General Observations which need corrective actions
Severity No Area Description Action Required Rating
In all the main panels of TF
01 to TF 09 very old Testing for working condition 1 Generator Room No : 01 Mechanical Disk type EFR or replace with digital type Important and OCR used , Working Relays condition : Unknown
Need to Check the condition of
TF 03 Main panel power 2 analyzer readings innacurate CTs and Replace / Repair the Moderate power analyzer
TF 04 Main panel 630A Need to replace with new
3 Moderate MCCB Handle broken MCCB TF 04 Main incomming ACB Need to repair/ Replace ACB 4 Moderate OFF switches broken TF 01 Main incomming ACB Need to repair/ Replace ACB 5 OFF switches broken Moderate
TF 04 Main Changeover Need to replace with new
6 switch (1600A) Not working Changeover switch with same Important properly model
Ventilation level is not at
acceptable level , Effects to Need to modify existing 7 Important ventilation system the lifetime of switchgears
Air intakes for generators
are Clogged and damaged in some places, thiss will cause Need to fix 8 Moderate increase of heating inside generator rooms when operating
Capacitor bank room AC is
out of order, capacitors will Need to fix Important damage
Some of capacitor banks are
out of order, will cause to Need to fix with new Important increse the maximum capacitors demand
TF 05 outgoing to Capacitor Need to fix controlling lines
9 Generator Room No : 02 bank control lines to EFR is properly Low not in proper manner
TF 09 main panel power Need to repair / Replace with
10 analyzer readings are not Moderate new power analyzer accurate Air intakes for generators are Clogged and damaged in some places, thiss will cause Need to fix 11 Moderate increase of heating inside generator rooms when operating
Tripping of Knitting Main DB Need to check earth resistance
12 Transformer Yard when there is an earth fault values and separate commonly Important in another substation earthed frames and neutrals
No test report on Need to do transformer testing Moderate
transformers are available
Electrical safety audit report Need to renew Important
No SLD available for all
system with charted Need to prepare Moderate engineers certification Status