High Speed Fuses

Section Contents
Page
General Applications . . . . . . . . . . . . . . . . . . . . . . . . 94-95
North American fuses & accessories . . . . . . . . . . . .94-113
DFJ - High speed Class J fuse . . . . . . . . . . . . . . . . . . .97
Square Body fuses & accessories . . . . . . . . . . . . 114-176
BS 88 fuses & accessories . . . . . . . . . . . . . . . . . .177-185
Ferrule fuses & accessories. . . . . . . . . . . . . . . . . .186-206

High Speed
Fuses

93
High Speed Fuses

General Applications

Rated Voltage Power Factor X

The AC voltage rating of Cooper Bussmann® fuses is given For other power factor 1.0
in volts rms. Fuses tested to IEC are tested at 5% above values, the total clearing
their rated voltage. British Style BS 88 fuses are tested at integral can be
10% above its rated voltage. UL recognition tests are calculated as a multiple
0.9
performed at the rated voltage. of the clearing integrals,
the correction factor K
Rated Current and the correction factor
Rated current is given in amps rms. Cooper Bussmann fuses X. 0.8
can continuously carry the rated current.

Melting Characteristic
0.7
The melting 10 4 Arc Voltage 0.1 0.2 0.3 0.4 0.5
characteristic
6
4
COS ␸
This curve gives the
shows the virtual 2 1.4
10 3 peak arc voltage, U L , 1.2 UL
melting time in 6
4 which may appear 103
seconds as a 2
across the fuse during its 9
function of the 10 2
8
prospective current 6 operation as a function 7
4

in amperes rms. 2
of the applied working 6
voltage, E g , (rms) at a
Virtual Pre-Arcing Time In Seconds

The fuses are 10


6
1

5
specially 4 power
2 4
constructed for 0
factor of 15%.
10
short-circuit 6 3 Eg
protection against
4
Power Losses 200 300 400 500 600 660
2

high level fault 10 –1


Watts loss at rated
6
1.0
currents. Loading Kp
4
current is given in the 0.8
and operation of 2
0.6
10 –2 electrical characteristics.
the fuse in 0.5
6
The curve allows the
the non- 4
0.4
continuous/dashed
2 calculation of the power
10 –3 0.3
section of the melt 6 losses at load currents
4
curve must be 2
lower than the rated 0.2
avoided. The curve 10
10 2 4 6 8 10 2
–4

4 1
6 8 10 2 3
current. The correction
can also be read Prospective Current In Amperes RMS factor, K p , is given as a Ib
0.1
as the real melting function of the RMS load 30 40 50 60 70 80 90 100%
time as a function of the RMS value of the pre-arc current. current, Ib , in % of the
1.5 rated current .
Clearing Integrals
K
The total clearing I2t at 1.0
Cut-Off Current
rated voltage and at A fuse operation relating to short-circuits only. When a fuse
power factor of 15% are operates in its current-limiting range, it will clear a short-
given in the electrical circuit in less than 1⁄2 cycle. Also, it will limit the instantaneous
0.5
characteristics. For
0.4
other voltages, the 105

clearing I2t is found by 0.3


multiplying by correction
factor, K, given as a 0.2
Peak Let-Through Current

104
Eg
function of applied
working voltage, Eg, 100 200 300 400 500 600 660
(rms). 103 A
B

2 ≈ 10 2
102 103 104 105 106
Prospective Current in Amps RMS

peak let-through current to a value substantially less than


that obtainable in the same circuit if that fuse were replaced

94 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

General Applications

with a solid conductor of equal impedance. melting current corresponding to the time “t” of the overload
A asymmetrical current duration as read from the time-current curve of the fuse. The
B symmetrical current guidelines in the table below determine the acceptability of
the selected fuses for a given Imax.
Parallel Connection Frequency of Occurrence Overloads (> 1 sec) Impulse Loads (< 1 sec)
Less than once per month Imax < 80% x It Imax < 70% x It
When fuses are connected in parallel it is recommended that
Less than twice per week Imax < 70% x It Imax < 60% x It
the applied voltage does not exceed 0.9 UN (the rated
Several times per day Imax < 60% x It —
voltage of the fuse). This is due to the fact that the energy
released within the fuses may be unevenly shared between When impulse loads are an intrinsic/normal parameter of the
the parallel connected barrels. load current either as single pulse or in trains of pulses or
when their level is higher than the melting current at 0.01
When fuses are connected in parallel, one must take into
seconds (per time-current curve), contact Cooper Bussmann
account that the current sharing is not necessarily equal. And
for application assistance.
it must be checked, that the maximum load current is not
exceeded. In addition to the parameters set forth in the preceding table,
the RMS value of the load current as calculated for any

High Speed
Series Connection period of 10 minutes or more should not exceed the

Fuses
Fuses in series may not equally divide the applied voltage. It maximum permissible load current.
is recommended that series connected fuses should only be Furthermore, it is important that a fuse should not be applied
operated at fault currents that yield melting times less than in the non-continuous/dashed portion of the associated
10 ms and a recovery voltage per fuse of less than or equal time-current curve.
to 0.9 UN (the rated voltage of the fuse).
Any time-current combination point which falls in the
Mounting Guidance non-continuous/dashed portion of the time-current curve is
beyond the capability of the fuse to operate properly.
The recommendations below have to be followed when
mounting a Cooper Bussmann fuse with end plate threaded DC Operation
holes.
1. Screw in studs: 5 N•m Max, 3 N•m Min Depending upon the short-circuit time constant and the
2. Attachment of the fuse to bussbar by means of nut and magnitude of the prospective short-circuit current, the dc
washer: voltage at which a fuse can be applied may be less than its
Thread Torque (N•m)* ac rating. Long time constants require a lower dc voltage.
Configuration Max Min Conversely, however, higher available prospective short-
5
⁄16” – 18, M8 25 20
3
⁄8” – 16, M10 45 40 circuit currents result in faster fuse openings and thus permit
3
⁄8” – 24 45 40 a fuse to be operated at a higher DC voltage.
1
⁄2” – 13, M12 65 50
1
⁄2” – 20 65 50 Consult Cooper Reduction Factor
*1 N•m = 0.7375 lb-ft Bussmann for additional
information and applica-
Overloads tion assistance when 1.0
The design of Cooper Bussmann® fuses is such that they fuses have to operate
can be operated under rather severe operating conditions under DC conditions. 0.9
imposed by overloads (any load current in excess of the
Load Current Versus 0.8
maximum permissible load current).
Conductor Cross
In applications, there will be a maximum overload current,
Imax, which can be imposed on the fuse with a Section 0.5 0 .6 0.7 0 .8 0.9 1 .0
corresponding duration and frequency of occurrence. ≈ (IEC cross section)
Reduction of permissible
Time durations fall into two categories: load current when the conductor cross section is less than
1. Overloads longer than one second that given in IEC Publication 269-1 & 4 valid for Cooper
2. Overloads less than one second termed “impulse” loads. Bussmann high speed fuses.
The following table gives general application guidelines Application Assistance
which, in the expression Imax < (% factor) x It. It is the
If you have application problems or need a fuse outside our
standard program, please contact the nearest Cooper
Bussmann representative. Phone numbers are shown on the
back cover.

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 95


High Speed Fuses

North American Fuses

Introduction
North American Contents General Information
Catalog Amp
Cooper Bussmann offers a complete range of North
Number Volts Range Page
DFJ 600 1-600 97 American blade and flush-end style fuses and accessories.
FWA 130 1000-4000 98-99 Their design and construction were optimized to provide:
FWA 150 70-1000 100-101 • Low energy let-through (I2t)
FWX 250 35-2500 102-103 • Low watts loss
FWH 500 35-1600 104-105 • Superior cycling capability
KAC 600 1-1000 106 • Low arc voltage
KBC 600 35-800 107
• Excellent DC performance
FWP 700 5-1200 108-110
FWJ 1000 35-2000 111-112 North American style fuses provide an excellent solution for
medium power applications. While there are currently no
Accessories published standards for these fuses, the industry has
Fuse Bases 113 standardized on mounting centers that accept
Cooper Bussmann fuses.
North American Fuse Ranges
Amps Volts AC DC
1000-4000 130 X X
Voltage Rating
70-1000 150 X X All Cooper Bussmann® North American style fuses are tested
35-2500 250 X X at their rated voltage. Cooper Bussmann should be consulted
35-1600 500 X X
for applications exceeding those values.
1-1000 600 X —
5-1200 700 X X Accessories
40-600 800 — X
35-2000 1000 X — External and internal open fuse indication is available for
selected portions of the North American line. Fuse blocks are
available for most applications.

96 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

Drive Fuse High Speed Fuses


DFJ Class J Time-Current Characteristic Curves—Average Melt

High Speed
Fuses
Specifications
Description: High speed, current-limiting fuse.
The Cooper Bussmann® Drive Fuse will provide maximum
protection for AC and DC drives and controllers and meet
NEC® branch circuit protection requirements. The Drive Fuse
has the lowest I2t of any branch circuit fuse to protect power
semiconductor devices that utilize diodes, GTOs, SCRs and
SSRs.
Dimensions: See page 15 for Class J dimensions.
Construction: Melamine tube with silver fuse element.
Ratings:
Volts — 600Vac (or less), 450Vdc (or less)
Amps — 1-600A
IR — 200kA RMS Sym., 100kA DC
Agency Information: CE, Std. 248-8, Class J, UL Listed,
Guide JDDZ, File E4273, CSA Certified, Class 1422-02, File
53787. Current Limitation Curves
Features and Benefits
• Easily coordinated with existing and new variable speed
drives and electric controllers.
• Standard Class J dimensions allowing the use of readily
available fuse blocks, holders, and switches.
• Allows the lowest let-thru energy of any branch circuit
overcurrent protective device.

Typical Applications
• Protection of ac & dc drives
• Equipment using power semi-conductor devices
Catalog Numbers (Amps)
DFJ-1 DFJ-15 DFJ-70 DFJ-225
DFJ-2 DFJ-20 DFJ-80 DFJ-250
DFJ-3 DFJ-25 DFJ-90 DFJ-300
DFJ-4 DFJ-30 DFJ-100 DFJ-350
DFJ-5 DFJ-35 DFJ-110 DFJ-400
DFJ-6 DFJ-40 DFJ-125 DFJ-450
DFJ-8 DFJ-45 DFJ-150 DFJ-500
DFJ-10 DFJ-50 DFJ-175 DFJ-600
DFJ-12 DFJ-60 DFJ-200

Data Sheet: 1048

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 97


High Speed Fuses

North American — FWA 130V: 1000-4000A

FWA Arc Voltage


UL
This curve gives the peak
Specifications
arc voltage, UL, which
Description: North American 300
may appear across the
style flush-end high speed fuses.
fuse during its operation
Dimensions: See Dimensions as a function of the 200
illustrations. applied working voltage,
Ratings: Eg, (rms) at a power 100
Volts: — 130Vac factor of 15%. Eg
Amps: — 1000-4000A
Power Losses 50 100 150
IR: — 200kA RMS Sym.
Watts loss at rated current
— 50kA @130Vdc 1.0
is given in the electrical Kp
Agency Information: CE, UL Recognized on 1000-2000A characteristics. The curve 0.8
fuses allows the calculation of 0.6
0.5
Electrical Characteristics the power losses at load
0.4
currents lower than the
0.3
Total Clearing I2t rated current. The
1.5 correction factor, Kp, is 0.2
The total clearing I2t at K
given as a function of the
rated voltage and at power 1.0
RMS load current, Ib, in %
factor of 15% are given in Ib
of the rated current. 0.1
the electrical 30 40 50 60 70 80 90 100%
characteristics. For other 0.5 Catalog Numbers
voltages, the clearing I2t is Electrical Characteristics
found by multiplying by 0.3
I2t (A2 Sec)
correction factor, K, given Catalog Rated Current Clearing Watts
0.2
Numbers RMS-Amps Pre-arc at 130V Loss
as a function of applied
Eg FWA-1000AH 1000 170000 460000 60
working voltage, Eg, (rms). 0.15
26 65 104 130 FWA-1200AH 1200 270000 730000 70
FWA-1500AH 1500 520000 1400000 78
FWA-2000AH 2000 860000 2400000 108
FWA-2500AH 2500 1500000 4100000 130
FWA-3000AH 3000 2100000 5700000 150
FWA-4000AH 4000 3400000 9200000 257
• Watts loss provided at rated current.
Dimensions (in) • See accessories on page 113.
Catalog Number Fig. B C D Thread Depth
FWA-1000AH-2000AH 1 2.0 1.0 — Tapped 3⁄8”-24 x 1⁄2” Features and Benefits
FWA-2500AH-3000AH 1 3.0 1.5 — Tapped 1⁄2”-20 x 1⁄2”
FWA-4000AH 2 3.5 1.5 1.5 Tapped 1⁄2”-20 x 1⁄2” • Excellent DC performance
1mm = 0.0394˝ / 1˝ = 25.4mm • Low arc voltage and low energy let-through (I2t)
Fig. 1: 1000-3000A Fig. 2: 4000A
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
1.875
1.875 • DC drives
• Power converters/rectifiers
• Reduced voltage starters

B B C
C

Data Sheet: 720001

98 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWA 130V: 1000-4000A

FWA 1000-4000A: 130V


Time-Current Curve
104
6
4

103
6
4 FWA-1000AH
FWA-1200AH
2 FWA-1500AH
FWA-2000AH
102
FWA-2500AH
6
FWA-3000AH
4
FWA-4000AH
2

High Speed
Virtual Pre-Arcing Time In Seconds

101

Fuses
6
4

2
0
10
6
4

10–1
6
4

10–2
6
4

10–3
6
4

10–4
2 4 6 8 2 4 6 8
103 104 105
Prospective Current In Amps RMS

Peak Let-Through Curve


2

105

4
Peak Let-Through Current

2
FWA-4000AH
FWA-3000AH
104 FWA-2500AH
FWA-2000AH
FWA-1500AH
6 FWA-1200AH
FWA-1000AH
4

103
103 2 4 6 104 2 4 6 105 2 4 6

Prospective Short-Circuit Current Symmetrical RMS


Data Sheet: 35785301

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 99


High Speed Fuses

North American — FWA 150V: 70-1000A

FWA Arc Voltage


UL
Specifications This curve gives the peak
Description: North American style arc voltage, UL, which may
300
stud-mount fuses. appear across the fuse
during its operation as a
Dimensions: See Dimensions 200
function of the applied
illustrations.
working voltage, Eg, (rms)
Ratings: at a power factor of 15%. 100
Volts: — 150Vac/dc Eg
Amps: — 70-1000A Power Losses
50 100 150
IR: — 100kA Sym. (70-400A) Watts loss at rated current
is given in the electrical 1.0
— 200kA Sym. (450-1000A) Kp
0.8
characteristics. The curve
— 20kA @150Vdc (70-800A) 0.6
allows the calculation of 0.5
— 100kA @ 80Vdc (70-400A) the power losses at load 0.4
Agency Information: CE, UL Recognized currents lower than the
0.3
rated current. The
Electrical Characteristics correction factor, Kp, is 0.2
Total Clearing I2t given as a function of the
1.5 RMS load current, Ib, in %
K Ib
The total clearing I2t at rated of the rated current. 0.1
1.0
voltage and at power factor 30 40 50 60 70 80 90 100%
of 15% are given in the Catalog Numbers
Electrical Characteristics
electrical characteristics. For Rated I2t (A2 Sec)
0.5
other voltages, the clearing 1)
Catalog Current Clearing Watts
I2t is found by multiplying by Number RMS-Amps Pre-arc at 150V Loss
0.3 FWA-70B 70 470 4000 6.9
correction factor, K, given as 2)
FWA-80B 80 670 6000 7.7
0.2
a function of applied working FWA-100B 100 1200 12000 9.0
voltage, Eg, (rms). Eg FWA-125B 125 1870 18000 11.2
0.15
22 70 102 150 FWA-150B 150 2700 26000 13.5
FWA-200B 200 4780 45000 17.6
1) 500-1000A Range
2) 70-400A Range
FWA-250B 250 7470 70000 22.5
FWA-300B 300 10760 100000 27.0
FWA-350B 350 15700 140000 30.6
FWA-400B 400 20300 180000 35.2
FWA-500A 500 39000 120000 35.0
FWA-600A 600 46000 140000 47.0
Dimensions (in) FWA-700A 700 75000 220000 49.0
Fig. 1: 70-400A FWA-800A 800 92000 280000 58.0
FWA-1000A 1000 170000 510000 60.0
2.656
• Watts loss provided at rated current.
2.188
• See accessories on page 113.
1.936
1.156 0.125
Features and Benefits
• Excellent DC performance
0.750 0.312 1.000 • Low arc voltage and low energy let-through (I2t)
• Low watts loss
0.438 • Superior cycling capability

Fig. 2: 500-1000A Typical Applications


3.500
• DC common bus
• DC drives
2.438
• Power converters/rectifiers
1.250 0.250 • Reduced voltage starters

1.000 1.500

0.406
1mm = 0.0394” / 1” = 25.4mm

Data Sheet: 720002

100 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWA 150V: 70-1000A

FWA 70-1000A: 150V


Time-Current Curve
104
6
4

103
6
4 FWA-500A
FWA-600A
2 FWA-700A
FWA-800A
102 FWA-1000A
6
4

2
Virtual Pre-Arcing Time In Seconds

1
10

High Speed
6

Fuses
4

100
6
4

10–1
6 FWA-70A
4 FWA-80A
FWA-100A
2 FWA-125A
FWA-150A
10–2
6
4

2
–3
10
6 FWA-200A
4 FWA-250A
FWA-300A
2 FWA-350A
FWA-400A
10–4
2 4 6 8 2 4 6 8
102 103 104
Prospective Current In Amps RMS

Peak Let-Through Curve


106

4
FWA-400A
FWA-350A
2
FWA-300A
FWA-250A
104 FWA-200A
FWA-150A
Peak Let-Through Current

6 FWA-100A

3
10

6 FWA-80A

4 FWA-70A

102
2 4 6 2 4 6 2 4 6 2
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785310

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 101


High Speed Fuses

North American — FWX 250V: 35-2500A

FWX Arc Voltage 1.4


1.2 UL
Specifications This curve gives the peak
103
Description: North American arc voltage, UL, which may
800
style stud-mount and flush-end appear across the fuse
fuses. during its operation as a 600
function of the applied 500
Dimensions: See Dimensions
working voltage, Eg, (rms) 400
illustrations. 1)
at a power factor of 15%. 300
Ratings: 2)
Power Losses Eg
Volts: — 250Vac/dc 200
Amps: — 35-2500A Watts loss at rated current is 50 100 150 200 250
1) 35-800A Range
IR: — 200kA RMS Sym. given in the electrical char 2) 1000-2500A Range
acteristics. The curve allows 1.0
Kp
Agency Information: CE, UL Recognized & CSA 0.8
Component Acceptance on 35-800A fuses (20kA IR the calculation of the power
0.6
@250Vdc). losses at load currents lower 0.5
than the rated current . The 0.4

Electrical 1.5 correction factor, K p , is 0.3


K
Characteristics given as a function of the 0.2
1.0
RMS load current, Ib , in %
Total Clearing I t 2

of the rated current . Ib


0.1
The total clearing I2t at rated 0.5
1)
30 40 50 60 70 80 90 100%
voltage and at power factor Catalog Numbers
Electrical Characteristics
of 15% are given in the 2)
0.3 Rated I2t (A2 Sec)
electrical characteristics. 0.2
Catalog Current Clearing Watts
For other voltages, the Number RMS-Amps Pre-arc at 250V Loss
Eg FWX-35A 35 50 230 4.2
clearing I2t is found by 0.15 FWX-40A 40 60 310 5.2
multiplying by correction 75 125 200 250 300 FWX-45A 45 80 390 5.7
factor, K, given as a 1) 35-800A Range FWX-50A 50 100 520 6.0
2) 1000-2500A Range FWX-60A 60 140 740 8.1
function of applied working FWX-70A 70 330 1400 7.2
voltage, Eg, (rms). FWX-80A 80 430 1850 8.1
FWX-90A 90 570 2450 9.0
Dimensions (in) FWX-100A 100 740 3150 10.0
Tapped FWX-125A 125 1130 4850 12.5
Amp Thread FWX-150A 150 1620 6950 15.7
Rang e Fig. A B C D E F G H J Depth FWX-175A 175 2170 9300 18.5
35-60 1 3.19 0.81 1.59 2.59 2.25 0.34 0.63 0.13 0.52 — FWX-200A 200 2790 12000 22
70-200 1 3.13 1.22 1.59 2.44 2.19 0.34 1.00 0.19 0.47 — FWX-225A 225 3210 14700 24
225-600 1 3.84 1.50 1.59 2.94 2.25 0.41 1.00 0.25 0.75 — FWX-250A 250 3960 18100 27
700-800 1 3.84 2.00 1.59 3.03 2.28 0.41 1.50 0.25 0.78 — FWX-275A 275 4720 21600 31
1000-1200 2 2.59 3.00 1.50 — — — — — — 3
⁄8”-24 x 1⁄2” FWX-300A 300 6000 27300 32
1500-2500 3 2.59 3.50 1.50 1.50 — — — — — 3
⁄8”--24 x 1⁄2” FWX-350A 350 10600 48600 39
1mm = 0.0394” / 1” = 25.4mm FWX-400A 400 14500 66100 44
FWX-450A 450 22100 101000 49
Fig. 1: Fig. 2: Fig. 3: FWX-500A 500 28000 128000 54
35-800A 1000-1200A 1500-2500A FWX-600A 600 41100 188000 62
FWX-700A 700 48800 190000 72
FWX-800A 800 59000 230000 84
J
FWX-1000AH 1000 44000 360000 100
A
A FWX-1200AH 1200 92000 750000 103
FWX-1500AH 1500 120000 880000 140
FWX-1600AH 1600 160000 1200000 140
FWX-2000AH 2000 320000 2300000 151
A D E C D
FWX-2500AH 2500 670000 4700000 163
• Watts loss provided at rated current. • See accessories on page 113.

B C
B C
Features and Benefits Typical Applications
• Excellent DC performance • DC common bus
F • Low arc voltage and low • DC drives
G
energy let-through (I2t) • Power converters/rectifiers
• Superior cycling capability • Reduced voltage starters
H

B Data Sheet: 720005

102 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWX 250V: 35-2500A

FWX 35-800A: 250V FWX 1000-2500A(H): 250V


Time-Current Curve Time-Current Curve
104 104
6
4

2
103
3
10
FWX-200A 6
FWX-350A
102 4
FXW-400A
FWX-500A
Virtual Pre-arcing Time In Seconds

FWX-600A 2 FWX-1000AH
FWX-800A
10 2 FWX-1200AH
101
FWX-1500AH
6
4 FWX-1600AH
FWX-2000AH
100 2 FWX-2500AH
1

High Speed
Virtual Pre-Arcing Time In Seconds
10

Fuses
FWX-35A
6
FWX-40A
10–1 FWX-60A 4
FWX-70A
FWX-100A 2
FWX-150A
10–2 100
6
4

10–3 2

10–1
6
10–4
4
2 102 103 104
Prospective Current In Amps RMS 2

10–2
6
Peak Let-Through Curve 4

2
105
10–3
B
6
4

2
FWX-800A
FWX-600A
FWX-400A
10–4
2 4 6 8 2 4 6 8
FWX-300A 103 104 105
FWX-200A
Prospective Current In Amps RMS
104
Peak Let-Through Current

Peak Let-Through Curve

105

6
FWX-2500AH
4 FWX-2000AH
103
FWX-1600AH
FWX-150A
FWX-1500AH
FWX-100A
FWX-1200AH
Peak Let-Through Current

FWX-70A 2
FWX-60A FWX-1000AH
FWX-45A
A FWX-35A
104

4
102
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS 2

103
2 4 6 2 4 6 2 4 6
103 104 105
Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 359 Data Sheet: 35785299

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 103


High Speed Fuses

North American — FWH 500V: 35-1600A

FWH Arc Voltage 2.0


UL
This curve gives the peak 1.6
Specifications
Description: North American style arc voltage, UL, which 1.2
stud-mount fuses. may appear across the 103
fuse during its operation 800
Dimensions: See Dimensions
as a function of the
illustration. 600
2)
applied working voltage,
Ratings: 500
Eg, (rms) at a power 1)
Volts: — 500Vac/dc 400
factor of 15%. Eg
Amps: — 35-1600A 300
Power Losses 100 200 300 400 500
IR: — 200kA Sym. 1) 35-200 & 1000-1600A Range

— 50kA @ 500Vdc Watts loss at rated 2) 225-800A Range


1.0
current is given in the Kp
Agency Information: CE, UL Recognition & CSA 0.8
electrical characteristics.
Component Acceptance on 35-800A only (50kA IR@500Vdc). 0.6
The curve allows the 0.5
UL Recognition on 35-1200A only, CSA Component
calculation of the power 0.4
Acceptance: 35-1600A.
losses at load currents
0.3
Electrical Characteristics lower than the rated
current. The correction 0.2
1.5
Total Clearing I2t K factor, Kp, is given as a
The total clearing I2t at rated 1.0 function of the RMS load
Ib
current, Ib, in % of the 0.1
voltage and at power factor of 30 40 50 60 70 80 90 100%
15% are given in the electrical rated current.
characteristics. For other 0.5
Catalog Numbers
voltages, the clearing I2t is 1) Electrical Characteristics
found by multiplying by 0.3 Rated I2t (A2 Sec)
0.2 Catalog Current Clearing Watts
correction factor, K, given as a 2) Numbers RMS-Amps Pre-arc at 500V Loss
function of applied working Eg FWH-35B 35 34 150 8
0.15
voltage, Eg, (rms). FWH-40B 40 76 320 7.5
100 250 400 500
FWH-45B 45 105 450 7.5
1) 35-800A Range
2) 1000-1600A Range FWH-50B 50 135 670 7.5
Dimensions (in) FWH-60B 60 210 900 9.9
Amp FWH-70B 70 210 900 10.6
Rang e Fig. A B C D E F G H J FWH-80B 80 305 1400 12.7
35-60 1 3.188 0.813 1.593 2.541 2.193 0.344 0.719 0.125 0.518 FWH-90B 90 360 1600 15
70-100 1 3.625 0.947 1.736 2.853 2.807 0.352 0.750 0.125 0.375 FWH-100B 100 475 2000 17
125-200 1 3.625 1.156 1.836 2.892 2.768 0.344 1.000 0.188 0.406 FWH-125B 125 800 3500 25
225-400 1 4.340 1.500 2.090 3.440 2.750 0.410 1.000 0.250 0.750 FWH-150B 150 1100 4600 30
450-600 1 4.340 2.000 2.090 3.530 2.780 0.410 1.500 0.250 0.780 FWH-175B 175 1450 6200 35
700-800 1 6.340 2.500 2.090 4.970 3.440 0.530 2.000 0.380 1.300 FWH-200B 200 1900 8500 40
1000-1200 1 6.969 3.000 3.219 5.465 4.475 0.625 2.375 0.438 1.120 FWH-225A 225 4600 23300 39
1400-1600 2 See Drawing FWH-250A 250 6300 32200 41
1mm = 0.0394” / 1” = 25.4mm FWH-275A 275 7900 40300 46
Fig. 1: 35-1200A FWH-300A 300 9800 49800 51
A FWH-325A 325 13700 63800 53
D FWH-350A 350 14500 72900 58
E FWH-400A 400 19200 96700 65
C H FWH-450A 450 24700 127000 74
FWH-500A 500 29200 149000 84
FWH-600A 600 41300 206000 108
G F B FWH-700A 700 55000 298000 120
FWH-800A 800 76200 409000 129
FWH-1000A 1000 92000 450000 145
J
FWH-1200A 1200 122000 600000 180
Fig. 2: 1400-1600A FWH-1400A 1400 200000 1000000 210
10.219
FWH-1600A 1600 290000 1400000 230
0.125 0.5 3.219 0.625 • Watts loss provided at rated current. • See accessories on page 113.
1.625
1.750
Features and Benefits Typical Applications
3.5
• Excellent DC performance • DC common bus
• Low arc voltage and low • DC drives
energy let-through (I2t) • Power converters/rectifiers
0.75
6.219 4.25
• Superior cycling capability • Reduced voltage starters
8.969 Data Sheet: 720007

104 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWH 500V: 35-1600A

FWH 35-200A(B) & 900-1600A(A): 500V FWH 250-800A: 500V


Time-Current Curve Time-Current Curve

10 4 103
6
4

103
6 102
4

2 FWH-300A
FWH-400A
102 FWH-500A
FWH-600A
6 FWH-800A
4
101
2 FWH-900A
FWH-1000A
101 FWH-1200A
6 FWH-1400A

Virtual Pre-Arcing Time In Seconds

High Speed
4 FWH-1600A

Fuses
2
100
100 FWH-80B
6 FWH-90B
4 FWH-100B
FWH-125B
2 FWH-35B FWH-150B
FWH-40B FWH-175B
10–1 FWH-45B FWH-200B
FWH-50B 10–1
6
4 FWH-60B
FWH-70B
2

10–2
6
4 10–2
2

10–3
6
4

2 10–3
10–4
2 4 6 8 2 4 6 8 2 4 6 8
102 103 104
Prospective Current In Amps RMS

10–4
102 103 104 105
Prospective Current In Amps RMS
Peak Let-Through Curve Peak Let-Through Curve
105 105
FWH-1600A B
FWH-1400A
6
FWH-1200A
4 FWH-1000A

4
10 104
Peak Let-Through Current
Peak Let-Through Current

FWH-800A
4
FWH-600A
FWH-500A
FWH-400A
2 FWH-300A
FWH-250A

103 103

FWH-200B
6 FWH-150B
FWH-125B
4 FWH-100B A
FWH-80B
FWH-60B
2 FWH-50B
FWH-40B
FWH-35B
102 102
2 4 6 2 4 6 2 4 6 2 102 103 104 105
102 103 104 105
Prospective Short-Circuit Current Symmetrical RMS
Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785304 Data Sheet: 360

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 105


High Speed Fuses

North American — KAC 600V: 1-1000A

KAC Catalog Numbers (Amps)


KAC-1 KAC-25 KAC-175
KAC-2 KAC-30 KAC-200
Specifications KAC-3 KAC-35 KAC-225
Description: North American style KAC-4 KAC-40 KAC-250
stud-mount fuses. These 600V fuses are KAC-5 KAC-45 KAC-300
supplied as replacements only. For new KAC-6 KAC-50 KAC-350
KAC-7 KAC-60 KAC-400
installations, Cooper Bussmann recommends KAC-8 KAC-70 KAC-450
the 700V FWP Series fuse. KAC-9 KAC-80 KAC-500
KAC-10 KAC-90 KAC-600
Dimensions: See Dimensions illustrations. KAC-12 KAC-100 KAC-700
Ratings: KAC-15 KAC-110 KAC-800
KAC-17.5 KAC-125 KAC-1000
Volts: — 600Vac KAC-20 KAC-150
Amps: — 1-1000A • See accessories on page 113.

IR: — 200kA RMS Sym. Features and Benefits


Agency Information: CE, UL Recognition • Low arc voltage and low energy let-through (I2t)
on 1-600A only. • Low watts loss
• Superior cycling capability

Typical Applications
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (in)
Amp
Rang e Fig. A B1 B2 B3 C D E F G H
1-30A 1 2.875 2.500 – – 1.875 0.406 – 0.563 0.063 0.257
35-60A 2 4.375 – 3.750 3.500 2.750 0.625 0.343 0.813 0.094 0.468
70-100A 2 5.000 – 4.063 3.656 2.750 0.750 0.406 1.000 0.125 0.609
110-200A 2 5.140 – 4.390 3.766 2.906 1.000 0.406 1.500 0.188 0.718
225-400A 2 6.182 – 4.815 4.565 3.000 1.625 0.562 2.000 0.250 0.687
450-800A 1 6.250 4.750 – – 3.063 2.000 – 2.500 0.250 0.563
1000A 1 7.250 4.750 – – 3.063 2.750 – 3.500 0.375 0.563
1mm = 0.0394˝ / 1˝ = 25.4mm

Fig. 1: 1-30 & 450-1000A

B1
C G

D F

Fig. 2: 35-400A

A
B2
B3
C G

D E F

Data Sheet: 720009

106 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — KBC 600V: 35-800A

KBC Catalog Numbers (Amps)


KBC-35 KBC-100 KBC-300
KBC-40 KBC-110 KBC-350
Specifications KBC-45 KBC-125 KBC-400
Description: North American KBC-50 KBC-150 KBC-450
style stud-mount and flush-end KBC-60 KBC-175 KBC-500
fuses. These 600V fuses are KBC-70 KBC-200 KBC-600
KBC-80 KBC-225 KBC-800
supplied as replacements only. KBC-90 KBC-250
For new installations, Cooper • See accessories on page 113.
Bussmann recommends the 700V
FWP Series fuse. Features and Benefits
• Low arc voltage and low energy let-through (I2t)
Dimensions: See Dimensions
• Low watts loss
illustrations.
• Superior cycling capability
Ratings:
Volts: — 600Vac Typical Applications
Amps: — 35-800A • Power converters/rectifiers

High Speed
• Reduced voltage starters
IR: — 200kA RMS Sym.

Fuses
Agency Information: CE, UL Recognition on 35-600A only.

Dimensions (in)
Amp
Rang e Fig. A B C D E F G H I
35-60A 1 4.375 3.750 3.500 2.750 0.343 0.625 0.813 0.094 0.468
70-100A 2 See Drawing
110-200A 1 4.406 3.719 3.594 2.906 0.312 0.875 1.219 0.187 0.375
225-400A 1 5.125 4.188 3.563 2.906 0.406 1.000 1.500 0.250 0.719
450-600A 1 5.125 4.389 3.687 2.875 0.406 1.500 2.000 0.250 0.757
800A 3 See Drawing
1mm = 0.0394” / 1” = 25.4mm

Fig. 1: 35-60 and 110-600A


A
B
C
E D H

F G

Fig. 2: 70-100A
4.406

0.125
3.656
2.906

1.000
0.750

0.312

Fig. 3: 800A
4.000
3.750 ‹/•" - 24 ≈ ⁄/™"
0.750

2.500 2.859

0.750
Data Sheet: 720010

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 107


High Speed Fuses

North American — FWP 700V: 5-1200A

FWP Arc Voltage 2


UL
This curve gives the peak arc 1.6
Specifications 1.4
voltage, UL, which may
Description: North American 1.2
1)
appear across the fuse 103
style stud-mount fuses.
during its operation as a 2)
Dimensions: See Dimensions 8
function of the applied
illustrations. working voltage, Eg, (rms) at 6
Ratings: 5
a power factor of 15%.
Volts: — 700Vac/dc 4
Power Losses Eg
Amps: — 5-1200A 3
300 400 500 600 700
IR: — 200kA RMS Sym. Watts loss at rated current is
1) 125-600A Range
given in the electrical 2) 35-100 & 700-1200A Range
— 50kA @700Vdc
characteristics. The curve
Agency Information: CE, UL Recognition & CSA 1.0
allows the calculation of the 0.8
Kp
Component Acceptance on 5-800A power losses at load 0.6

Electrical Characteristics currents lower than the rated 0.5


current. The correction factor, 0.4

Total Clearing I2t Kp, is given as a function of 0.3


1.5
K the RMS load current, Ib, in 0.2
The total clearing I t at rated
2

1.0 % of the rated current.


voltage and at power factor of
15% are given in the electrical 2) 0.1
Ib
characteristics. For other 30 40 50 60 70 80 90 100%
0.5 Catalog Numbers
voltages, the clearing I2t is Electrical Characteristics
found by multiplying by 1) Rated I2t (A2 Sec)
0.3 Catalog Current Clearing Watts
correction factor, K, given as 3)
0.2 Numbers RMS-Amps Pre-arc at 700V Loss
a function of applied working FWP-5B 5 1.6 10 1.5
voltage, Eg, (rms). 0.15 Eg FWP-10B 10 3.6 20 4
316 460 604 700 FWP-15B 15 10 75 5.5
1) 35-100A Range FWP-20B 20 26 180 6
2) 125-600A Range FWP-25B 25 44 340 7
3) 700-1200A Range FWP-30B 30 58 450 9
FWP-35B 35 34 160 12
FWP-40B 40 76 320 12
Dimensions (in) FWP-50B 50 135 600 12
Amp
Rang e Fig. A B C D E F G H I FWP-60B 60 210 950 15.5
5-30 1 2.870 0.563 1.855 2.477 2.477 0.250 0.405 0.063 0.250 FWP-70B 70 305 2000 18
35-60 1 4.375 0.813 2.750 3.708 3.312 0.344 0.725 0.125 0.542 FWP-80B 80 360 2400 21
70-100 1 4.406 0.947 2.594 3.625 3.563 0.344 0.750 0.125 0.375 FWP-90B 90 415 2700 25
125-200 1 5.090 1.500 2.840 4.190 3.500 0.410 1.000 0.250 0.750 FWP-100B 100 540 3500 27
225-400 1 5.090 2.000 2.840 4.280 3.530 0.410 1.500 0.250 0.780 FWP-125A 125 1800 7300 28
450-600 1 7.090 2.500 2.840 5.720 4.190 0.530 2.000 0.380 1.300 FWP-150A 150 2900 11700 32
700-800 1 6.630 2.000 2.844 5.562 5.062 0.625 1.500 0.250 0.875 FWP-175A 175 4200 16700 35
900-1000 2 See Drawing FWP-200A 200 5500 22000 43
1200 3 See Drawing FWP-225A 225 7700 31300 45
1mm = 0.0394” / 1” = 25.4mm FWP-250A 250 10500 42500 48
FWP-300A 300 17600 71200 58
Fig. 1: 5-800A Fig. 2: 900-1000A Fig. 3: 1200A FWP-350A 350 23700 95600 65
1.375
3.500 FWP-400A 400 31000 125000 78
J 0.125 FWP-450A 450 36400 137000 94
0.500 FWP-500A 500 45200 170000 107
FWP-600A 600 66700 250000 122
9.590 6.840 3.844
FWP-700A 700 54000 300000 125
5.966 3.844 10.844 FWP-800A 800 78000 450000 140
7.594
A D E C 5.154 FWP-900A 900 91500 530000 150
FWP-1000A 1000 120000 600000 170
0.625
1.031 FWP-1200A 1200 195000 1100000 190
1.625 • Watts loss provided at rated current. • See accessories on page 113.
0.625 1.750

2.750
0.750 Features and Benefits
0.5 4.250 • Excellent DC performance Typical Applications
F
G 3.500
• Low arc voltage and low • DC common bus
H energy let-through (I2t) • DC drives
B
• Superior cycling capability • Power converters/rectifiers
• Reduced voltage starters
Data Sheet: 720012

108 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWP 700V: 5-1200A

FWP 5-30A(B): 700V FWP 35-100A(B) & 700-1200A(A): 700V


Time-Current Curve Time-Current Curve
104 104
6 6
4 4

2 2

103 103
6 6
4 4

2 2
FWP-700A
102 102 FWP-800A
6 6 FWP-900A
4 4 FWP-1000A
FWP-1200A
2 2

Virtual Pre-Arcing Time In Seconds


101 101
Virtual Pre-Arcing Time In Seconds

6 6
FWP-35B
4 4
FWP-40B
2 FWP-50B

High Speed
2
FWP-60B

Fuses
100 100 FWP-70B
6 6 FWP-80B
FWP-5B 4 FWP-90B
4
FWP-10B FWP-100B
2 FWP-15B 2
FWP-20B
10–1 10–1
FWP-25B
6 FWP-30B 6
4 4

2 2

10–2 10–2

6 6
4
4
2
2
10–3
10–3
6
6
4
4
2
2
10–4
10–4 2 4 6 8 2 4 6 8 2 4 6 8
2 4 6 8
101
2 4 6 8
102
2 4 6 8
103 102 103 104
Prospective Current In Amps RMS
Prospective Current In Amps RMS

Peak Let-Through Curve Peak Let-Through Curve

104 106
FWP-1200A
6 6 FWP-1000A

4 FWP-800A
4
FWP-700A

2
FWP-30B
2
FWP-25B
3
10
Peak Let-Through Current

6 104

4
Peak Let-Through Current

2 4
FWP-20B
2
FWP-15B
10 FWP-10B
2
FWP- 5B
6

4 103

2 6
FWP-100B
4
101 FWP-70B
2 4 6 2 4 6 2 4 6 2 4 6 2
101 102 103 104 105 FWP-60B
Prospective Short-Circuit Current FWP-50B
2
FWP-40B
FWP-35B
102
2 4 6 2 4 6 2 4 6 2
102 103 104 105
Prospective Short-Circuit Current

Data Sheet: 35785316 Data Sheet: 35785308

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 109


High Speed Fuses

North American — FWP 700V: 5-1200A

FWP 150-600A: 700V


Time-Current Curve
103

102

FWP-150A
FWP-200A
FWP-300A
101 FWP-400A
FWP-600A
Virtual Pre-Arcing Time In Seconds

100

10–1

10–2

10–3

10–4
102 103 104 105
Prospective
ProspectiveCurrent
CurrentInInAmperes RMS
Amps RMS

Peak Let-Through Curve

105
B

104
Peak Let-Through Current

FWP-600A
FWP-400A
FWP-300A
FWP-200A
FWP-150A

103

102
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 361

110 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American — FWJ 1000V: 35-2000A

FWJ Arc Voltage 2000


UL
Specifications This curve gives the peak arc 1600
Description: North American voltage, UL, which may
style stud-mount fuses. appear across the fuse 1200
during its operation as a
Dimensions: See Dimensions
function of the applied 800
illustration.
working voltage, Eg, (rms)
Ratings: at a power factor of 15%. 400
Volts: — 1000Vac Eg
Amps: — 35-2000A Power Losses
200 600 1000 1400 1800
IR: — 25kA (35-200A) Watts loss at rated current is
— 100kA (250-2000A) given in the electrical 1.0
Kp
characteristics. The curve 0.8
— 50kA @ 800Vdc (35-
allows the calculation of the 0.6
200A, 450-600A) 0.5
power losses at load

High Speed
Agency Information: CE, UL 0.4
currents lower than the

Fuses
Recognition File E91958 on rated current. The 0.3
35-600A only. correction factor, Kp, is 0.2
given as a function of the
Electrical Characteristics RMS load current, Ib, in %
of the rated current. Ib
Total Clearing I2t 0.1
1.5 30 40 50 60 70 80 90 100%
K
The total clearing I2t at rated Catalog Numbers
1.0 Electrical Characteristics
voltage and at power factor of Rated I2t (A2 Sec)
15% are given in the electrical Catalog Current Clearing Watts
characteristics. For other Numbers RMS-Amps Pre-arc at 1000V Loss
0.5 FWJ-35A 35 210 2000 7
voltages, the clearing I2t is FWJ-40A 40 300 2500 8
found by multiplying by FWJ-50A 50 470 3500 10
0.3
correction factor, K, given as FWJ-60A 60 670 5000 11
0.2 FWJ-70A 70 1100 6900 12
a function of applied working
FWJ-80A 80 1550 9700 13
voltage, Eg, (rms). 0.15
Eg
FWJ-90A 90 1900 12000 14
200 500 800 1000 FWJ-100A 100 2800 17500 15
FWJ-125A 125 4800 35000 16
FWJ-150A 150 6300 45000 25
Dimensions (in) FWJ-175A 175 7500 65000 30
Amp FWJ-200A 200 11700 80000 32
Rang e Fig. A B C D E F G H I FWJ-250A 250 16000 112000 50
35-60 1 5.000 0.940 3.110 4.235 4.180 0.352 0.750 0.125 0.380 FWJ-300A 300 23500 164000 56
70-100 1 4.932 1.125 3.085 4.266 4.156 0.352 1.000 0.188 0.407 FWJ-350A 350 33000 231000 62
125-200 1 5.685 1.526 3.261 4.803 4.055 0.445 1.000 0.250 0.819 FWJ-400A 400 47000 330000 67
250-400 1 5.768 2.000 3.500 4.811 4.150 0.433 1.500 0.250 0.764 FWJ-500A 500 39500 329000 95
500-600 1 7.201 2.500 3.465 5.984 4.706 0.562 2.000 0.375 1.201 FWJ-600A 600 61000 520000 105
800-2000 1 6.811 3.500 3.312 5.472 4.962 0.625 2.750 0.500 0.880 FWJ-800A 800 87000 500000 182
1mm = 0.0394” / 1” = 25.4mm FWJ-1000A 1000 190000 1100000 206
FWJ-1200A 1200 370000 2100000 240
Fig. 1: 35-2000A
FWJ-1400A 1400 470000 2700000 248
A FWJ-1600A 1600 700000 4000000 267
D FWJ-1800A 1800 925000 5300000 239
E FWJ-2000A 2000 1330000 7600000 244
• Watts loss provided at rated current.
C H
• See accessories on page 113.

G F B
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
J
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
Data Sheet: 720027 • Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 111
High Speed Fuses

North American — FWJ 1000V: 35-2000A

FWJ 35-600A: 1000V FWJ 800-2000A: 1000V


Time-Current Curve Time-Current Curve
104 104
6 6
4 4

2 2

103 103
6 6
4 4

2 2

102
102
FWJ-200A 6
6
FWJ-250A 4 FWJ-800A
4
FWJ-300A 2 FWJ-1000A

Virtual Pre-Arcing Time In Seconds


2 FWJ-350A FWJ-1200A
101 FWJ-1400A
FWJ-400A
Virtual Pre-Arcing Time In Seconds

101 6 FWJ-1600A
FWJ-500A FWJ-1800A
6 4
4 FWJ-600A FWJ-2000A
2
2
100
100 6
6 4
4 2
2 10–1
10–1 6
4
6
4 FWJ-40A 2
FWJ-50A
2 FWJ-60A 10–2
FWJ-70A 6
10–2 4
FWJ-80A
6 FWJ-90A
4 2
FWJ-100A
FWJ-125A 10–3
2
FWJ-150A 6
10–3 FWJ-175A 4
6 2
4
10–4
2 2 4 6 8 2 4 6 8 2 4 6 8
103 104 105
10–4 Prospective Current
Prospective In Amperes
Current in AmpsRMS
2 4 6 8 2 4 6 8
102 103 104
Prospective Current In Amps RMS
Data Sheet: 35785309

Peak Let-Through Curve


2
FWJ-2000A
FWJ-1800A
105 FWJ-1600A
FWJ-1400A
FWJ-1250A
6
FWJ-1000A
FWJ-600A
4 FWJ-800A
FWJ-400A
FWJ-500A
FWJ-350A
FWJ-300A
2 FWJ-250A
FWJ-200A
FWJ-175A
Peak Let-Through Current

104 FWJ-150A
FWJ-125A
FWJ-100A
6 FWJ-90A
FWJ-80A
4 FWJ-70A
FWJ-60A
FWJ-50A
FWJ-40A
2

103

102
2 4 6 2 4 6 2 4 6 2 4 6
102 103 104 105
Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785303

112 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa


High Speed Fuses

North American Fuse Accessories

Fuse Bases (Blocks)


Modular Style
Cooper Bussmann offers a comprehensive line of fuse bases
that provide the user with design and manufacturing flexibility.
Two identical half bases make up a Cooper Bussmann®
modular fuse base. These “split” units can be panel mounted
any distance apart to accommodate any length fuse.

Stud Type (Not sold in pairs)


C5268 Series Stud Type
The simpler design is the C5268 Series modular fuse base.
With this design, the fuse terminal and cable (with
termination) are mounted on the same stud, minimizing labor
needed for installation. The stud type base is available in the
configuration shown in the table below.

High Speed
Catalog Max Fuse Stud Stud Dia.

Fuses
Number Amp Rating Height (in) & Threads
C5268-1 200 1.00 5
⁄16˝-18
C5268-2 200 1.75 5
⁄16˝-18
C5268-3 200 0.75 5
⁄16˝-18
C5268-4 100 1.00 1
⁄4˝-20
C5268-5 100 1.75 1
⁄4˝-20

Connector Type
BS Style Connector Type
Cooper Bussmann also offers a modular style fuse base that
utilizes a tin-plated connector (for wire termination and heat
dissipation) and a plated-steel stud (for fuse mounting). The
connector type fuse base is available in the configurations
shown below. Consult Cooper Bussmann for additional
product details.
Modular Max Max Fuse Data Sheet
Base Style Voltage Amp Rating Number
1BS101 600 100 1206
1BS102 600 400 1207
1BS103 600 400 1208
1BS104 600 600 1209
BH-0xxx 700 100 1200
BH-1xxx 2500 400 1201
BH-2xxx 5000 400 1202
BH-3xxx 1250 700 1203
Refer to page 275 for BH style holders.

Fixed Center
Fixed Center Base Style
Cooper Bussmann offers a comprehensive line of fixed
mount style fuse bases under the trademark TRON® rectifier
fuse blocks. The cable and fuse connections are similar to
the stud type fuse base — both are mounted on the same
stud. Consult Cooper Bussmann for complete product details.

For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 113