ELECTRICAL DESIGN
Tbilisi 2019
Explanatory Note
Electrical Part
List of Drawings
System Description
Drawings Description Remarks Electrical Part of the design is developed based on scope of work and requirements received from
ordering customer, and with consideration of other engineering systems. The design is developed based
EL-1 Drawing list, system general description / ნახაზების ჩამონათვალი
on design norms. Norms Used:
EL-2 PDB-1 switchboard diagram / PDB-1 ელ. გამანაწილებელი ფარის სქემა "PUE 6", "SNiP 25-05-95", EN 12464 -1_2011, SP 31-110-2003
EL-3 DB-1 switchboard diagram / DB-1 ელ. გამანაწილებელი ფარის სქემა Electrical power demand:
EL-4 Exterior Network power network plan / გარე ქსელის გეგმა Pd = 36.4 kW
Pn = 26.3kW
EL-5 Grounding loop plan / დამიწების კონტურის მოწყობის გეგმა The presented design includes documentation on the systems listed below:
EL-6 Basement floor lighting plan / სარდაფის სართულის განათების ქსელის გეგმა Power distribution;
Interior lighting;
EL-7 1st floor lighting plan / I სართულის განათების ქსელის გეგმა Fire Alarm System;
EL-8 Basement floor electrical sockets plan / სარდაფის სართულის როზეტების ქსელის გეგმა
Materials used:
EL-9 1st floor electrical sockets plan / I სართულის როზეტების ქსელის გეგმა
NYM type of Cables will be used for power mains and illumination network.
EL-10 Fire alarm system riser diagram / სახანძრო სიგნალიზაციის სისტემის სტრუქტურული სქემა
JY(st)Y-1x2x0,8 type cables will be used for fire alarm system network.
EL-11 Basement floor fire alarm system plan / სარდაფის სართულის სახანძრო სიგნალიზაციის სისტემის გეგმა
Electric Power Supply:
EL-12 1st floor fire alarm system plan / I სართულის სახანძრო სიგნალიზაციის სისტემის გეგმა
Electric Network Parameters: 230/400V 50Hz, TN-C-S
EL-13 Materials bill of quantities / მასალების სპეციფიკაცია Per Electric Power Supply the site belongs to sustainability 2nd category.
Grounding:
4 Ohm grounding system is required to be arranged at the site. There will be all main equipment, heat
distribution metal piping, water supply piping, cable trays and etc. connected to the grounding bar, for
which all corresponding grounding wires will be connected to the main grounding bar, located in the
power distribution board (PDB-1). From PDB-1 the grounding system will be distributed to all other sub
power distribution boards and consumers. Grounding circuit resistance shall not exceed R < 4 Ohms.
EL-1
GEN-1
33 KVA 400V 50Hz
DG-1
Power Distribution Board - PDB-1
L1 L2 L3 L1 L2 L3
PDB-1
MCCB MCB Pi=36,4 kW
3x63A 3x63A Pd=26,3 kW
PV
Inverter
Pi=36.4 kW
Pd=26.3 kW
DB-1
Power Distribution Board
EL-2
Electrical switchboard - DB-1
el. gamanawilebeli fari - DB-1
PE N L1 L2 L3
Dimensions / zoma 120 modulze
3xC63/6kA
Installation Type / montaJis tipi Cafluli
Safety Class / dacvis klasi IP40
Incoming Lines / Semavali xazebi zemodan Top / bottom
Outgoing Lines / gamavali xazebi zemodan Top / bottom
Installed power / dadgmuli simZlavre Pd 36.37
Demand power /moTxovnili simZlavre Pm 26.30
Power System / denis sistema 3N+PE, AC50Hz, 230/400V, TN-S
L1 L2 L3
1L1
1L2
1L3
2xC16/30mA
3xC25/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
N
PE
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 5 x 4
### QF1 QF2 QF3 QF4 QF5 QF6 QF7 QF8 QF9
Circuit # / jgufis # 1DB-P1 1DB-P2 1DB-P3 1DB-P4 1DB-P5 1DB-P6 1DB-P7 1DB-P8
Installed load (kW) 36.37 8,30 2,00 0,40 0,20 0,50 0,80 0,50 0,70
Demand load (kW) 26.30
Voltage / muSa Zabva (V) 400 400 230 230 230 230 230 230 230
Current / deni (A) 42.17 12.48 8.70 1.74 0.87 2.17 3.48 2.17 3.04
Mains circuit breaker Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket
Load Electric cooker
Semyvani saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo
daniSnuleba el. qura
a/amomrTveli rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi
EL-3/1
1L1 1L1
1L2 1L2
1L3 1L3
2xC16/30mA
2xC16/30mA
2xC16/30mA
2xC16/30mA
2xC16/30mA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
N N
PE PE
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
QF10 QF11 QF12 QF13 QF14 QF15 QF16 QF17 QF18 QF19 QF20 QF21
1DB-P9 1DB-P10 1DB-P11 1DB-P12 1DB-P14 1DB-P15 1DB-P16 1DB-P17 1DB-P18 1DB-P19 1DB-P20 1DB-P21
0,90 0,60 0,50 0,80 0,50 0,20 0,20 2,50 2,50 0,60 0,50 0,50
230 230 230 230 230 230 230 230 230 230 230 230
3.91 2.61 2.17 3.48 2.17 0.87 0.87 10.87 10.87 2.61 2.17 2.17
Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket Power Socket
saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo saStefselo
rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi rozetebi
EL-3/2
1L1 1L1
1L2 1L2
1L3 1L3
C16/6kA
C10/6kA
C16/6kA
C10/6kA
C10/6kA
C10/6kA
C10/6kA
C10/6kA
N N
PE PE
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
QF22 QF23 QF24 QF25 QF26 QF27 QF28 QF29
1DB-P25 1DB-M4 1DB-M6 1DB-L5 1DB-L6 1DB-L7 1DB-L8 1DB-L9
0,30 0,80 1,50 0,20 0,34 0,60 0,48 0,48
EL-3/3
1L1 1L1
1L2 1L2
1L3 1L3
C10/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C16/6kA
C10/6kA
0,4-0,63A
1,6-2,5A
KM1 2NO-25A AC1
A1 A1
A2 A2
N N
PE PE
NYM 3 x 1,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 2,5
NYM 3 x 1,5
NYM 3 x 1,5
QF30 QF31 QF32 QF33 QF34 QF35 QF36 QF37 QF38 QF39
1DB-M1 1DB-M2 1DB-M3 1DB-M5 1DB-P13 1DB-P22 1DB-P23 1DB-P24 1DB-P26 1DB-L1
0,20 0,40 0,10 1,50 0,70 1,00 0,20 0,60 0,60 0,28 0,12
230 230 230 230 230 230 230 230 230 230 230
0.87 1.74 0.43 6.52 3.04 4.35 0.87 2.61 2.61 1.22 0.52
Power Socket Power Socket Power Socket Power Socket Power Socket
Boiler Water pump Water pump Air conditioner Lighting Emergency lighting
saStefselo saStefselo saStefselo saStefselo saStefselo
gaTbobis qvabi wylis tumbo wylis tumbo kondicioneri ganaTeba avariuli ganaTeba
rozetebi rozetebi rozetebi rozetebi rozetebi
EL-3/4
1L1 1L1
1L2 1L2
1L3 1L3
C10/6kA
C10/6kA
C10/6kA
C10/6kA
C10/6kA
C10/6kA
C10/6kA
A2
-S 2 13 -S 3 13
A1
14 14
KM
A1
M1 M2
A2
N N
PE PE
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
NYM 3 x 1,5
QF40 QF41 QF42 QF43 QF44 QF45 QF46
1DB-L2 1DB-L3 1DB-L4 1DB-L10 1DB-L11 1DB-L12 1DB-EM1
0,36 0,02 0,35 0,22 0,02 0,30 0,30 0,30 0,40
Lighting Emergency lighting Lighting Lighting Emergency lighting Lighting Lighting Lighting Evacuation signs
ganaTeba avariuli ganaTeba ganaTeba ganaTeba avariuli ganaTeba ganaTeba ganaTeba ganaTeba saevakuacio niSnebi
EL-3/5
Legend:
1. Sector HQ building
2. Generator shed
3. Outside WC
Swamp
23 24
DB-1 1
PDB-1
Power cables in double Dirt R
oa
Ro
2
ad
Galvanized steel
strip 4x40mm
Rod / ღერო
D20 / 2,5m
15
<4Ω
Exterior Network power network plan
Grounding
EL-4
Loop < 4 Ω
1:200
Grounding Circuit Scheme
700
2500 2500
Legend
700
3x30mm 3x30mm
1
1
- Soil
2
500 2500 2500
2 3 3x30mm 3x30mm
- Strip 3x30mm
3x30mm 3x30mm
3 - Grounding Vertical Rod 2500
Ø=20mm 2500 2500
4 - Soil
Grounding Rod
Connector
Grounding Rod l=2,5m Grounding Rod l=2,5m
Grounding circuit resistance shall not exceed 4 Ohm. After its installation the resistance shall be measured.
If measured resistance exceeds 4 Ohm, vertical grounding rod shall be added to the grounding system.
After that, grounding system resistance shall be measured again.
EL-5
3 4 5
-2.700
10
11
1
2
3
4
5
6
7
8
9
D
-2.700
1DB-L9
NYM-3x1,5
Description / დასახელება
1DB-P7
NYM-3x2,5
Circuit number / cable type ჯგუფის ნომერი, კაბელის ტიპი, კვეთი
EL-6
2
1300
1
3600
a b
1DB-L12
NYM-3x1,5
1DB-L5
NYM-3x1,5 1DB-L6
NYM-3x1,5
1DB-L4
1DB-L3 NYM-3x1,5
1DB-EML4
NYM-3x1,5
NYM-3x1,5
DB-1 1DB-EM1
1DB-L8 1DB-L7
1DB-L11 NYM-3x1,5 NYM-3x1,5
NYM-3x1,5
NYM-3x2,5
1DB-EML2
1DB-L2 NYM-3x1,5
NYM-3x1,5
1DB-EML1
NYM-3x1,5
1DB-L1
NYM-3x1,5
1DB-L10
NYM-3x2,5
-2.700
10
11
1
9
D
-2.700
1DB-P25 1DB-P26
NYM-3x2,5 NYM-3x2,5
Description / დასახელება
Electrical switchboard
ელ. გამანაწილებელი ფარი
1DB-P7 Circuit number / cable type
NYM-3x2,5 ჯგუფის ნომერი, კაბელის ტიპი, კვეთი
Schuko type power socket 2P+E-16A
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A
Schuko type power socket 2P+E-16A, IP44
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A, IP44
Schuko type power socket 2P+E-16A, Surface Type Installation
ზედაპირული საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A
Schuko type power socket 2P+E-16A, IP65
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A, IP65
Cable direct supply point 1Ph - 230 V
კაბელის პირდაპირი მიყვანის წერტილი 1Ph -230 V
Cable direct supply point 3Ph - 400 V
კაბელის პირდაპირი მიყვანის წერტილი 3Ph - 400 V
Cable tray 150x60 mm
150x60
საკაბელო არხი 150x60 მმ
EL-8
LEGEND / პირობითი აღნიშვნები
Description / დასახელება
Electrical switchboard
ელ. გამანაწილებელი ფარი
1DB-P7 Circuit number / cable type
NYM-3x2,5 ჯგუფის ნომერი, კაბელის ტიპი, კვეთი
Schuko type power socket 2P+E-16A
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A
Schuko type power socket 2P+E-16A, IP44
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A, IP44
Schuko type power socket 2P+E-16A, Surface Type Installation
ზედაპირული საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A
Schuko type power socket 2P+E-16A, IP65
საშტეფსელო როზეტი დამიწების კონტაქტით, 2P+E-16A, IP65
Cable direct supply point 1Ph - 230 V
კაბელის პირდაპირი მიყვანის წერტილი 1Ph -230 V
Cable direct supply point 3Ph - 400 V
კაბელის პირდაპირი მიყვანის წერტილი 3Ph - 400 V
Cable tray 150x60 mm
150x60
საკაბელო არხი 150x60 მმ
1DB-M1
NYM-3x2,5
1DB-P5
1DB-M2 NYM-3x2,5
NYM-3x2,5
NYM-3x2,5 1DB-P12
NYM-3x2,5 NYM-3x2,5 NYM-3x2,5 NYM-3x2,5 NYM-3x2,5 NYM-3x2,5 NYM-3x2,5
150x60 NYM-3x2,5 150x60
150x60
RACK
1DB-P16 1DB-P4
NYM-3x2,5
24U DB-1 1DB-P8
1DB-P21 1DB-P6 NYM-3x2,5
NYM-3x2,5 NYM-3x2,5
NYM-3x2,5 1DB-P2
1DB-P24
NYM-3x2,5 1DB-P7 NYM-3x2,5
150x60
1DB-P22 1DB-P1
NYM-3x2,5 1DB-M6
NYM-5x4
NYM-3x2,5
1DB-P23
NYM-3x2,5
EL-9
JY(st)Y-1x2x0,8
I sarTuli
FACP
1LD- 10
1LD- 11
1LD- 12
1LD- 13
1LD- 14
1LD- 15
1LD- 16
1LD- 22
1LD- 23
1LD- 24
1LD- 25
1LD- 26
1LD- 27
1LD- 28
1LD- 29
1LD- 30
1LD- 31
1LD- 32
1LD- 33
1LD- 34
1LD- 35
1LD- 36
1LD- 37
1LD- 1
1LD- 2
1LD- 3
1LD- 4
1LD- 5
1LD- 6
1LD- 7
1LD- 8
1LD- 9
Loop1
0 sarTuli
1LD- 17
1LD- 18
1LD- 19
1LD- 20
1LD- 21
sardafis sarTuli
Description / დასახელება
EL-10
3 4 5
-2.700
10
11
1
9
D 1LD- 19
1LD- 18
1LD- 20
-2.700
1LD- 17
1LD- 21
JY(st)Y-1x2x0,8
Description / დასახელება
EL-11
1LD- 8 1LD- 25
1LD- 10 1LD- 12 1LD- 14 1LD- 16 1LD- 23 1LD- 27
1LD- 13
1LD- 24
1LD- 5
1LD- 2
1LD- 3
1LD- 37
1LD- 34
1LD- 6
1LD- 35
1LD- 1
JY(st)Y-1x2x0,8 1LD- 36
FACP
Description / დასახელება
EL-12