E" QH"JKIJ" ETKVKECN" ETKVKECN" ETKVKECN" ETKVKECN"
QXGTNQCFKPI"
"

c" d" "

Table 2(a): Non-symmetrical Load


Reference of Infrared Thermography Inspection

"
Tghgtgpeg"Eqpfkvkqpcn"Gzrncpcvkqp"
"
Pq0" Pqvg"
Use specific notice from vendor as temperature limit base reference.
Cutler-Hammer use minimum 75OC insulation. (See Table 3).
30"
All equipment connection including busbar, contactor, breaker, cable, capacitor,
motor and transformer exceeds its minimum temperature limit will deteriorate its
insulation.
For general reference, use:
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
40" a. 110.14(C)(1)(a) for circuits rated 100 amperes or less (14 AWG through 1
AWG conductors).
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
b.
110.14(C)(1)(b) for circuits rated over 100 amperes (larger than 1 AWG)
Termination/conductor life time will be halved at exceeding 10OC in the limit
50" temperature. The limit temperature = 60OC (if refer to point 1(a) above), or 75OC (if
refer to point 1(b) above),
Use NEC Handbook (National Electrical Code, NFPA 70) 2005 Table 310.16
60"
Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts.
70" Four level severity in infrared inspection :
Tgswktgu"oqpkvqtkpi"cpf"c"ejgem/wr"cv"vjg"
NQY"
gctnkguv"eqpxgpkgpv"vkog
OGFKWO" Tgswktgu"cvvgpvkqp

JKIJ" Tgswktgu"cvvgpvkqp"cu"uqqp"cu"rquukdng

ETKVKECN" Tgswktgu""koogfkcvg"cvvgpvkqp

80" Critical case should inform related section immediately

90" Critical case also include the happen of melting in connection

:0" Determine the level of severity, in the back ground temperature about 30OC

;0" Compare the temperature of top and bottom connection of breaker or fuse holder.

Table 2(b): Reference Conditional Explanation of Non-symmetrical Load

"
"
Reference of Infrared Thermography Inspection"
"

"
"

"

Summary:

Please ensure that vendor’s notice is fulfilled.

Table 3: Cutler-Hammer Motor Control Center


"
"
"
"
"
Reference of Infrared Thermography Inspection"
"

"

" "
Evidence (Bushing Termination – Cable Action (Bushing Termination – Cable
Connection): Connection)

Contact Resistance (Before Being Contact Resistance (After Being


Retightened): 160µΩ Retightened): 5µΩ
Summary:

Both Contact Resistance Measurement value at 5µΩ and Infrared Thermography showed
us proper condition, thus we may use this value as base reference in the future.

Table 4: Contact Resistance Measurement Value

You might also like