Professional Documents
Culture Documents
w w w . i i fi i r . o r g
Article history: This paper presents analysis of a 5.275 kW (1.5-ton) water-to-water ground source heat
Received 2 November 2012 pump (WW-GSHP) satisfying hot water needs in a 345 m2 research house operated under
Received in revised form simulated occupancy conditions. The hot water use protocol from the Building America
5 March 2013 Research Benchmark Definition claims to capture the living habits of the average American
Accepted 6 March 2013 household and its impact on energy consumption.
Available online 28 March 2013 Energy and exergy analyses provide insight on system efficiency and sources of irre-
versibility, the main cause of wasted energy. The WW-GSHP shared the ground loop with a
Keywords: 7.56 kW water to air ground source heat pump (WA-GSHP) to space condition the same
Exergy house. Understanding the performance of GSHPs is vital if the ground is to be used as a
Heat pump viable renewable energy resource.
Thermodynamics Published by Elsevier Ltd.
Renewable energy
Water heating
Ground-source
Geothermal
5
This manuscript has been authored by UT-Battelle, LLC, under Contract No. DE-AC05-00OR22725 with the U.S. Department of Energy.
The United States Government retains and the publisher, by accepting the article for publication, acknowledges that the United States
Government retains a non-exclusive, paid-up, irrevocable, world-wide license to publish or reproduce the published form of this
manuscript, or allow others to do so, for United States Government purposes.
* Corresponding author. Energy and Transportation Sciences Div., Oak Ridge National Laboratory, Oak Ridge, TN, USA. Tel.: þ1 865 576
8003; fax: þ1 865 574 8884.
E-mail address: allymr@ornl.gov (M.R. Ally).
0140-7007/$ e see front matter Published by Elsevier Ltd.
http://dx.doi.org/10.1016/j.ijrefrig.2013.03.006
1418 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
2010) at the research house serviced by a 5.275 kW (1.5-Ton) and lower heating elements for backup energy needed in case
WW-GSHP charged with 1.587 kg (56.0 oz. avoirdupois) R410A, the WW-GSHP was inoperable due to an equipment fault. The
providing approximately 227 L day1 (60 gal day1) of hot water tank’s rated energy factor (EF) for conventional electric resis-
at 49 C (120 F) is analyzed. The ground-loop antifreeze solu- tance operation was 0.92.
tion (“brine”) was a mixture of 20% (v/v) propylene glycol and A schematic of the equipment and the state points at which
water maintained at approximately 275.8 kPa gauge (40 psi measurements are recorded every 30 s and averaged over
gauge) pressure. Thermodynamic analysis is focused around 15 min periods for subsequent analysis, is shown in Fig. 2. The
the refrigerant loop identified by the control volume (dashed compressor discharge and suction pressures are measured by
line) in Fig. 1 as it exchanges energy with the ground and with pressure transducers with 0.25% full scale (FS) accuracy. Fluid
the hot water tank via their respective heat exchangers. temperatures entering the heat pump (EWT) and leaving the
heat pump (LWT) from the ground loop and DHW tank were
measured using thermistors with conductive paste in appro-
2. Ground-loop and water use priate temperature wells on the brine and hot water piping,
respectively. Refrigerant temperatures at the indicated state
The ground loop of the WW-GSHP consists of 1.9 cm (0.75 in.) points were measured with surface mounted thermistors
internal diameter high density polyethylene (HDPE) tubing liberally coated with conductive paste, tightly attached to the
with a total length of 559 m (1834 ft.), arranged in three parallel connecting lines with electrical tape and wrapped with three
circuits (6 pipes) shared with the WA-GSHP equipment for rounds of insulated tape. The thermistors had a 15 s time
space conditioning (Hughes and Im, 2012). The installed constant and a 0.2 C tolerance. The brine loop flow was
equipment is shown in Fig. 1. Note the small physical size of measured with a turbine flow meter having an accuracy of 2%
the WW-GSHP compared to the hot water tank and the WA- or better over the experienced range of flow. The DHW flow
GSHP. through the unit was determined by measuring the pressure
Water use schedules for the shower, clothes washer, and drop of the water across the water-to-refrigerant HX (HX3 in
dishwasher are shown in Table 1. Hot water use is approxi- Fig. 1) with a differential pressure transducer having 0.25% FS
mately 227 L day1 (60 gal day1) with the water temperature in accuracy. Compressor, brine, and DHW pump power were
the shower maintained close to 40.6 C (105 F). The dishwasher measured with instrumentation-grade W-W1h1 transducers,
averages 15.3 L (4.04 gal) of hot water per cycle, running four with split-core current transformers (CTs) having a minimum
cycles per week. The clothes washer averages 13.9 L (3.68 gal) of accuracy of 0.45% of reading plus 0.05% of FS. Pressure drops
hot water per cycle, running 6 cycles per week. in connecting lines were taken as 1e1.5% of the upstream
pressure, based on data supplied by the manufacturer.
A data logger was programmed to collect data every 30 s,
average the 30 s data collected over a 15 min period and save it
3. Equipment, sensors, data collection, and
for further analysis. The data analysis procedure is based on
analysis methodology
the assumption of quasi steady-state operation, which for
small heat pumps like the one studied herein is typically
A 5.275 kW (1.5 ton) WW-GSHP rated at a COP of 3.1 based on a
reached within 5 min after the compressor switches on. Quasi
source entering water temperature (EWT) of 0 C (32 F) and
steady-state is earmarked by stable thermodynamic state
load EWT of 37.8 C (100 F) provided hot water needs of the
points within the control volume and at locations 9 and 10 for
house. The WW-GSHP was connected to a 303 L (80 gal)
water flows from and to the DHW tank via HX3. The time to
seamless, blow-molded, polybutylene hot water tank, imper-
reach quasi steady-state conditions at locations 9 and 10 varied
vious to rust and corrosion. The tank came with 4.5 kW upper
from 1 to 4.5 min depending on the temperature of the water in
the tank at the start of the water flow to the heat pump via HX3.
When T9 was at its lowest value 30.3 C (86.5 F) (December) it
took 4 min of compressor run time before T10 reached its
quasi steady-state value of 48.3 C (119 F). Since compressor
run times for water heating were generally longer than 5 min,
the assumption of quasi steady-state is valid. The expansion
valve is assumed to be adiabatic. Thermodynamic properties at
the respective state points are calculated using Reference
Fluid Thermodynamic and Transport Properties Database
(REFPROP) (Lemmon et al., 2010) as a Microsoft Excel add-in
program in the data reduction and analysis spreadsheet. En-
ergy and Exergy balances and measures of performances are
tabulated for each month to provide a comprehensive set of
data on system performance.
The monthly COPs reported are the weighted average
Fig. 1 e Equipment for water heating and for space values for the month based on the compressor run time. The
conditioning installed in the basement of the 345 m2 uncertainty of the COP values is estimated to be no greater
(3714 ft2) house. The WW-GSHP and the WA-GSHP are both than 0.254. For the benefit of design engineers, exergy
connected to the same ground loop. analysis is used to identify sources of systemic inefficiencies.
1420 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
Table 1 e Schedule and duration of water use under simulated occupancy conditions.a
Shower schedule Clothes washer schedule Dishwasher schedule
Start times Daily water use Start times Days Daily water use Start times Days Daily water use
(24 h basis) (24 h basis) (24 h basis)
Gallons Liters (L) Gallons Liters (L) Gallons Liters (L)
a Shower used mixed hot and cold water at approximately 40.6 C (105 F); clothes washer and dishwasher used hot water at approximately
49 C (120 F).
There is one segment of the loop where data is slightly erro- around the refrigerant-to-DHW heat exchanger (HX3); or
neous but this does not materially alter the overall analysis using compressor maps.
and conclusions. Nevertheless, the authors consider mention The general energy balance equation applied between
of this error as being important to the discussions, analysis, various state points (Warke Jr., 1995) is given by:
and conclusions.
X X V2
X V2
dE
Q_ o þ Q_ j þ W
_ þ h þ þ gz m_ h þ þ gz m_ ¼ CV
j in
2 out
2 dt
4. Mass and energy balances (2)
The general mass balance equation is given by: where Q_ o is the thermal energy exchanged with the sur-
X X roundings at To. The thermal energies represented by Q_ j are
_
dm
¼ _
m _ ¼0
m (1) energy exchanges with additional reservoirs at temperatures
dt e i
T1,T2,T3.Tj; W _ is the rate of work (mechanical and/or elec-
Applying Eqn. (1) to the brine (ground) loop between state trical) input; h, V2/g, gz represent enthalpy, kinetic, and po-
points 7 and 8 under steady state conditions yields the brine tential energy terms, respectively; and m _ is the mass flow rate
mass flow rate, ðm _ b Þe ¼ ðm
_ b Þi ¼ m
_ b . Similarly, application of of refrigerant or of brine, as the case may be. The unsteady
Eqn. (1) between any two state points on the refrigerant loop, term, dECV/dt representing the rate of accumulation of energy
under the assumption of quasi steady-state gives the refrig- within the control volume of interest is zero under the
erant mass flow rate in the heat pump. Since there is no direct assumption of quasi steady-state invoked in the analysis;
measurement of the refrigerant mass flow rate in the system, ECV ¼ U þ (1/2)V2 þ gz and U is the internal energy of the mass
three different approaches were used to ascertain its value; within the control volume. Both, work ðWÞ _ and heat ðQ_ o ; Q_ j Þ
through mass and energy balances around the brine-to- terms are defined as positive in Eqn. (2) (Warke Jr., 1995; Myers,
refrigerant heat exchanger (HX2); mass and energy balances 2007) for energy transfer into the CV.
Fig. 2 e Schematic of WW-GSHP with connections to the ground loop and the domestic hot water tank (DHW). The state
points where measurements are taken are numbered. Control volume demarcates the system of interest from the
surroundings.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0 1421
4.1. Mass and energy balances around HX2 and HX3 GSHP to the water tank. The compressor energy consumption
is highest in the winter (132.88 kWh) and lowest during the
Applying Eqns. (1) and (2) to the refrigerant side in HX2 be- summer (67.47 kWh). More heat is extracted from the ground
tween state points 5 and 6 and once again to the brine side during winter (314.12 kWh) than during summer (226.25 kWh)
between points 7 and 8 yields the refrigerant mass flow rate for water heating.
_ r;b based on mass and energy balances around
estimate, m The ratio of compressor energy, We,Compressor to the total
HX2. Thus, energy input, Ein varied from 0.216 (September) to the highest
value of 0.295 in February. Both pumps combined used a
_ b ðh7 h8 Þ
m
_ r;b ¼
m (3) maximum of 3.3% of the total monthly energy input (in
ðh6 h5 Þ
February). Although the brine and DHW pumps did not oper-
Similarly, applying Eqns. (1) and (2) to the refrigerant side ate near their optimum efficiency, these data suggest that
between state points 3 and 4 on the refrigerant loop, and once pump efficiency is unlikely to be a dominant factor in
again between points 9 and 10 on the DHW side yields the improving WW-GSHP performance, at least for the size range,
_ r;DHW based on the mass
refrigerant mass flow rate estimate, m climate, and use patterns prevalent in this study.
and energy balances around HX3. Thus, To improve performance, an investigation of the sources of
systemic inefficiencies is identified in the following section.
_ DHW ðh10 h9 Þ
m
_ r;DHW ¼
m (4)
ðh3 h4 Þ
The refrigerant mass flow rates from Eqns. (3) and (4) as well as 5. Exergy analysis
that obtained from the compressor map, m _ map are found to be
in good agreement as shown in Table 2. The percentage error The general entropy balance equation applied between
between m _ map and m _ r;DHW ð%D1 ¼ ðm _ r;DHW m_ map Þ 100=m
_ map Þ various state points in Fig. 2 is:
is less than the percentage error between m _ map and m _
ð%D2 ¼ ðm_ r;b m
_ map Þ 100=m _ map Þ because the relative errors in
X X Q_ o X Q_ j
s_ total ¼ _ s
m _ s
m ¼ 0 (7)
temperature measurement are larger when the temperature out in
To j
Tj
differences are small (as on the brine side) than they are for the
where s_ total is the sum of the entropy generation rates due to
DHW side where the temperature differences are larger.
internal irreversibilities and those due to irreversible heat
Further analysis is based on the refrigerant mass flow rates
transfer between the particular control volume encompassing
obtained from the compressor map.
the state points, and the surroundings.
The irreversibility, or equivalently, the availability
4.2. Energy analysis and COP destruction, which are both equal measures of the loss op-
portunity of doing useful work for a control volume whose
The averaged monthly energy balances for the WW-GSHP are boundary is taken at the temperature To (or Tj) of the sur-
presented in Table 3. The total energy input is given by: roundings, is given by:
Ein ¼ We;Brine Pump þ We;Comp: þ We;DHW Pump þ We;Aux: þ We;Controls I_ ¼ To s_ or; I_ ¼ Tj s_ (8)
þ Q0;ground
Eqns. (1), (2), (7) and (8), when applied to the control volumes
(5)
encompassing the particular initial and final states, yield the
The total energy output is given by: necessary mass, energy, and entropy balances and quantifies
the extent of irreversibility or availability destruction. The
Eout ¼ QDHW þ Q0;Comp: þ losses (6) sum of all the availability destructions constitutes the sys-
The percent difference between energy input and output, (% temic inefficiency of the closed refrigerant cycle.
D ¼ (Ein jEoutj)100/Ein) is less than 4%, demonstrating good-
ness of data. Also note that the energy input (Ein) is greater 5.1. Compressor
than the absolute value of the energy output (jEoutj), with the
difference attributed to energy losses. The water heating COP Extending the control volume of the compressor to the sur-
(Table 3), defined as the ratio of the energy delivered to the roundings and noting that no heat reservoirs other than the
water tank via HX3 to the total electrical energy used by the surrounding atmosphere are in contact with this control vol-
heat pump, shows improvement from January to July as the ume essentially implies that (Q_ j ¼ 0 but Q_ o s0). This control
EWT from the brine (ground) loop gradually increases. In volume includes the initial and final state points 1 and 2,
August, there was an equipment malfunction and hence the respectively. Applying Eqns. (1), (2), (7) and (8) to the control
resistance heater in the water tank was relied on for water volume encompassing these two state points gives:
heating until the problem was rectified. Except in November
Q_ o ¼ m _e
_ map ðh2 h1 Þ W (9)
when only 0.155 kWh resistance heat was used when the
WW-GSHP was replaced with the next generation unit, the
Q_ o
remaining months (excluding August during equipment _ map ðs2 s1 Þ
s_ ¼ m (10)
malfunction), required no resistance heat. The tank resistance To
heaters are turned on only during a “lockout” fault at the WW-
GSHP, otherwise all the necessary heat is supplied by the WW- I_ ¼ sT
_ o (11)
1422
Table 2 e Energy transfer and irreversibility rates calculated from averaged monthly measured thermodynamic properties at the given state points for the WW-GSHP.
Compressor
Discharge (final state:(2)) Suction (initial state: (1)) Q_ o W_e m_ map m_ r;DHW %D1 _ r;b
m %D2 s_ I_ (W) To Run
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (K) time (h)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 80.0 3189.5 328.69 1.07326 2.2 714.3 282.91 1.05594 400.7 1350.7 0.020753 0.020685 0.33% 0.01984 4.39% 1.723 507 294.20 98.383
Feb 79.1 2957.7 327.39 1.06942 0.4 617.7 282.18 1.05870 433.2 1315.5 0.019517 0.019335 0.93% 0.01831 6.19% 1.684 495 294.10 86.950
Mar 78.1 3003.2 325.31 1.06222 2.2 654.6 283.02 1.05689 465.8 1336.3 0.020581 0.020185 1.92% 0.01933 6.09% 1.695 499 294.19 91.938
Apr 75.9 3147.8 319.73 1.04251 9.2 819.0 285.76 1.04757 552.5 1415.0 0.025387 0.024476 3.59% 0.02353 7.31% 1.751 516 294.31 63.033
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
May 76.3 3248.8 318.66 1.03710 15.6 952.5 289.30 1.04727 650.9 1499.5 0.028911 0.027870 3.60% 0.02729 5.60% 1.914 564 295.04 58.204
Jun 78.6 3286.8 321.31 1.04387 22.6 1053.4 294.67 1.05696 698.6 1526.9 0.031088 0.030083 3.23% 0.02971 4.43% 1.954 575 296.18 50.600
Jul 80.8 3342.2 323.41 1.04819 26.9 1086.5 298.66 1.06779 755.5 1529.7 0.031279 0.030167 3.55% 0.02959 5.41% 1.935 570 296.78 44.104
Aug 83.2 3385.6 328.78 1.06675 29.4 1076.9 302.36 1.08420 689.3 1468.3 0.029487 0.029329 0.53% 0.02797 5.15% 1.810 533 296.85 57.846
Sept 78.5 3314.5 321.30 1.04424 27.0 1137.3 298.12 1.06351 768.8 1518.8 0.032351 0.032469 0.36% 0.03078 4.84% 1.969 580 296.83 56.183
Oct 76.5 3354.8 318.46 1.03607 22.4 1120.5 293.69 1.05104 726.7 1525.4 0.032253 0.032195 0.18% 0.03059 5.16% 1.971 580 296.40 62.171
Nov 74.3 3238.2 316.87 1.03373 16.1 999.4 289.30 1.04499 652.4 1473.2 0.029772 0.029523 0.84% 0.02783 6.54% 1.883 554 294.37 64.883
Final state point: (3) Initial state point: (2) Q_ o a W_e m_ map _ r;DHW
m %D1 m_ r;b %D2 Rectified s_ Rectified I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 80.5 2956.8 329.32 1.07521 80.0 3189.5 328.69 1.07326 13.0 0.0 0.020753 0.020685 0.33% 0.01984 4.39% 0.04044 11.90 294.20
Feb 80.3 2951.2 329.11 1.07452 79.1 2957.7 327.39 1.06942 33.7 0.0 0.019517 0.019335 0.93% 0.01831 6.19% 0.09964 29.30 294.10
Mar 79.4 2997.7 327.21 1.06780 78.1 3003.2 325.31 1.06222 39.2 0.0 0.020581 0.020185 1.92% 0.01933 6.09% 0.11472 33.75 294.19
Apr 77.5 3143.9 322.22 1.04977 75.9 3147.8 319.73 1.04251 63.0 0.0 0.025387 0.024476 3.59% 0.02353 7.31% 0.18428 54.24 294.31
May 78.2 3240.3 321.49 1.04534 76.3 3248.8 318.66 1.03710 81.8 0.0 0.028911 0.027870 3.60% 0.02729 5.60% 0.23803 70.23 295.04
Jun 80.6 3280.8 324.30 1.05253 78.6 3286.8 321.31 1.04387 93.0 0.0 0.031088 0.030083 3.23% 0.02971 4.43% 0.26897 79.67 296.18
Jul 83.0 3333.6 326.65 1.05751 80.8 3342.2 323.41 1.04819 101.5 0.0 0.031279 0.030167 3.55% 0.02959 5.41% 0.29148 86.51 296.78
Aug 85.6 3189.2 332.15 1.07639 83.2 3385.6 328.78 1.06675 99.2 0.0 0.029487 0.029329 0.53% 0.02797 5.15% 0.28419 84.36 296.85
Sept 81.3 3252.6 325.40 1.05606 78.5 3314.5 321.30 1.04424 132.5 0.0 0.032351 0.032469 0.36% 0.03078 4.84% 0.38216 113.44 296.83
Oct 79.2 3258.7 322.46 1.04766 76.5 3354.8 318.46 1.03607 129.2 0.0 0.032253 0.032195 0.18% 0.03059 5.16% 0.37363 110.74 296.40
Nov 76.7 3170.1 320.48 1.04425 74.3 3238.2 316.87 1.03373 107.5 0.0 0.029772 0.029523 0.84% 0.02783 6.54% 0.31309 92.16 294.37
Final state point: (4) Initial state point: (3) Q_ o W_e m_ map _ r;DHW
m %D1 _ r;b
m %D2 s_ I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 42.1 2936.1 128.28 0.45812 80.5 2956.8 329.32 1.07521 4172.1 0.0 0.020753 0.020685 0.33% 0.01984 4.39% 0.324 103 317.72
Feb 42.3 2930.5 128.69 0.45948 80.3 2951.2 329.11 1.07452 3911.7 0.0 0.019517 0.019335 0.93% 0.01831 6.19% 0.303 96 317.85
Mar 42.8 2976.7 129.60 0.46225 79.4 2997.7 327.21 1.06780 4067.1 0.0 0.020581 0.020185 1.92% 0.01933 6.09% 0.313 100 318.35
Apr 44.3 3121.9 132.30 0.47032 77.5 3143.9 322.22 1.04977 4821.6 0.0 0.025387 0.024476 3.59% 0.02353 7.31% 0.370 118 319.70
May 45.1 3217.6 133.80 0.47475 78.2 3240.3 321.49 1.04534 5426.3 0.0 0.028911 0.027870 3.60% 0.02729 5.60% 0.435 139 320.48
Jun 44.7 3257.8 132.90 0.47173 80.6 3280.8 324.30 1.05253 5950.2 0.0 0.031088 0.030083 3.23% 0.02971 4.43% 0.511 164 320.48
Jul 45.5 3310.3 134.38 0.47630 83.0 3333.6 326.65 1.05751 6014.2 0.0 0.031279 0.030167 3.55% 0.02959 5.41% 0.537 173 321.32
Aug 45.3 3166.9 134.16 0.47611 85.6 3189.2 332.15 1.07639 5838.1 0.0 0.029487 0.029329 0.53% 0.02797 5.15% 0.526 169 320.30
Sept 44.8 3229.8 132.96 0.47219 81.3 3252.6 325.40 1.05606 6225.5 0.0 0.032351 0.032469 0.36% 0.03078 4.84% 0.528 169 320.61
Oct 44.9 3235.9 133.16 0.47276 79.2 3258.7 322.46 1.04766 6105.7 0.0 0.032253 0.032195 0.18% 0.03059 5.16% 0.497 159 320.69
Nov 44.2 3147.9 132.05 0.46952 76.7 3170.1 320.48 1.04425 5609.7 0.0 0.029772 0.029523 0.84% 0.02783 6.54% 0.426 136 319.87
Final state: (5) Initial state: (4) Q_ o W_e m_ map m_ r;DHW %D1 m_ r;b %D2 s_ I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 1.5 662.6 128.28 0.48602 42.1 2936.1 128.28 0.45812 0.0 0.0 0.020753 0.020685 0.33% 0.01984 4.39% 0.579 170 294.20
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
Feb 3.2 621.6 128.69 0.48942 42.3 2930.5 128.69 0.45948 0.0 0.0 0.019517 0.019335 0.93% 0.01831 6.19% 0.584 172 294.10
Mar 1.7 659.0 129.60 0.49110 42.8 2976.7 129.60 0.46225 0.0 0.0 0.020581 0.020185 1.92% 0.01933 6.09% 0.593 175 294.19
Apr 4.6 825.4 132.30 0.49444 44.3 3121.9 132.30 0.47032 0.0 0.0 0.025387 0.024476 3.59% 0.02353 7.31% 0.612 180 294.31
May 9.0 958.5 133.80 0.49565 45.1 3217.6 133.80 0.47475 0.0 0.0 0.028911 0.027870 3.60% 0.02729 5.60% 0.604 178 295.04
Jun 12.2 1061.0 132.90 0.48979 44.7 3257.8 132.90 0.47173 0.0 0.0 0.031088 0.030083 3.23% 0.02971 4.43% 0.561 166 296.18
Jul 13.1 1093.5 134.38 0.49422 45.5 3310.3 134.38 0.47630 0.0 0.0 0.031279 0.030167 3.55% 0.02959 5.41% 0.560 166 296.78
Aug 11.7 1046.7 134.16 0.49486 45.3 3166.9 134.16 0.47611 0.0 0.0 0.029487 0.029329 0.53% 0.02797 5.15% 0.553 164 296.85
Sept 14.0 1122.2 132.96 0.48871 44.8 3229.8 132.96 0.47219 0.0 0.0 0.032351 0.032469 0.36% 0.03078 4.84% 0.534 159 296.83
Oct 13.1 1091.5 133.16 0.49008 44.9 3235.9 133.16 0.47276 0.0 0.0 0.032253 0.032195 0.18% 0.03059 5.16% 0.558 165 296.40
Nov 9.8 982.5 132.05 0.48890 44.2 3147.9 132.05 0.46952 0.0 0.0 0.029772 0.029523 0.84% 0.02783 6.54% 0.576 170 294.37
Final state point: (6) Initial state point: (5) Q_ o W_e m_ map _ r;DHW
m %D1 _ r;b
m %D2 s_ I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 1.5 657.9 282.13 1.05301 1.5 662.6 128.28 0.48602 3192.8 0.0 0.020753 0.020685 0.33% 0.01984 4.39% 0.191 53 275.81
Feb 0.5 617.3 281.17 1.05491 3.2 621.6 128.69 0.48942 2976.0 0.0 0.019517 0.019335 0.93% 0.01831 6.19% 0.178 49 274.06
Mar 1.4 654.4 282.09 1.05342 1.7 659.0 129.60 0.49110 3138.3 0.0 0.020581 0.020185 1.92% 0.01933 6.09% 0.181 50 275.50
Apr 8.7 819.6 285.18 1.04541 4.6 825.4 132.30 0.49444 3881.2 0.0 0.025387 0.024476 3.59% 0.02353 7.31% 0.227 64 282.05
May 15.2 951.8 288.86 1.04563 9.0 958.5 133.80 0.49565 4482.9 0.0 0.028911 0.027870 3.60% 0.02729 5.60% 0.319 92 287.72
Jun 22.3 1053.6 294.32 1.05571 12.2 1061.0 132.90 0.48979 5018.2 0.0 0.031088 0.030083 3.23% 0.02971 4.43% 0.497 146 293.53
Jul 26.7 1085.8 298.39 1.06680 13.1 1093.5 134.38 0.49422 5130.0 0.0 0.031279 0.030167 3.55% 0.02959 5.41% 0.608 180 296.51
Aug 29.2 1039.4 302.13 1.08334 11.7 1046.7 134.16 0.49486 4953.0 0.0 0.029487 0.029329 0.53% 0.02797 5.15% 0.735 219 298.08
Sept 26.8 1114.4 297.91 1.06275 14.0 1122.2 132.96 0.48871 5336.4 0.0 0.032351 0.032469 0.36% 0.03078 4.84% 0.601 179 296.97
Oct 22.2 1083.9 293.38 1.04988 13.1 1091.5 133.16 0.49008 5167.6 0.0 0.032253 0.032195 0.18% 0.03059 5.16% 0.454 133 293.59
Nov 15.8 975.6 288.90 1.04354 9.8 982.5 132.05 0.48890 4669.7 0.0 0.029772 0.029523 0.84% 0.02783 6.54% 0.320 92 288.38
Final state point: (1) Initial state point: (6) Q_ o W_e m_ map _ r;DHW
m %D1 m_ r;b %D2 s_ I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Jan 2.2 714.3 282.91 1.05594 1.5 657.9 282.13 1.05301 16.2 0.0 0.020753 0.020685 0.33% 0.01984 4.39% 0.006 1.65 294.20
Feb 0.4 617.7 282.18 1.05870 0.5 617.3 281.17 1.05491 19.7 0.0 0.019517 0.019335 0.93% 0.01831 6.19% 0.007 2.01 294.10
1.92% 6.09%
1423
Mar 2.2 654.6 283.02 1.05689 1.4 654.4 282.09 1.05342 19.2 0.0 0.020581 0.020185 0.01933 0.006 1.86 294.19
Final state point: (1) Initial state point: (6) Q_ o W_e m_ map m_ r;DHW %D1 _ r;b
m %D2 s_ I_ To
(W) (W) (kg s1) (kg s1) (kg s1) (W K1) (W) (K)
T P h s T P h s
( C) (kPa) (kJ kg1) (kJ kg1 K1) ( C) (kPa) (kJ kg1) (kJ kg1 K1)
Apr 9.2 819.0 285.76 1.04757 8.7 819.6 285.18 1.04541 14.8 0.0 0.025387 0.024476 3.59% 0.02353 7.31% 0.004 1.28 294.31
May 15.6 952.5 289.30 1.04727 15.2 951.8 288.86 1.04563 12.9 0.0 0.028911 0.027870 3.60% 0.02729 5.60% 0.003 1.02 295.04
Jun 22.6 1053.4 294.67 1.05696 22.3 1053.6 294.32 1.05571 10.7 0.0 0.031088 0.030083 3.23% 0.02971 4.43% 0.003 0.82 296.18
Jul 26.9 1086.5 298.66 1.06779 26.7 1085.8 298.39 1.06680 8.5 0.0 0.031279 0.030167 3.55% 0.02959 5.41% 0.002 0.72 296.78
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
Aug 29.4 1076.9 302.36 1.08420 29.2 1039.4 302.13 1.08334 6.9 0.0 0.029487 0.029329 0.53% 0.02797 5.15% 0.002 0.63 296.85
Sept 27.0 1137.3 298.12 1.06351 26.8 1114.4 297.91 1.06275 6.6 0.0 0.032351 0.032469 0.36% 0.03078 4.84% 0.003 0.77 296.83
Oct 22.4 1120.5 293.69 1.05104 22.2 1083.9 293.38 1.04988 10.2 0.0 0.032253 0.032195 0.18% 0.03059 5.16% 0.003 0.86 296.40
Nov 16.1 999.4 289.30 1.04499 15.8 975.6 288.90 1.04354 11.7 0.0 0.029772 0.029523 0.84% 0.02783 6.54% 0.003 0.96 294.37
a Q_ o should be zero. Positive values reflect errors in temperature measurement. The rectified entropy production and irreversibility are calculated assuming adiabatic conditions. See text for
explanations.
Jan 12.20 132.88 2.899 0 1.294 149.27 314.12 410.43 36.31 463.39 446.74 3.59% 273.94 277.68 2.75
Feb 10.19 114.38 2.5 0 1.942 129.01 258.77 340.10 37.66 387.78 377.76 2.58% 272.23 275.89 2.64
Mar 10.95 122.85 2.637 0 1.856 138.30 288.53 373.88 43.01 426.83 416.89 2.33% 273.83 277.16 2.70
Apr 7.64 89.19 1.811 0 1.235 99.88 244.65 303.90 34.53 344.53 338.43 1.77% 280.40 283.71 3.04
May 6.96 87.28 1.738 0 1.261 97.23 260.92 315.81 36.87 358.16 352.67 1.53% 285.73 289.71 3.25
Jun 5.77 77.26 1.522 0 1.016 85.57 253.92 301.06 33.99 339.49 335.05 1.31% 290.69 296.37 3.52
Jul 4.59 67.47 1.308 0 0.996 74.36 226.25 265.23 31.80 300.62 297.02 1.19% 291.83 301.20 3.57
Aug 5.86 84.94 2.861 10.184 1.214 105.05 286.51 337.68 37.65 391.57 375.34 4.14% 292.12 304.04 3.21
Sept 5.94 85.33 2.865 0 1.248 95.38 299.81 349.74 41.51 395.20 391.25 1.00% 291.92 302.02 3.67
Oct 7.34 94.83 3.2 0 1.319 106.69 321.27 379.57 43.21 427.97 422.77 1.21% 290.92 296.25 3.56
Nov 7.97 95.59 3.282 0.155 1.144 107.98 302.99 363.95 41.13 411.12 405.08 1.47% 286.36 290.40 3.37
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0 1425
The compressor energy transfer and irreversibility rates Since insulation is not perfect, some heat loss to the sur-
between the discharge (final state 2) and suction (initial state roundings is expected, yielding Q_ o slightly negative and
1) ports, and the compressor run times are shown in Table 2. h2 z h3 with h2 slightly larger than h3. However, Table 2 shows
The compressor irreversibility remains fairly constant that although h2 is very close in value to h3, it is slightly lower
throughout the months, but the compressor heat rejection (rather than higher) in value than h3. Also, Q_ o is positive
rates to the surrounding varies from a minimum of 400.7 W in indicating that heat flows from the surroundings to the con-
January to a maximum of 768.8 W in September. Since necting line which is not possible because the discharge line is
compressor heat is rejected to conditioned space, it is a benefit always hotter than the surroundings when the compressor is
during the winter, but a disadvantage during the summer, operating. The problem here lies in a slightly incorrect tem-
especially since more heat is rejected to conditioned space in perature measurement indicating that the temperature at
summer than in winter. The ratio, I= _ W
_ e remains fairly con- state point 3 is slightly higher than at state point 2 which again
stant, just below 0.4 throughout the year, whereas the ratio, cannot be the case. Although the differences in temperature
Q_ o =W
_ e is low during the winter and increases slightly during measurements are small, they remain within the manufac-
the hot summer months (JulyeSeptember) as shown in Fig. 3. turer’s specified accuracy (0.2 C) for the thermistors used.
During these hot summer months, the EWT from the ground When differences in state properties are expectedly very
loop is the highest for the year as shown in Fig. 3 where the close, as in these cases, the errors in measurement tend to be
ratio EWT/EWTmax. nears 1.0 in September, the month of significant.
highest EWT (perhaps an artifact of the same ground loop Since the connecting line is short, and the magnitude of the
used for space conditioning, as well). If heat rejected by the energy transfers and entropy production rates are small
compressor Q_ o can be reduced during summer months, it compared to the entire cycle, they do not materially impact
would reduce the cooling load. One way might be to increase the overall analysis or conclusions. An attempt was made to
the size of the ground loop, but the total compressor heat alleviate the impact of this minor error by assuming that the
rejected to the conditioned space, given by the product of Q_ o line is adiabatic, thus implying that Q_ o is zero. Then, using
and the compressor run time, is of the order of 40e45 kWh per Eqns. (12)e(14), the values of entropy production and irre-
month, and not sufficient to warrant the cost and possibly versibility were rectified on this basis, and these values are
lower COPs due to lower brine EWTs on account of loop reported in Table 2.
extension.
5.3. Refrigerant-DHW heat exchanger (HX3)
5.2. Compressor discharge line to HX3
The control volume of the refrigerant line in HX3 encom-
The control volume for the compressor discharge line (insu- passes the segment between initial and final state points 3 and
lated) to HX3 encompasses state points 2 and 3 in Fig. 2. The 4, respectively. Applying the general mass, energy, and en-
general mass, energy and exergy balance equations (1), (2), (7) tropy balances, Eqns. (1), (2) (7) and (8) gives the necessary
and (8) for this line reduce to: equations for this segment:
Q_ o þ m
_ map ðh2 h3 Þ ¼ 0 (12) Q_ o þ m
_ map ðh3 h4 Þ ¼ 0 (15)
Q_ o Q_ o
_ map ðs3 s2 Þ
s_ ¼ m (13) _ map ðs4 s3 Þ
s_ ¼ m (16)
To 1
ðT9 þ T10 Þ
2
I_ ¼ sT
_ o (14)
1
I_ ¼ sT
_ o; To ¼ ðT9 þ T10 Þ (17)
2
where Q_ o is <0 because heat is transferred from the refrig-
erant to the DHW tank. The entropy generation, irreversibility
and heat transferred to make hot water are tabulated in Table
2. The values for T9 and T10 are given in Table 4.
Q_ o ¼ m
_ map ðh5 h4 Þ; Q_ o ¼ 0 ðadiabaticÞ (18)
_ map ðs5 s4 Þ
s_ ¼ m (19)
Fig. 3 e Ratios of compressor irreversibility and
compressor heat rejection rates to its electrical
consumption. I_ ¼ sT
_ o (20)
1426 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
Table 5 e Sources and rates of entropy production and irreversibility for state points in the refrigeration closed cycle.
Compressor Compressor DHW (HX3) Expansion valve & Refrig.-brine Ref.-brine HX to Total
discharge connecting lines HX (HX2) compressor suction
to DHW (HX3)
State points/ [1 / 2] s_ [2 / 3] s_ [3 / 4] s_ [4 / 5] s_ [5 / 6] s_ [6 / 1] s_ (W K1) s_ (W K1)
(W K1) 1
(W K ) 1
(W K ) 1
(W K ) 1
(W K )
machine is the poorest in summer than in winter as given by operating between the brine to refrigerant heat exchanger
the parameter, h (Table 7). This poorer performance is re- (HX2) and the refrigerant to DHW heat exchanger (HX3). Since
flected in the irreversibility rates given in Table 6 e higher a 2-T Carnot engine is being considered and the temperatures
irreversibility in summer than in winter. in both HX2 and HX3 vary, the average of the EWT and LWT is
The sum of the rate of work input of an ideal compressor taken as the temperature at which heat is extracted from the
(Carnot engine power consumption) plus the rate of lost work ground, and the average of temperatures T9 and T10 to which
due to irreversibility within the control volume of the heat is rejected in HX3 to generate hot water. If the irrevers-
compressor must equal the rate of electrical work consumed ibilities are calculated correctly, then Eq. (27) must be satisfied
by the actual compressor. The Carnot engine power is calcu- within reasonable experimental error:
lated on the basis of a two temperature (2-T) Carnot engine
W _ Carnot þ s_ Total To ¼ W
_ Comp: ¼ W _ Carnot þ I_Total (27)
_ Carnot is calculated as follows:
where W
Jan 2.863 833 3192.8 7.581 421.2 1254.6 1350.7 0.312 7.66
Feb 2.855 810 2976.0 7.259 410.0 1219.5 1315.5 0.312 7.87
Mar 2.903 820 3138.3 7.428 422.5 1242.0 1336.3 0.316 7.59
Apr 3.149 871 3881.2 8.492 457.1 1327.7 1415.0 0.323 6.58
May 3.514 963 4482.9 9.783 458.2 1420.9 1499.5 0.306 5.53
Jun 3.794 1038 5018.2 11.891 422.0 1460.4 1526.9 0.276 4.55
Jul 3.934 1075 5130.0 12.954 396.0 1470.7 1529.7 0.259 4.02
Aug 3.910 1070 4953.0 14.411 343.7 1414.1 1468.3 0.234 3.84
Sept 4.017 1068 5336.4 13.562 393.5 1461.3 1518.8 0.259 3.93
Oct 3.856 1021 5167.6 11.832 436.7 1457.4 1525.4 0.286 4.66
Nov 3.522 938 4669.7 10.157 459.8 1398.2 1473.2 0.312 5.37
work consumed by the compressor. The compressor efficiency the smaller temperature differences between the EWT and the
relative to the Carnot work is determined by h ¼ ½W _ Carnot = LWT.
W_ Comp: meas: . The ground is unequivocally a useful source of renewable
Monthly data in Table 7 displays the agreement between energy for water heating e providing 68e76% of the total water
measured compressor power and that computed from Eq. (27), heating energy in January and in September, respectively.
validating that the irreversibility calculations are within The heat rejected by the compressor within the condi-
acceptable experimental errors. The averaged compressor tioned space is a benefit during the heating season, but a
efficiency is 29% (2.94%) of an ideal Carnot reverse engine penalty during the cooling season. The monthly compressor
operating between the same temperatures, and remains heat rejection was found to be between 32 kWh and 43 kWh
rather consistent over the 11-month period. (see Table 3) with negligible net benefit or loss to conditioned
space.
Although 88e91% (11-month average) of the total electrical
energy input is consumed by the compressor, it represents
7. Discussion only about 22e29% of the total energy input of the WW-GHSP
for water heating; (w2e3% of total energy input is for pumps
The entire hot water demand specified by the Building and controls) e the balance is extracted from the ground. This
America Benchmark Definition (Hendron and Engebrecht, technology enables judicious use of the ground as a renewable
2010) which attempts to capture the living habits of the energy resource.
average American (United States) household and how they The WW-GSHP operates at approximately 0.26e0.31 of the
impact energy consumption was met with a 5.275 kW (1.5-ton) efficiency of a 2-T Carnot heat pump (Table 7), which was
WW-GSHP in DOE climate region 4 (mixed-humid). The daily surprisingly larger than expected. This level of performance
hot water needs are approximately 227 L day1 (60 gal day1) remained fairly consistent from January to November. Exergy
at a temperature of 49 C (120 F). The WW-GSHP serviced a analysis shows the distribution of inefficiencies within the
303 L (80 gal) capacity hot water tank with two 4.5 kW heating vapor compression cycle. The greatest source of systemic in-
elements for backup. efficiency from the standpoint of the Second Law is the
The highest averaged monthly COP achieved was 3.67 in compressor. Although the rate of heat transfer from the
September with an EWT of 28.9 C. The lowest COP of 2.64 was ground to the brine is lower in winter than in the summer,
in February with an EWT of 2.74 C. The COPs are calculated on more heat is extracted from the ground during winter
the basis of total energy input because that is what the con- (314 kWh) than in summer (226 kWh) because of the lower
sumer ultimately pays for in utility bills. Although the rate of temperature of the cold water supply which requires more
energy extracted from the ground is higher in the summer heat to reach the desired temperature. Compressor energy
than in the winter, the least amount of energy (226 kWh) was consumption was highest in January (132.9 kWh) and lowest
extracted from the ground in July and the most energy in July (67.47 kWh) because of lower COP due to lower EWT
(314 kWh) extracted in January to make hot water because of and a greater temperature difference between supply and set
two reasons: (a) the incoming city supply water temperature is point water temperatures in winter than in summer. Since
higher during the summer and therefore requires less energy total lost work is highest in winter than it is in summer, the
to heat up to 49 C than in the winter and, (b) the compressor consumer pays more for systemic inefficiency during winter
run times are less in summer than in the winter. than in summer.
The energy balance equation was verified within 2.01%
(0.01%) on average. The largest discrepancy (4.14%) in the
energy balance occurred in August during equipment down- 8. Conclusions
time. Generally, the energy balances showed higher discrep-
ancies during winter months, January, February and March of A 5.275 kW (1.5-ton) WW-GSHP is shown to supply 227 L day1
3.59%, 2.58% and 2.33%, respectively due to the larger errors in (60 gal day1) of hot water at 49 C (120 F) meeting the protocol
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0 1429
for hot water use based on the Building America Research Ally, M.R., Munk, J.D., Baxter, V.D., Gehl, A.C., 2012. Exergy
Benchmark Definition which aims to capture the living habits analysis and operational efficiency of a horizontal ground
of the average American household. The coefficient of per- source heat pump system operated in a low-energy test house
under simulated occupancy conditions. Int. J. Refrigeration 35
formance of this heat pump varied from a low value of 2.64 in
(4), 1092e1103.
February when the entering water temperature from the Baden, S.P., Fairey, P., Waide, P., de T’serclaes, P., Laustsen, J.,
ground loop was 2.74 C, to a high value of 3.67 in September August 2006. Hurdling financial barriers to low energy
when the entering water temperature was 28.87 C. Reason- buildings: experiences from the USA and Europe on financial
ably high efficiencies may be obtained even from a shallow incentives and monetizing building energy savings in private
horizontal ground loop using 20% (v/v) polypropyleneewater investment decisions. In: Proc. of 2006 ACEEE Summer Study
mixtures. The maximum efficiency of the WW-GSHP was 32% on Energy Efficiency in Buildings. American Council for an
Energy Efficient Economy, Washington, D.C.. Publication No.
of the Carnot efficiency (Table 7). Depending on the season,
FSEC-PF-396-06. http://www.fsec.ucf.edu/en/publications/pdf/
between 33% and 47% of the total electrical energy input to the FSEC-PF-396-06.pdf
compressor is rejected as heat to the surroundings (Table 3). Cecchinato, L., Corradi, M., Fornasieri, E., Zamboni, L., 2005.
The compressor heat rejected to the conditioned space is ad- Carbon dioxide as refrigerant for tap water heat pumps: a
vantageous in winter but disadvantageous during summer. comparison with the traditional solution. Int. J. Refrigeration
The measurements indicated that the quantity of heat 28 (8), 1250e1258.
U.S. DOE, 2009. Buildings Energy Data Book, Table1.1. US
extracted from the ground during the summer is almost twice
Department of Energy, Buildings Technology Program, Office
that in the winter, reflective of the higher summer entering
of Energy Efficiency and Renewable Energy, Washington, D.C..
water temperatures. The main sources of systemic in- http://buildingsdatabook.eren.doe.gov/docs/xls_pdf/1.1.3.pdf.
efficiency, listed in order of decreasing significance, are the http://buildingsdatabook.eren.doe.gov/docs/xls_pdf/1.1.9.pdf.
compressor, the expansion valve, the domestic hot water heat U.S. DOE, October 2010. Multi-year Program Plan-building
exchanger (HX3), the ground loop heat exchanger (HX2) and Regulatory Programs. U.S. Department of Energy, Office of
the connecting lines. Energy Efficiency and Renewable Energy, Washington, D.C..
http://apps1.eere.energy.gov/buildings/publications/pdfs/
Although the irreversibility rate, I_ (W) is lowest in the
corporate/regulatory_programs_mypp.pdf
winter and highest during the summer, the total irreversibility Fernandez, N., Hwang, Y., Radermacher, R., 2010. Comparison of
or lost work, I_ tComp (kWh) is higher in winter than in sum- CO2 heat pump water heater performance with baseline cycle
mer because of the longer compressor run times in the former and two high COP cycles. Int. J. Refrigeration 33 (8), 635e644.
versus the latter season (see Table 6). Hendron, R., Engebrecht, C., January 2010. Building America
Approximately 68e76% of the total energy input for water Research Benchmark Definition. National Renewable Energy
heating comes from the ground, estimated by the ratio, Laboratory. Report No. NREL/TP-550-47246.
Hjerkinn, T., 2007. Analysis of heat pump water heater systems
Q_ o;ground =Ein readily calculated from Table 3. The electrical en-
for low-energy block of flats. Doctoral dissertation, Master
ergy input to the compressor is about 22e29% of the total energy thesis at the Norwegian University of Science and
input and is 88e91% of the total electrical energy input, whereas Technology (NTNU), Dept. of Energy and Process
the electrical energy consumption of the two pumps and the Engineering, EPT-M-2007-24.
control system account for less than 3% of the total energy input Hughes, P., Im, P., January 2012. Foundation Heat Exchanger Final
and less than 10% of the total electrical energy input. Report: Demonstration, Measured Performance, and Validated
Model and Design Tool. Oak Ridge National Laboratory. ORNL/
Since more than two-third (68e76%) of the energy needed
TM-2012/27.
to produce domestic hot water can be extracted from the
IPCC, 2007. Summary for policymakers. In: Metz, B., Davidson, O.R.,
ground, this technology enables practical use of ground Bosch, P.R., Dave, R., Meyer, L.A. (Eds.), Climate Change 2007:
thermal energy as a renewable energy resource. Mitigation. Contribution of Working Group III to the Fourth
Assessment Report of the Intergovernmental Panel on Climate
Change. Cambridge University Press, Cambridge, United
Kingdom and New York, NY, USA. http://www.ipcc.ch/pdf/
assessment-report/ar4/wg3/ar4-wg3-spm.pdf.
Acknowledgments Lemmon, E.W., Huber, M.L., McLinden, M.O., 2010. NIST Standard
Reference Database 23: Reference Fluid Thermodynamic and
The authors would like to thank Dr. Brian Fricke, Dr. Bo Shen, Transport Properties-REFPROP. Version 9.0. National Institute
and Mr. Vishaldeep Sharma for reviewing this paper and of Standards and Technology, Standard Reference Data
suggesting changes. The authors also appreciate support by Program, Gaithersburg.
Miller, W.A., Kosny, J., Shrestha, S., Kohler, C., 2010.
the U.S. Department of Energy’s Buildings Technology pro-
Demonstration of four different residential envelopes.
gram that provided funding for this project. American Council for an Energy Efficient Economy (ACEEE)
Summer Study on Energy Efficiency in Buildings, Asilomar
Conference Center in Pacific Grove, CA, August, 2010.
Minetto, S., 2011. Theoretical and experimental analysis of a CO2
references heat pump for domestic hot water. Int. J. Refrigeration 34 (3),
742e751.
Myers, G.E., 2007. Engineering Thermodynamics, second ed. AMCHT
Ally, M.R., Munk, J.D., Baxter, V.D., 2011. Field test of high Publication, Madison, Wisconsin, ISBN 978-0-9666065-2-2.
efficiency residential buildings with ground-source and air- Nanxi, L., Shi, L., Lizhong, H., Mingshan, Z., 2005. Moderately high
source heat pump systems. In: 10th IEA Heat Pump temperature water source heat-pumps using a near-
Conference, May 16e19, 2011, Tokyo, Japan. azeotropic refrigerant mixture. Appl. Energy 80 (4), 435e447.
1430 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 4 1 7 e1 4 3 0
Neksa, P., Rekstad, H., Zakeri, G.R., Schiefloe, P.A., 1998. CO2- Stene, J., Hjerkinn, T., 2008. High-efficiency Heat Pump Water
heat pump water heater: characteristics, system design Heater System for Apartment Buildings of Passive House
and experimental results. Int. J. Refrigeration 21 (3), Standard. Passivhus NORDEN 2008, Trondheim, April 2e3, 2008.
172e179. http://www.annex32.net/pdf/articles/STENE_CO2HPWH_
Stene, J., 2005. Residential CO2 heat pump system for combined PassiveH_paper.pdf.
space heating and hot water heating. Int. J. Refrigeration 28 (8), Warke Jr., K., 1995. Advanced Thermodynamics for Engineers.
1259e1265. McGraw-Hill, New York, ISBN 0-07-068292-5.