Given Data:
Column size 230x450mm
Pu = 1200kN
Mux = 20 KN-m
Muy = 24 KN-m
Fck = 25 N/mm2
Fy = 500 N/mm2
d’ = 60mm
=13.66mm or 20mm
=21mm or 20mm
ex = Mux/Pu= 16.66 mm
ey = Muy/Pu = 20.00 mm
P/fckbD =0.46
P%/fck =0.052
Pu/fckbD =0.46
P%/fck =0.052
4. Calculate αn
Pz =0.45fckAc + 0.75fyAsc
= 1673.62 KN.
Pitch:
The pitch of links shall not be more than, the least of following distances.
2. Sixteen times the smallest diameter of the longitudinal reinforcement bar to be tied =
16x12=192mm.
Spacing of hoops
3.300mm
As per Clause 8.2 of IS 13920:2016, Special Confining reinforcement shall extend for 300 mm
into the footing. It is extended for 300 mm as shown in fig.
𝑓𝑐𝑘
0.05 Sv h 𝑓𝑦
h = longer dimension of rectangular link measure to its outer face, which does not
exceed 300mm.
Column Design for Residential Quarter for Moshi Fire Station at Moshi
Given Data:
Column size 300x530mm
Pu = 1700kN
Mux = 7 KN-m
Muy = 50 KN-m
Fck = 25 N/mm2
Fy = 500 N/mm2
d’ = 60mm
=16mm or 20mm
=23.66mm or 20mm
ex = Mux/Pu= 4.11 mm
ey = Muy/Pu = 29.41 mm
(Use 04 Nos. 16mm- 804.4mm2 and 06 Nos. 12mm-678 mm2 =1483 mm2)
P/fckbD =0.43
P%/fck =0.036
Pu/fckbD =0.43
P%/fck =0.036
9. Calculate αn
Pz =0.45fckAc + 0.75fyAsc
= 2344 KN.
[(20 /93.15) ^1.85] + [(24 /47.61) ^1.85] = 0.058 + 0.28 =0.72 < 1.
Pitch:
The pitch of links shall not be more than, the least of following distances.
2. Sixteen times the smallest diameter of the longitudinal reinforcement bar to be tied =
16x12=192mm.
Spacing of hoops
3.300mm
As per Clause 8.2 of IS 13920:2016, Special Confining reinforcement shall extend for 300 mm
into the footing.
𝑓𝑐𝑘
0.05 Sv h 𝑓𝑦
h = longer dimension of rectangular link measure to its outer face, which does not exceed
300mm.