System Description HART Interface Solutions

Introduction HART Multiplexer Slave


HART
• Compact 20 mm housing
The K-system provides single- and multi-channel solutions for
HART applications. • HART field device inputs

The K-System HART Multiplexer works as a master/slave • Up to 16 field devices can be KFD0-HMS-16

system and when fully occupied can drive up to 256 HART connected 1

field devices. Up to 15 additional slaves can be connected to • Used with HART Multiplexer Master
K-System

the master, each of which can support another 16 channels. KFD2-HMM-16


This allows up to 7936 field devices to be addressed through 26

one RS 485 interface (31 addresses x 256 field devices).


The HART Loop Converter converts the HART
communication signal of a field device in analog values or trip
points.

Figure 3 20 mm housing (KFD0-HMS-16)


Multiplexers

HART Termination Boards


HART

The wiring of the single I/O components of the HART product


portfolio is done via a Termination Board. Since a wide variety
of Termination Boards are available, only the basic wiring
options are described here.
Field devices and DCS are
connected via Termination

32

30

28

26

24

22

20

18

16

14

12

10

2
Termination

Boards. The Termination


Boards

X1
Boards are designed to

31

29

27

25

23

21

19

17

15

13

11

1
establish the connection of a

C15

C13

C11

C9

C7

C5

C3

C1
Figure 1 K-System HART communication 1 2

KFD*-HM*-16 HART

C16

C14

C12

C10

C8

C6

C4

C2
Multiplexer to up to 16 field X2
R16
R15
R14
R13
R12
R11
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
devices.
Components
25 26

More detailed information to


FI-PFH-XXXXXX Y
connection layout can be PEPPERL + FUCHS

HART Multiplexer
32

30

28

26

24

22

20

18

16

14

12

10

2
found in the data sheet of the
HART Loop
Converters

HART Multiplexer Master according Termination X3


31

29

27

25

23

21

19

17

15

13

11

1
Board.
• HART field device inputs
• 16 field devices and up to 15
KFD0-HMS-16 slave units can Figure 4 HART Termination Board
KFD2-HMM-16

be connected 1

• Configured using PACTware™


ON
HART Loop Converter
• Power supply via Power Rail HART Loop Converters use the full
Accessories

26 potential of new and existing


13
19
14
20
15
21
16 17 18
multivariable HART field devices. 1 2 3 4 5 6
KFD2-HLC-
• HART input with transmitter supply Ex1.D.4S
1 PWR
IN /
CH K

• One field device can be connected OUT


1 2

3 4

• Up to 4 relay outputs RS232


ESC

OK

• 3 analog outputs 4 mA ... 20 mA


Figure 2 40 mm housing 7
13
8
14
9
15
10
16
11
17
12
18
(KFD2-HMM-16) • Sink and source mode output 19 20 21 22 23 24
11/2010

• Configurable by keypad
908837 (US) / 208599 (EU)

Figure 5 40 mm housing
(KFD2-HLC-Ex1.D.4S)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


528 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description

Topology
HART

HART Multiplexer
A wide variety of Termination Boards are available. For additional information about topology, refer to HART Multiplexer System
manual.
Multiplexer Master and Slaves are connected to Termination Boards, which transmits the control signals via screw terminals. In

K-System
this case the Termination Board provides a parallel connection to the Multiplexer or Slave. This assembly method is completely
independent of DCS.
For hazardous location applications, the intelligent field device must be isolated from the safe area via a K-System isolator. The
isolated signals are then connected to Termination Boards, where a parallel connection to the Multiplexer or Slave is made via a
26-pin ribbon cable.

HART
HART
HART

Multiplexers
HART
Isolated
DCS barriers

PEPPERL + FUCHS PEPPERL + FUCHS

16 32 32 16 16 32 32 16

Up to
16

Termination
field devices

Boards
1 17 17 1 1 17 17 1
X2 X1 X2 X1
2 26 2 26
IDC connector IDC connector
1 25 1 25

Termination
X3 X3

Board
Power Rail insert
Management
software 26-pin ribbon cable
1 2 3

HART Loop
4 5 6

Converters
KFD2-EB2 KFD2-HMM-16 KFD0-HMS-16

ON
ERR PWR ON

S1 I II

5 AT

13 14 15 16 17 18
19 20 21

7 8 9
10 11 12
13 14 15
Converter
14-pin ribbon cable DIN Rail
RS 232

RS 485 up to 15 HART Multiplexer Slaves per Master Accessories


24 VDC

Figure 6 Example of HART Interface topology


11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 529
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions

HART Loop Converter


HART
The HART Loop Converter has an active and passive input
HART
for the field device. The active input can be used for the HART
transmitter supply. When using the passive input (passive
mode), the HLC connected in parallel to the existing field
circuit and performs the communication.
R
4 mA ... 20 mA
K-System

Active input
Transmitter supply
The active input is used for supply of a transmitter. The
measured value is transmitted via the HART communication 1 2
4 5
3
6
1 2 3 4 5 6
not via the 4 mA ... 20 mA signal. The field device KFD2-HLC-
Ex1.D.4S KFD2-STC4-Ex1.2O.H

(transmitter) is connected to terminals 1(+) and 3(-). The IN /


CH K
1

1 2
PWR

terminals 4 and 5 are jumpered. OUT


3 4
PWR
ESC

RS232

OK

7 8 9 10 11 12
13 14 15 16 17 18
Multiplexers

19 20 21 22 23 24

HART 7 8 9
10 11 12
HART

13 14 15

Figure 8 Signal transfer with HART Loop Converter (HLC)


– connection to existing field circuit
Termination

1 2 3 4 5 6
KFD2-HLC-
Boards

Ex1.D.4S
PWR
IN /
CH K
1

1 2
Connection to field device with active current output
OUT
3 4

ESC If the HART Loop Converter is connected to an active current


RS232

OK source of a 3-wire or 4-wire field device, in addition to the


7
13
8
14
9
15
10
16
11
17
12
18
connection to terminals 2(+) and 3(-), terminals 5 and 6
19 20 21 22 23 24
should be jumpered.
HART Loop
Converters

HART

Figure 7 Signal transfer with HART Loop Converter (HLC)


– active mode

Passive input
Accessories

Connection to existing field circuit 1 2 3 4 5 6


KFD2-HLC-
Ex1.D.4S

The HART Loop Converter can be connected in parallel to an IN /


CH K
1 PWR

1 2

existing, externally-powered field circuit. The field circuit is OUT


3 4

connected to terminals 2(+) and 3(-). RS232


ESC

OK

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
11/2010
908837 (US) / 208599 (EU)

Figure 9 Signal transfer with HART Loop Converter (HLC)


– connection to field device with active current source
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


530 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description

Mounting and supply Mounting on Power Rail


HART
The HIS devices of K-System are mounted on a As shown in the figure, the isolation modules are snapped
35 mm DIN rail acc. to EN 60715. To reduce wiring and onto the Universal Power Rail in a vertical downward
installation costs, Power Rail is the optimum solution. movement.
Low heat dissipation allows vertical or horizontal mounting.

K-System
Power Rail
The Power Rail is a plastic insert into a standard DIN rail and
contains two leads that deliver power to the modules. Power
is sent through the rail by a power feed module that delivers
24 V DC at 4 A. The module uses a 5 A fuse to protect the
barriers. The Power Rail virtually eliminates the risk of wiring
faults and facilitates easy expansion. Power Rail is available
in two versions:
• UPR-03: 3-lead version supplies two leads for power and
one lead for error signal

Multiplexers
• UPR-05: 5-lead version supplies two leads for power, one

HART
lead for error signal and two leads for serial data
exchange.

Figure 11 Proper K-System mounting

CORRECT: Device snapped on vertically.

Termination
Boards
Figure 10 Universal Power Rail UPR-05

HART Loop
Converters
Accessories
Figure 12 Improper K-System mounting

INCORRECT: Device snapped on from the side.

Mounting the Termination Board


11/2010
908837 (US) / 208599 (EU)

Figure 13 Termination Board mounting on DIN rail


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 531
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions

Conventional power supply without Safety information


HART
Power Rail
The corresponding data sheets, the Declaration of
Conventional power supplies create complicated and Conformity, the EC-Type Examination Certificate and
expensive wiring systems. After all isolated barriers are applicable certificates (see data sheet) are an integral part of
connected, there is a significant amount of wiring and more this document.
wiring must be added for features such as lead breakage and
K-System

short-circuit monitoring. Intended use


Laws and regulations applicable to the usage or planned
purpose of usage must be observed. Devices are only
approved for proper usage in accordance with intended use.
1 2 3 1 2 3 1 2 3 1 2 3 Improper handling will result in voiding of any warrantee or
4 5 6 4 5 6 4 5 6 4 5 6
DIN Rail
manufacturer's responsibility.
These devices are used in C&I technology for the galvanic
isolation of C&I signals, such as 20 mA and 10 V unit signals,
and also for the adaptation and/or standardization of signals.
The devices are not suitable for the isolation of signals in
Multiplexers

power engineering, unless this is specifically referred to in the


HART

7 8 9 7 8 9 7 8 9 7 8 9
10 11 12 10 11 12 10 11 12 10 11 12
respective data sheet.
Protection of operating personnel and the system is not
ensured if the product is not used in accordance with its
intended use.

24 V DC Installation and commissioning


Termination

Figure 14 Conventional installation Commissioning and installation must be carried out by


Boards

specially trained and qualified personnel only.

Power supply with Power Rail Installation of the interface devices in the
The Pepperl+Fuchs Power Rail eliminates wiring hassles and safe area
reduces expense. The power feed module mounts on the
Power Rail for easy and reliable distribution of power to all The devices are constructed to satisfy the IP20 protection
connected isolated modules. This method eliminates all of the classification and must be protected from adverse
parallel power wiring necessary on a conventional installation environmental conditions such as water spray or dirt
HART Loop

exceeding the pollution degree 2.


Converters

without Power Rail.


The devices must be installed outside the hazardous area!
Power Feed Power Rail HART Loop
Module Converter
Installation and commissioning of the
interface devices within Zone 2/Div. 2 of
the hazardous area
1 2 3
4 5 6
1 2 3 4 5 6 Only devices with the corresponding manufacturer's
KFD2-HLC-
Accessories

KFD2-HMM-16 Ex1.D
ERR PWR
Declaration of Conformity or separate certificate of conformity
ON
can be installed in Zone 2/Div. 2.
RS232
ESC
The individual data sheets indicate whether these conditions
are met.
OK

7 8 9 10 11 12
13 14 15 16 17 18 13 14 15 16 17 18
19 20 21 19 20 21 22 23 24

7 8 9
10 11 12
13 14 15
11/2010
908837 (US) / 208599 (EU)

24 V DC HART Multiplexer Master

Figure 15 Power Rail installation

For additional information about connection, refer to system


description Isolated Barriers K-System.
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


532 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
For US and Canada installations, in Zone 2/Div. 2 follow the Technical data
NEC and CEC wiring methods. The enclosure must be able to HART
accept Zone 2/Div. 2 wiring methods. The referenced product
certification control drawing must be observed. Electrical data
For all other applications, the devices should be installed in a For electrical data, see data sheets.
switch or junction box that:
Mechanical data

K-System
• meets at least IP54 in accordance to EN 60529.
• meets to the requirements of resistance to light and Mounting
resistance to impact according to EN 60079-0/ • Snap-on 35 mm standard DIN rail acc. to EN 60715. Can
IEC 60079-0. be mounted horizontally or vertically, side by side.
• meets to the requirements of thermal endurance • Panel mount: The lugs on the base of the modules must
according to EN 60079-15/IEC 60079-15. be extended and used for mounting purposes with 3 mm
• must not cause ignition danger by electrostatic charge screws.
during intended use, maintenance and cleaning. • K-MS mounting base for screw attachment
The EC-Type Examination Certificates, standard
certificates/approvals or the manufacturer's Declaration of Mass

Multiplexers
Conformity should be observed. It is especially important to Termination Boards: 200 g to 400 g

HART
observe the "special conditions" if these are included in the
Modules: 100 g to 250 g
certificates.
Housing material
Repair and maintenance Polycarbonate (PC)
The transfer characteristics of the devices remain stable over Dimensions
long periods of time. This eliminates the need for regular
adjustment. Maintenance is not required. Housing drawings please refer to the appendix.

Termination
Protection degree

Boards
Fault elimination
Modules: IP20 acc. to EN 60529
No changes can be made to devices that are operated in
hazardous areas. Repairs on the device are not allowed. Connection
• Removable connector with integrated self-opening device
Isolation coordinates for installations for terminals for leads of up to a max. of 1 x 2.5 mm2
galvanic isolation according to EN 50178 (14 AWG)
and EN 61140 • Signal connection via ribbon cable

HART Loop
Converters
The devices of the K-System are electronic equipment for use Labeling
in secluded electrical operating sites where only skilled
personnel or electrically instructed personnel will have place for labeling on the front side, label: 8 mm x 18 mm
admission or access.
The devices are assessed for pollution degree 2 and
overvoltage category II according to EN 50178.
For additional details, see data sheets.

Accessories
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 533
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

You might also like