You are on page 1of 8

41/1

41 Heat pumps and


their applications

Andy Neave BSc (Hons), MBA, AMIMechE


Calorex Heat Pumps Ltd, Maldon, Essex

Contents
41.1 What is a heat pump? 41/3

41.2 Types of heat pumps 41/3

41.3 Coefficient of performance 41/3

41.4 Thermodynamic cycles 41/4


41.4.1 Mechanical vapour compression cycle 41/4
41.4.2 Mechanical vapour recompression 41/4
41.4.3 Absorption cycle 41/5

41.5 Climate change levy 41/5

41.6 Industrial applications 41/6


41.6.1 Heating 41/6
41.6.2 Cooling 41/6
41.6.3 Air conditioning 41/6
41.6.4 Heat recovery 41/6
41.6.5 Dehumidification 41/7
41.6.6 Swimming pools 41/7
41.6.7 Process drying 41/8
41.6.8 Evaporation and distillation 41/9

41.7 Sources of further information 41/9

This page has been reformatted by Knovel to provide easier navigation.


41.1 What is a heat pump? recovery device, such as a plate heat exchanger, where the
maximum temperature available is just below the source
Heat pumps are mechanical devices that extract low-grade water temperature.
heat from one source and transfer the heat to another. The
advantage of a heat pump is that it up-grades the heat and
delivers it at a higher temperature than the source from 41.2.1.5 Geothermal or ground source
which the heat was extracted.
A geothermal or ground source heat pump is a variant
Heat pumps are usually based on refrigeration cycles.
on either a water-to-air or a water-to-water heat pump. In
Unlike refrigerators the primary aim of heat pumps is to
this case the energy source is from the ground, from a
provide heating, although reverse cycle heat pumps can
bore-hole, ground water or a ground loop.
provide both heating and cooling.
A ground loop is a closed circuit of pipe that is buried
Much of the technology used in heat pumps is identical
1-1.5m below ground level. Water circulated through
to that used in refrigeration plant. The bias to heating,
this loop of pipe will be returned at ground temperature
however, changes the emphasis of the design of the
(a constant 10-120C in the UK) throughout the year.
refrigeration circuit towards the condenser.
The length of pipe required and the area covered by the
loop will depend on the amount of energy that is to be
extracted.
41.2 Types of heat pumps A single bore-hole can be used in conjunction with a
closed loop of pipe as above. Alternatively two can be
Heat pumps are characterized by the mediums between drilled to exchange water with naturally occurring water
which they transfer heat. There are three primary sources bearing rock strata.
of energy, air, water and the ground. The heat extracted
can be transferred to heat air or water, although it would
also be possible in a cooling application to reject heat to 41.3 Coefficient of performance
the ground.
The measurement of efficiency of a heat pump is known
as the Coefficient of Performance or COP. This is defined
41.2.1.1 Air-to-air as:-
In an air-to-air heat pump energy is extracted usually from Total energy given out
ambient air and transferred to heat or cool a second air Energy used to drive heat pump
stream.
Ambient air is the most common energy source used The energy given out by a heat pump is equal to the
by heat pumps. It should be remembered that air contains energy recovered from the heat source plus the energy
energy down to very low temperatures i.e. the point at input from the driving force. The COP of a heat pump
which its constituents, Nitrogen and Oxygen, become will therefore always be greater than 1, as the power input
liquids. will always be added to the heat sink.
The energy in air comes from two sources, the sensible COPs of 2.5 to 3 are common, and in some situations
energy available from reducing the temperature of the air, can be as high as 5 or 6. The COP of a heat pump is
and the latent energy available from the water content of seldom constant as it depends on the temperature of the
the air. The water content of air varies with its condition heat source and the heat sink.
but is approximately 1 per cent by volume. As a point of comparison, the COP of a boiler operating
at 80 per cent efficiency would be 0.8 and of a heat
exchanger with a heat transfer efficiency of 65 percent
41.2.1.2 Air-to-water would be 0.65.
In an air-to-water heat pump energy is transferred from
ambient air, as above, to a water heating circuit. See
Figure 41.1.

41.2.1.3 Water-to-air
In a water-to-air heat pump heat is transferred from a
water circuit to heat an air stream. This can be viewed as
heating the air stream or alternatively, if the air is ambient,
as cooling the water circuit.

41.2.1.4 Water-to-water
In a water-to-water heat pump energy is transferred from
one water circuit to another at a higher temperature. This
gives the heat pump an advantage over a passive heat Figure 41.1 Small heat pump
41.4 Thermodynamic cycles
41.4.1 Mechanical vapour compression
cycle
The majority of heat pumps use the vapour compression
cycle, exactly the same as used in refrigeration. See
Figure 41.2.
In this type of cycle a mechanical compressor provides
the energy input into the cycle. The working fluid is

Pressure
termed the refrigerant. There are four stages to the cycle
(refer to Figures 41.2 and 41.3):-
1. Heat is absorbed from the energy source into the
evaporator. In the evaporator the refrigerant changes
from a liquid to a gas at a constant pressure. The
refrigerant is vaporized or evaporated.
2. The compressor raises the pressure and temperature
of the refrigerant. The refrigerant goes from being a
saturated gas/vapour to a super-heated vapour.
3. The heat absorbed by the refrigerant and the energy Enthalpy
added by the compressor is released from the cycle as
the refrigerant passes through the condenser. In the Figure 41.3 Pressure Enthalpy diagram of a vapour compression
condenser as energy is rejected to the heat sink at cycle
constant pressure the refrigerant changes from a super-
heated vapour back to a liquid. The gas condenses. However, practical considerations often limit their use to
4. The high pressure, high temperature liquid passes larger applications.
through an expansion device, either a valve or a capil-
lary. The pressure of the refrigerant is reduced back to 41.4. Ll Refrigerants
the lower evaporating pressure. The temperature of the
refrigerant also reduces during the expansion process. The most commonly used types of refrigerants are fluo-
The refrigerant is now a mixture of liquid and vapour rinated hydrocarbon compounds. These are either hydro-
as it passes back into the evaporator. chlorofluorocarbons (HCFCs) such as R22 or hydrofluo-
rocarbons (HFCs) such as R407c, R134a or R410a.
It is common for the cycle to be reversed so that Hydrocarbons Butane and Propane are finding use in
cooling becomes the priority, rather than the primary aim small appliances such as domestic dehumidifiers where
of heating. their flammability is not a major concern due to the low
There are many types of compressor used in this type of quantities used. Ammonia has traditionally been used in
cycle, e.g. reciprocating, screw, rotary, vane, centrifugal, large commercial and industrial applications, and systems
swing or scroll. They are usually driven by an electric using carbon dioxide are under development.
motor.
The use of compression devices driven by other forms 41.4.1.2 Legislation
of energy is possible. The most common alternatives are
the use of prime mover such as gas or diesel engines. Legislation on ozone depletion and global warming has
forced the refrigeration industry to develop equipment to
use alternative and new refrigerants.
High pressure side The production of old CFC refrigerants, such as R12,
has now been banned due to its effect on the ozone layer.
Condenser It has an ozone depletion factor (ODF) of 1. The use
of R12 for maintenance has been banned from 1 January
2001.
Although the production of HCFC R22 with an ODF
Jixpansion_ of 0.1 is not due to be phased out until 2009, European
valve equipment manufacturers will be forced to cease produc-
Compressor tion of equipment using HCFCs before 1 January 2004
at the latest. For some countries and types of equipment
earlier phase out dates apply. The use of recycled R22 for
maintenance will be allowed until 2015.
Evaporator
41.4.2 Mechanical vapour recompression
Low pressure side
Mechanical vapour recompression (MVR) heat pumps use
Figure 41.2 Vapour Compression Cycle the process fluid as the working fluid, usually in an open
or semi-open cycle. These systems often use water vapour The stages in the absorption process are:-
or steam as the working fluid.
In an open cycle vapour from an industrial process is 1. The evaporator absorbs heat from the energy source.
compressed to a higher pressure and consequently to a The energy absorbed evaporates some of the refrigerant
higher temperature. Once expanded through a nozzle or vapour from the liquid absorbent.
venturi the vapour is condensed in the same process giving 2. The vapour passes into the absorber where it is dis-
off heat. solved into the absorbent, releasing some energy and
In a semi-open cycle the heat from the compressed concentrating the solution. The heat sink fluid is usu-
vapour is transferred to the process via a heat ally passed through the absorber prior to the condenser
exchanger. in order to collect and remove this released energy.
Compared with the closed vapour compression cycle 3. Some of the solution is pumped to the generator, its
described above these systems eliminate the use of one pressure being raised to that of the condenser.
or two heat exchangers, and as the temperature difference 4. Heat is added to the generator to raise the temperature
between heat source and heat sink is low the performance of the solution and evaporate the refrigerant vapour out
of MVR systems is high. Typically COP of 10-30 can be of the solution. This reduces the concentration of the
achieved. Current MVR systems operate with heat source solution.
temperatures of 70-8O0C and deliver heat at between 110 5. The weaker solution from the generator is then passed
and 15O0C. back to the absorber, via an expansion valve to equalize
pressures. The solution in the absorber is diluted and
so can continue to absorb vapour without becoming
41.4.3 Absorption cycle saturated.
6. The high temperature, high-pressure vapour from the
The operation of the absorption refrigeration cycle is sim- generator passes into the condenser. Here the useful
ilar to the above vapour compression cycle. The evap- heat is rejected to the heat sink and the vapour is con-
orator, condenser, and expansion device serve common densed back to a saturated liquid at constant pressure.
purposes, but a heat-operated absorber and regenerator 7. The refrigerant vapour returns to the evaporator via
replace the compressor. A schematic of the absorption the expansion device, which reduces the pressure and
cycle is shown in Figure 41.4. temperature of the vapour. Prior to the collection of
In the absorption cycle the refrigerant vapour is dis- further heat from the energy source.
solved in a suitable liquid. The power required to pump
the working fluid around the cycle is less than that There are a number of practical drawbacks that limit the
required compressing a refrigerant vapour. applicability of this refrigerant cycle.
There are two common fluid pairings used. In smaller
equipment the refrigerant used is ammonia and the 1. Achievable COPs are low, typically 1.2 to 1.4.
absorbent used is water. In larger equipment the refrig- 2. Equipment sizes for lithium bromide/water systems are
erant is water and a solution of lithium bromide is used large.
as the absorbent. 3. Concentrations of fluids are critical for stable operation.
4. Practical systems are complex.
5. Operating ranges are restricted by fluid pair-
Generator Condenser
ings. Lithium bromide/water systems cannot oper-
ate below freezing. Ammonia/water systems are
Heat
in Heat restricted in top temperature due to high
out pressures.
High temp
side
However, these types of systems have found success
where heat is available from a cheap source, or as waste
heat from an existing process. Some smaller gas fired
equipment has also been developed.
Absorbant
pump Flpw_ Expansion
control device
41.5 Climate change levy
The Climate Change Levy being introduced by the Gov-
Low temp ernment will oblige businesses to pay a levy on their
side energy bills. One of the aims of this legislation, along-
Heat side reducing CO2 emissions, is to provide an incentive
in for businesses to reduce their total energy usage and to
Heat look at how efficiently they use energy.
out
Absorber Evaporate Heat pumps can be beneficial in reducing energy usage
in a number of applications, and so could be helpful in
Figure 41.4 Absorption Cycle reducing the levy imposed.
41.6 Industrial applications ambient temperatures e.g. the Far East and Mediterranean
countries, the use of air-to-water heat pumps to gener-
41.6.1 Heating ate hot water for domestic and commercial/hotel use is
common.
41.6.1.1 Buildings However, hot water production when waste process
General heating for buildings using heat pumps is more water is available as a heat source can be viable, see
frequently used in Europe where district heating schemes section 41.6.4 below.
are more common. Here the higher initial capital cost
of a heat pump can be spread over a larger number of 41.6.2 Cooling
properties. These are water-to-water heat pumps, or air to The most common chillers providing chilled water to
water units often used in conjunction with low capacity industrial processes are air-cooled water-to-air heat pumps
back-up heating for the coldest periods of the year. or water-cooled water-to-water heat pumps. The cooling
In the USA air-to-air and ground source water-to- duty of these chillers is always larger than the energy
air heat pumps are commonly used in domestic heating input, the COP is greater than one.
where air distribution heating systems are the norm. This The absorption cycle can be found used in industrial
usage occurs particularly in areas where higher average chillers, particularly those of high capacity that can be
ambient temperatures allow higher heat pump COPs or driven by a waste heat source, perhaps even linked to a
where a ground source is available or a ground loop can CHP plant.
be accomodated. These units are often reverse cycle to Gas fired vapour absorption chillers are becoming
provide cooling in the summer. increasingly common. Small packaged units of 5OkW
Use in the UK is limited by the cost of available cooling capacity are available on the market.
alternative energy sources e.g. low cost gas. Here gas
fired boilers traditionally work in conjunction with a wet
radiator system. Even allowing for the inefficiencies of
41.6.3 Air conditioning
boilers the COP of a heat pump would have to be in excess Reverse cycle split air conditioning units are called 'heat
of 3 in order to give any running cost saving to fund the pumps', although the cooling only versions are also air-
higher initial cost of a heat pump, based on the present to-air heat pumps. These heating and cooling systems
differential between electrical and gas energy prices. are a viable alternative to cooling only air conditioning,
The COP of an air-to-water heat pump falls during cold eliminating the need for a separate heating system. They
weather just when the most heating is needed. A unit are finding increasing use in commercial and industrial
operating in air temperatures of 50C and producing water office buildings.
at 550C would have a COP of 2-2.5. The 'Versatemp' type water based system is a unique
The increased use of under-floor heating operating concept that has been on the market for many years. In this
at approx. 4O0C has increased the consideration given system individual reverse cycle water-to-air heat pumps
to using ground source heat pumps. With a constant are located in each room in a building. They exchange
source temperature of 10-120C the COP of the heat heat with a two-pipe water circuit providing heating or
pump remains stable at around 3-3.5. In this scenario, cooling to the space as required. This water circuit is kept
particularly where gas is not available, the viability of a constant temperature by a central heating and cooling
heat pumps for heating looks a lot more favourable. plant, which could be a reverse cycle water-to-water,
water-to-air or ground source heat pump. The system can
41.6.1.2 Hot water simultaneously provide cooling on one side of a building
exposed to solar gain and heating to the other side in
Heating hot water using heat pumps suffers similar com- shade.
parisons in the UK. In other areas of the world with higher
41.6.4 Heat recovery
Heat recovery from industrial processes is perhaps the
most under-used application for heat pumps.
Heat recovery can be from both air and water, with the
most viable heat sink being water. Water can be heated
to as high as 7O0C lending itself to direct use in heating
buildings or domestic hot water, or for preheating water
for the same or another process.
There are many situations in which dynamic heat recov-
ery using a heat pump is superior to a passive heat recov-
ery device such as a plate heat exchanger or air-to-air
cross-flow heat exchanger.

41.6.4.1 Recovery from water


Figure 41.5 Example of a dehumidified body panel storage area An example would be where waste process water at a low
(Courtesy of Calorex Heat Pumps Ltd) temperature of 20-3O0C is discharged to drain. A passive
device could only recover heat by heating an incoming
water supply to 5-1O0C below the discharge temperature.
A water-to-water heat pump could recover this waste
energy and up-grade it to a higher temperature, heating
the second water circuit to 7O0C, or more efficiently to a
slightly lower level. This pre-heated water could be fed
to a boiler to be boosted for use in another part of the
process.
41.6.4.2 Recovery from air
It is similarly practical to recover heat from a ventilation
exhaust air stream. The recovered energy can be directed
towards the make-up air or to water, either to pre-heat
process water or to heat domestic hot water.
The practicality of such a heat recovery scheme is
limited by the proximity of the heat source and the heat
sink. If long water or refrigeration pipework runs are Figure 41.6 Typical refrigerant dehumidifiers (Courtesy of Calorex
required the installation cost and heat losses can out- Heat Pumps Ltd)
weigh the energy cost savings made by the installation
of a heat pump. to negligible levels see Figure 41.5. The advantage of a
There are examples where air-to-water heat pumps are package heat pump dehumidifier is that they can oper-
being used to cool over heated plant room spaces. The ate in an unheated warehouse, so eliminating the need to
recovered energy is used to pre-heat water for hot water heat the space (except for human comfort) and providing
calorifiers, and the cooling effect extends equipment life a considerable running cost saving alongside the initial
of plant installed in the space. benefit of protecting the stored product. If dehumidifica-
41.6.4.3 Practical limits tion is planned from the start it can also eliminate the
need for an insulated building to be constructed saving
The operating conditions in which a heat pump can be considerable capital cost. Figure 41.6 shows a range of
used for heat recovery applications is limited first by refrigerant dehumidifiers with capacities from 30 litre/day
the characteristics of the working fluid, and then by the to 600 litre/day at 2O0C and 75% RH.
mechanical components.
For example, an electrically driven mechanical vapour 41.6.5.2 Excess moisture
compression heat pump will be limited to an operating
temperature range of -150C to 7O0C by the refrigerant Many industrial processes produce moisture in enclosed
gases used. spaces. Dehumidifiers can be an energy efficient way of
removing the excess moisture from the space reducing
41.6.5 Dehumidification condensation and similar damaging effects on buildings,
equipment and products. They can replace the need for
A refrigerant cycle based dehumidifier is a type of air- ventilation with high volumes of air that need to be heated
to-air heat pump. The evaporator is designed to reduce to comfort levels before being dumped into the atmosphere
the temperature of the air to below its dew point. The along with the entrained moisture. The heat recovered by
condensation that forms on the evaporator is collected the dehumidifier can be used to assist in space heating
and fed to a drain. The latent energy absorbed by the or process water heating, providing a secondary energy
refrigerant is returned into the air stream passing through saving to justify the capital outlay for a dehumidifier.
the dehumidifier as sensible heat. Typically a heat pump
dehumidifier will return 3 times as much heat energy as
is used by the compressor. 41.6.6 Swimming pools
Dehumidifiers can be configured to have an extra water
condenser to recover heat to water, if this was a more 41.6.6.1 Outdoor
viable use for the recovered energy. Air-to-water heat pumps are commonly used for summer
heating of swimming pool water, in both commercial and
41.6.5.1 Storage domestic situations.
Many storage warehouses require, or can benefit from, a These are usually electrically driven vapour compres-
controlled humidity condition to protect the stored prod- sion heat pumps. With ambient air temperatures from
ucts. For instance paper and board products, hygroscopic 1O0C to 3O0C during a May to September swimming
materials as varied as cement and sugar, timber, textiles season and required water temperatures of 25-3O0C, the
and steel. Dehumidifiers can limit the relative humid- coefficient of performance of a heat pump varies between
ity in a building to below 70 per cent to prevent mould 3.5 and 5.5. This gives favourable running costs even
growth, to prevent dimensional change, or degradation compared with gas fired boilers.
of a product, and in the case of steel if the humidity Initial capital costs can be comparable with conven-
is kept below 50 per cent RH corrosion can be reduced tional boilers in this application, as the installation of a
heat pump is simpler, with no requirement for flues, water content, and where the time available for the drying process
pumps, fuel tanks and associated accessories. is a number of hours. Figure 41.7 shows an example of a
drying chamber using a heat pump dehumidifier.
41.6.6.2 Indoor There is no reason why heat pump dehumidification
All indoor swimming pools require heating of both the drying cannot be applied to a continuous process. There
pool hall air and pool water. They also require dehumid- would need to be sufficient dwell time in the drying
ification to control the moisture that evaporates from the oven for the moisture to be extracted. The total moisture
pool surface. Dehumidification is required to protect the extraction rate required will dictate the number and size of
building structure and to provide a comfortable environ- dehumidifier required. The greater the capacity required
ment for the users. A humidity level of 60 per cent RH the larger the capital cost of the drying system, as a greater
is considered desirable. proportion will be spent on the heat pumps. A point will
The use of heat pumps for dehumidification and heat be reached at which the additional cost of the heat pump
recovery for indoor swimming pools is a common and system compared to a conventional oven cannot be paid
well recognized practice. back in a realistic time frame by energy cost and other
Conventional practice 20 years ago was to use large savings.
quantities of fresh air to sweep the moisture out of the The products to be dried are usually loaded onto a
pool hall. A ventilation rate of 10-151itres/s per m2 of series of racked trolleys and moved into a chamber,
pool surface and wetted surround was specified. This see Figure 41.8. Chambers are either large enough to
fresh air was heated to 28-3O0C from winter ambient accommodate a whole shifts production or a number of
temperatures (typical design condition -30C) and then smaller chambers are used in rotation to give continuous
exhausted. Meanwhile the water was being continuously production.
heated to 26-280C to counteract losses from evaporation. At the start of a cycle heat is introduced to speed
This used large quantities of energy to heat the air and up the release of moisture from the product. Air is re-
further energy to maintain water temperatures. circulated within the chamber to move the evaporated
If any heat recovery was achieved it usually involved
a cross-plate heat exchanger between the two air streams.
This allowed some sensible heat to be recovered from the
exhaust air back into the incoming fresh air at an effi-
ciency of approx. 50-75 per cent. Therefore the majority
of latent energy available in the moisture evaporated from
the pool, was exhausted to atmosphere and wasted.
A heat pump based dehumidification system can recover
the sensible energy and also the majority of the latent
energy. This energy can be transferred back into the pool
water and also used to assist in heating the pool hall air.
By re-circulating the pool hall air and limiting the fresh
air input to that required for occupants and odour dilution
the energy input could be further reduced.
At pool hall air conditions of 3O0C and 60 per cent RH
a heat pump dehumidification system will have a COP
of 5. This gives rise to energy efficient maintenance of
the pool hall environment, allowing operators to see a Figure 41.7 Dehumidification drying chamber for cardboard tubes
saving of up to 66 per cent in running costs compared to (Courtesy of Caiorex Heat Pumps)
a 100 per cent fresh air system. Payback periods of less
than 3 years are possible on refurbishment projects.

41.6.7 Process drying


The drying of products is an established application for
using heat pumps. The heat pumps used are air-to-air
heat pump dehumidifiers, so the process is often called
dehumidification drying.
Drying is an important part of many industrial pro-
cesses, and there are a number of different technologies
available for drying. The drying method most applicable is
dependent on a number of factors such as the throughput
of product, the drying time available, the required mois-
ture content, the nature of the product and how it can be
handled.
Dehumidification drying is most applicable to batch pro- Figure 41.8 Example of racked trolley used in drying chamber
duction processes for products with a high initial moisture (Courtesy of CHP Ltd)
moisture away from the drying products towards the 41.6.8 Evaporation and distillation
dehumidifiers. The dehumidifiers then extract the moisture
and recover the latent energy. This is then returned as Evaporation and distillation are energy intensive pro-
sensible heat back into the chamber so maintaining the cesses and a number of heat pumps are installed in these
operating temperature. The warm dry air is then circulated processes in the chemical and food industries.
In evaporation processes it is the residue that is the
backed past the drying products to extract more moisture.
product, whereas in distillation it is the vapour, or dis-
The latent heat recovery of the air-to-air heat pump tillate, that is the product of the process. The advantage
dehumidifier makes a dehumidification drying chamber of using a heat pump is that heat is recycled within the
highly energy efficient especially when compared with a process so reducing energy costs.
conventional hot air drying oven. Most of the heat pumps used are MVR open or semi-
The ability to be able to control both the temperature open cycles. For instance they are used in distilleries for
and humidity of the process allows a drying regime to be pot ale concentration.
tailored to suit a particular product.
The depressed vapour pressure created by the dehu-
midifier sets up a high enough differential vapour pressure 41.7 Sources of further information
between the product and the air, for the process to operate
effectively at much lower temperatures than a conven- UK Heat Pump Network. Managed for the DETR by
tional drying oven. Typically a dehumidification drying Building Services Research & Information Association
(BSIRA). Contact: Dr Sandra Gomez, BSIRA, V wing,
chamber operates at 40-7O0C compared with the typical
TRL, Old Wokingham Road, Crowthorne, Berks. RG45
120-20O0C for a gas fired oven. This can give positive
6XA. 01344750515.
benefits to the quality of the dried product and can allow Heat Pump Association (HPA). Contact Tony Bendall,
sensitive products that would have been damaged in a c/o FETA, Henley Road, Medmenham Marlow, Bucks,
conventional oven, to be dried more rapidly. SL7 2ER. Web-site: www.feta.co.uk.
The energy efficiency of the process means that consid- International Energy Agency (IEA) Heat Pump Centre.
erably less kWhrs are used in extracting a given amount Hosted by Novem the Dutch Energy and Environment
of moisture, reducing both the running costs and the COa Agency. Contact: Novem, PO Box 17, 6130 AA Sittard,
emissions. Payback periods of 1-2 years have been cal- The Netherlands. Web site: www.heatpumpcentre.org.
culated for capital investment in dehumidification drying Energy Efficiency Best Practice Programme. Managed
chambers on running costs alone. Add to this the addi- for the government by BRESCU (Building Research
tional benefits of improved product quality, higher product Establishment) for building applications, and ETSU for
throughput and reduced space required for drying and industrial applications. Contact: via free Environment and
heat pump dehumidification drying becomes an attractive Energy Helpline on 0800 585794
proposition. International Ground Source Heat Pump Association
A number of industries have a well proven track record (IGSHPA). 490 Cordell South, Stillwater, Oklahoma,
of using heat pump dehumidification drying chambers:- 74078-8018, USA. Tel: 001-800-626-4747. Web site:
www.igshpa.okstate.edu.
Geothermal Heat Pump Consortium, Inc. 701 Pennsyl-
Ceramic vania Avenue, NW. Third Floor, Washington DC, 20004-
Textile 2696, USA. Tel: 001-202-508-550, Fax: 001-202-508-
Paper & board 5222. Web site: www.ghpc.org.
Food & confectionery The British National Committee for Electroheat
Timber (BNCE), Heat Pump Group, Millbank, London, SWlP
Brick & block producers 4RD. Tel: 0207 963 5709.

You might also like