Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.

3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.0
Project :‐ Tanque septico rio frio Designed by:‐ Armando Jose Rivero
Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 02‐Dec‐19
Location:‐ Location M.A.S.
General Input :‐
tr= 0.20 m

Seismic Force
Direction of
L= 5.00 m tw= 0.30 m HL= 2.20 m Hw= 2.50 m
γL= 10.0 KN/m3

B= 10.00 m
Rectangular Tank Plan Rectangular Tank Elevation

γc= 24.0 KN/m3
fc= 28.0 N/mm2 Ec= 24870.1 N/mm2 ACI318‐08, Clause 8.5.1
g= 9.81 m/sec2

Importance factor I = 1.25 ACI 350.3‐06, Table 4.1.1(a)


Rc = 1.00 ACI 350.3‐06, Table 4.1.1(b)
Ri = 3.00 ACI 350.3‐06, Table 4.1.1(b)
SEISMIC ZONE 1
Z factor 0.075
Soil Profile  Stiff Soil
Soil Profile Type SD
Na For Zone 4 only 1
Nv For Zone 4 only 1
Ca 0.120
Cv 0.180
Ts =0.40Cv/Ca 0.600

1‐Calculation the Equivalent Weight for impulsive Wi & convective Wc component:

WL = 1100.0 KN  , L / HL = 2.27 ,Ww = 561.6 KN ,Wr = 262.0 KN

= 0.49 WL = 537.5 KN ACI 350.3‐06, Eq 9‐1

= 0.53 WL = 583.0 KN ACI 350.3‐06, Eq 9‐2

2‐Calculation the Height of center of gravity for impulsive hi & convective hc components:

= 0.825 m ACI 350.3‐06, Eq 9‐3 & Eq 9‐4

= 1.249 m ACI 350.3‐06, Eq 9‐5

3‐Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:

= 1361.1 KN = 1.25 m = 2.60 m


,        ,

= 1.04 m , = 148311.9 KN/m ACI 350.3‐06, R9.2.4

= 0.19 sec ACI 350.3‐06, Eq 9‐11

= 5.23 = 2.68 sec ACI 350.3‐06, Eq 9‐13,14

𝟐𝚷 𝑾𝒄
𝑻𝒄 = 𝟐𝚷 , ∴ 𝑲𝒄 = (𝟐𝚷 𝟐
∗ = 325.4 KN/m
𝝎𝒄 𝒈𝒌𝒄 𝑻𝒄

Page 1 of 2
Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.0
Project :‐ Tanque septico rio frio Designed by:‐ Armando Jose Rivero
Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 02‐Dec‐19
Location:‐ Location M.A.S.
4‐Calculation the total lateral impulsive force Pi & convective force Pc :

= 0.400 ACI 350.3‐06, Appendix B, Eq B‐1,2,3

= 0.100 ACI 350.3‐06, Appendix B, Eq B‐4,5

= 93.6 KN = 43.7 KN ACI 350.3‐06, Appendix B, Eq B‐6,7

= 89.6 KN = 72.8 KN ACI 350.3‐06, Appendix B, Eq B‐8,9

5‐Calculation the total Base Shaer V:
= 238.2 KN ACI 350.3‐06, Appendix B & Eq 4‐5
6‐Dynamic force distribution above base per Wall perpendicular to ground motion:

Pi Top = 0.5 KN/m2

Pi Bottom = 3.6 KN/m2

Pc Top = 2.3 KN/m2 ACI 350.3‐06, R5.3.1

Pc Bottom = 1.0 KN/m2

= 1.8 KN/m2

= 1.8 KN/m2 = 1.8 KN/m2
= 0.5 KN/m2 = 2.3 KN/m2 = 4.7 KN/m2

= 3.6 KN/m2 = 1.0 KN/m2 = 6.4 KN/m2


Wall Inertia Force Pw Impulsive Force Pi  ConvectiveForce Pc Total Seismic Force E per Wall
perpendicular to ground motion
Dynamic force distribution above base per Wall perpendicular to ground motion

7‐ Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength‐level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3‐06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350‐06, Clause 9.2.1 load combinations.