Professional Documents
Culture Documents
"
"
U{oogvtkecn"Nqcf"
"
Fkhhgtgpvkcn"Vgor0"5∅
∅"
"
" >"7£E" 7£E"/"32£E" 33£E"/"42£E" 43£E"/"62£E" @"62£E"
Oczkowo"Vgor0"5∅
∅
"
KPHQTOCVKQP"
82£E"⁄" 97£E"⁄" QH" OGFKWO" JKIJ" ETKVKECN" ETKVKECN"
322£E"" 322£E"" QXGTNQCFKPI"
"
"
KPHQTOCVKQP"
@"322£E" @"322£E" QH"JKIJ" ETKVKECN" ETKVKECN" ETKVKECN" ETKVKECN"
QXGTNQCFKPI"
"
"
Tghgtgpeg"Eqpfkvkqpcn"Gzrncpcvkqp"
"
Pq0" Pqvg"
Use specific notice from vendor as temperature limit base reference.
Cutler-Hammer use minimum 75OC insulation. (See Table 3).
30"
All equipment connection including busbar, contactor, breaker, cable, capacitor,
motor and transformer exceeds its minimum temperature limit will deteriorate its
insulation.
For general reference, use:
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
40" a. 110.14(C)(1)(a) for circuits rated 100 amperes or less (14 AWG through 1
AWG conductors).
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
b.
110.14(C)(1)(b) for circuits rated over 100 amperes (larger than 1 AWG)
Termination/conductor life time will be halved at exceeding 10OC in the limit
50" temperature. The limit temperature = 60OC (if refer to point 2(a) above), or 75OC (if
refer to point 2(b) above),
Use NEC Handbook (National Electrical Code, NFPA 70) 2005 Table 310.16
60"
Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts.
70" Four level severity in infrared inspection :
Tgswktgu"oqpkvqtkpi"cpf"c"ejgem/wr"cv"vjg"
NQY"
gctnkguv"eqpxgpkgpv"vkog
OGFKWO" Tgswktgu"cvvgpvkqp
JKIJ" Tgswktgu"cvvgpvkqp"cu"uqqp"cu"rquukdng
ETKVKECN" Tgswktgu""koogfkcvg"cvvgpvkqp
:0" Determine the level of severity, in the back ground temperature about 30OC
"
KPHQTOCVKQP"
82£E"⁄" 97£E"⁄" QH" OGFKWO" JKIJ" ETKVKECN" ETKVKECN"
322£E"" 322£E"" QXGTNQCFKPI"
"
"
KPHQTOCVKQP"
@"322£E" @"322£E" QH"JKIJ" ETKVKECN" ETKVKECN" ETKVKECN" ETKVKECN"
QXGTNQCFKPI"
"
"
Tghgtgpeg"Eqpfkvkqpcn"Gzrncpcvkqp"
"
Pq0" Pqvg"
Use specific notice from vendor as temperature limit base reference.
Cutler-Hammer use minimum 75OC insulation. (See Table 3).
30"
All equipment connection including busbar, contactor, breaker, cable, capacitor,
motor and transformer exceeds its minimum temperature limit will deteriorate its
insulation.
For general reference, use:
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
40" a. 110.14(C)(1)(a) for circuits rated 100 amperes or less (14 AWG through 1
AWG conductors).
NEC Handbook (National Electrical Code, NFPA 70) 2005, Article
b.
110.14(C)(1)(b) for circuits rated over 100 amperes (larger than 1 AWG)
Termination/conductor life time will be halved at exceeding 10OC in the limit
50" temperature. The limit temperature = 60OC (if refer to point 1(a) above), or 75OC (if
refer to point 1(b) above),
Use NEC Handbook (National Electrical Code, NFPA 70) 2005 Table 310.16
60"
Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts.
70" Four level severity in infrared inspection :
Tgswktgu"oqpkvqtkpi"cpf"c"ejgem/wr"cv"vjg"
NQY"
gctnkguv"eqpxgpkgpv"vkog
OGFKWO" Tgswktgu"cvvgpvkqp
JKIJ" Tgswktgu"cvvgpvkqp"cu"uqqp"cu"rquukdng
ETKVKECN" Tgswktgu""koogfkcvg"cvvgpvkqp
:0" Determine the level of severity, in the back ground temperature about 30OC
;0" Compare the temperature of top and bottom connection of breaker or fuse holder.
"
"
Reference of Infrared Thermography Inspection"
"
"
"
"
Summary:
"
" "
Evidence (Bushing Termination – Cable Action (Bushing Termination – Cable
Connection): Connection)
Both Contact Resistance Measurement value at 5µΩ and Infrared Thermography showed
us proper condition, thus we may use this value as base reference in the future.