5 Design of Column Base


3.5.1 Support Location

BP-1 BP-2 BP-1

73 75 77 79 81 83

74 76 78 80 82 84

Node Number local-x

local-z

3.5.2 Design of BP-1


local-y
Design forces Node No.: 73 TO 76 83 84 Staad Member's Local Cordinate
A. Reaction summary obtained from STAADPro.

a. For factored load combinations, (Envelope-3)

Load Fx Fy Fz Mx Mz
Node Load type
combination kN kN kN kN-m kN-m

1764 75 Max Fx 306.26 -2.71 66.69 0.00 0.00


1999 76 Min Fx -68.52 -1.45 -62.75 0.00 0.00
1766 83 Max Fy 124.85 10.37 0.11 0.00 0.00
1999 84 Min Fy 102.49 -10.39 0.08 0.00 0.00
1764 75 Max Fz 306.26 -2.71 66.69 0.00 0.00
1769 75 Min Fz -49.93 1.83 -65.79 0.00 0.00

The design software used is RAM Connection, STAAD output is arranged as follows to match
RAM Connection.

RAM Connection Input


Fy→V2 Fz→V3 Fx→Axial Mz→M33 My→M22
Description
kN kN kN kN-m kN-m
MaxFx -2.71 66.69 -306.26 0.00 0.00
MinFx -1.45 -62.75 68.52 0.00 0.00
MaxFy 10.37 0.11 -124.85 0.00 0.00
MinFy -10.39 0.08 -102.49 0.00 0.00
MaxFz -2.71 66.69 -306.26 0.00 0.00
MinFz 1.83 -65.79 49.93 0.00 0.00

* BP Connection ID : 1