You are on page 1of 6

analysis

®
VOLUME ONE NUMBER ONE

HVAC

I S S U E S A N D A N S W E R S F O R T H E C O N S U L T I N G / S P E C I F Y I N G C O M M U N I T Y

In this issue...
What standards should be ASHRAE 15 – 1994: Implications
adhered to when designing
and upgrading mechanical
equipment rooms? Many of
for Mechanical Room Design
the primary answers are
found in ASHRAE Standard Introduction conditioning industry and At the time of this legisla-
15-1994: Safety Code for First issued as a safety its customers have been tion, neither ASHRAE nor
Mechanical Refrigeration. code (Standard B9) in 1930, faced with The Clean Air ARI safety standards had
While there is no substitute the same year that CFC Act Amendments of 1990, been updated to address the
for reading the document (chlorofluorocarbon) refrig- which legislated the phase- new alternative refrigerants
itself, ASHRAE 15-1994 is erants were introduced in out of CFC production at that were already appearing
written in code language, the United States, ASHRAE the end of 1995. Although in the marketplace. Thus,
which is sometimes complex Standard 15 has undergone the regulations permit the ASHRAE 15 was revised in
and difficult to understand. unusually rapid change over responsible use of these 1992 and again in 1994.
Your best strategy is to obtain the last half-decade. During refrigerants, intentional The current standard is
a copy of the standard and this same period, the air venting is strictly prohibited. now being used to formulate
read it thoroughly, then use
this newsletter as a point
of reference.
ASHRAE 15-1994 is a
guideline, but it is being
used to formulate codes for
the safe installation and
operation of mechanical
refrigeration systems in the
United States and beyond.
To find out how the stan-
dard is being adopted in
your area, invite your local
Carrier representative to
discuss ASHRAE 15-1994...
before you design or imple-
ment any mechanical room
changes.
Educate Your Customers: The high-
lights of ASHRAE 15-1994 are summa-
rized in Carrier’s SYNOPSIS newsletter,
which is written specifically for building
owners and managers. To receive copies
at no charge, call 1-800-CARRIER and
request SYNOPSIS, Vol. 1, No. 1.

1
room safety check and review bon rupture disk that’s
Mechanical Room Safety Check potential liability problems. meant to shatter at 15 psig,
Location of inlet
vents in relation Location of roof drains ? The following checklist high- allowing the charge to safely
to exhaust outlets ?
lights the many important exit the system. These disks
Purge
vents to
Rupture disc
outlet locations ? Is there a tight
items to look for (Fig. 1): are often vented through the
outside ? seal on doors ?
Are safety rupture *#@&(*)
Are exhaust outlets located roof or side of the building.
lines the right size ?
Is access to mechanical
near inlet vents? Safety relief Yet in climates with warm
room restricted ?
Is there self contained
breathing apparatus
devices on chillers are typi- days and cool nights, mois-
Are drain valves connected
to evacuation devices ? outside of the room ?
cally vented to the outside, ture often condenses in the
most often through the roof. pipes before it can evaporate
Are there any Where do the It is important to know how off. Then, along with the
pit areas in the floor drains
room ? empty to ? close this vent is to the air rust and other accumulations
intakes on the roof and to in the pipe, it ends up “sit-
insure that there is at least 20 ting” on the rupture disk.
FIGURE 1 feet between them. Over time, it may corrode
Are roof drains vulnerable the joint and result in failure
codes for the safe installation 1994 and its subsequent to collecting refrigerant? If of the seal.
and operation of mechanical addenda have been written you lose refrigerant from an Are rupture lines the right
refrigeration systems through- to help professionals mini- exhaust outlet and it vents a size and length? For conve-
out the United States and mize risk and promote safety few feet above a flat, curbed nience, safety devices some-
beyond. stewardship. roof, the refrigerant could times run into a common
The purpose of this article very well lay across the roof header. However, an
Code Compliance is to provide a basic overview and find the first exit – prob- improperly sized header can
of mechanical room safety ably down the roof drains. exacerbate problems in an
and Safety issues in relation to the Most roof drains lead directly emergency, when the dis-
ASHRAE Standard 15-1994 ASHRAE Standard. It is not to a sewer system. charge capacity of safety lines
was intentionally written in intended to be a comprehen- Where does the purge is put to the test.
code language so it could be sive review of all require- vent? A conventional purge Are chiller drain valves
adopted nearly verbatim, if ments. While this is by no (not a new, high-efficiency secured? More often than
desired, by model code asso- means a substitute for read- model) loses three to 20 not, chiller drain valves are
ciations. The primary goal ing the document itself, it pounds of refrigerant for an easy way for an inexperi-
of this standard is to mitigate will help you to know what to every pound of noncondensi- enced technician to get into
safety risks to the environ- look for when reading the ble air it removes from the trouble. Make sure the
ment, to mechanical room standard. system. Most vent directly valves are locked off.
operators and, ultimately, to into the mechanical room, Is access to the mechanical
the general public. Mechanical Room which may invite unnecessary room restricted? Most
With the introduction of problems. All purges should mechanical rooms have nei-
alternative refrigerants such Safety Check vent outside. ther a door nor anything to
as HCFCs (hydro-chlorofluo- For many building owners, Where are safety rupture restrict people from entering
rocarbons), HFCs (hydroflu- mechanical rooms are virtu- disk outlets located? On a unsupervised. (There may
orocarbons), and mixtures of ally unknown portions of the CFC-11 or HCFC-123 chiller, be a fire door, but it is typi-
refrigerant compounds property. “Out of sight, out the safety device is a thin car- cally left open.) Not only are
known as blends, new refrig- of mind” rings true in far too
erant safety classifications many cases. Most owners
have been added under the understand only that the Safety Group Examples
ASHRAE 34-1992 Standard, equipment in the mechani-
Number Designation and cal room supplies chilled
Safety Classification of water for air conditioning. High A3
Flammability Propane B3
Refrigerants. Allowable Equipment may be ten, 20,
exposure limits for the vari- 30 or even 50 years old –
ous refrigerants range from a each unit installed to comply Low A2 B2
Flammability R-142b, 152a Ammonia
low of 10 ppm (parts per mil- with the codes of the day.
lion) to a cap of 1,000 ppm. Given the new ASHRAE A1
No Flame B1
Some blends are comprised Standard and the approach- Propagation R-11, 12, 22, R-123, SO2
114, 500, 134a
of one or more flammable ing CFC and HCFC produc-
compounds, introducing yet tion phaseout, now is the Lower Toxicity Higher Toxicity
another safety concern. right time for owners, opera-
Using ASHRAE 34-1992 as a tors and engineers to con-
starting point, ASHRAE 15- duct a complete mechanical FIGURE 2

2
tion phaseout has raised the model codes. As this pro-
critical issue of what to do gresses, the updated codes
Discharge Capacity of Pressure Relief Devices with an existing CFC chiller. will ultimately be passed
Each solution – containment, down to state and municipal
C=f DL conversion or replacement – levels. For this reason, it is
brings with it new concerns. always a good idea to meet
C = minimum required discharge Yet it is important to under- with your building inspector
capacity of relief device in pounds
of air per minute (kg/s)
stand that if the type of up-front, before mechanical
refrigerant in a chiller is room changes have been
D = outside diameter of vessel in feet (m)
changed or if the chiller made. Find out what’s hap-
L = length of vessel in feet (m) itself is replaced, ASHRAE pening to codes in your area,
f = factor dependent upon type of refrigerant 15-1994 applies. Section 5.3 then decide how to proceed.
of the standard reads:
“A change in the type of ASHRAE 15-1994
refrigerant in a system shall
FIGURE 3
not be made without the Overview
mechanical rooms potential- These are some of the notification of the authority A walk through ASHRAE
ly hazardous places, they many factors to consider having jurisdiction, the user 15-1994 begins with a gener-
contain systems critical to a when evaluating the safety of and due observance of safety al look at the property in
building’s operation. your mechanical room. For requirements. The refriger- question and its mechanical
Restricting access is only potential building owners, ant being considered shall be refrigeration systems. The
common sense. The the condition of the mechan- evaluated for suitability.” type of occupancy – institu-
mechanical room door ical room and its equipment The cost of mechanical tional, public assembly, resi-
should have a tight seal to are significant considerations room upgrades – typically 11- dential, commercial, large
isolate the room in case of in the decision to purchase a 13% of the total chiller con- retail, industrial or mixed
an emergency. particular property. version/replacement project occupancy – determines
Is a self-contained breath- cost, depending on the which system application
ing apparatus (SCBA) locat- Applying ASHRAE room’s age and location – rules apply.
ed outside of the room? In should be factored into the The next step is to identify
an emergency, a properly- 15-1994 refrigerant planning cost the type of refrigerant system
used SCBA can mean the What is your compliance analysis. On the other hand, involved: Direct or Indirect.
difference between life obligation to ASHRAE 15- the addition of containment Direct Systems are those in
and death – but not if it’s 1994? If you’re a profession- devices to your existing CFC which the chiller sends
stored inside the room al engineer, a manufacturer equipment does not trigger refrigerant out into the cool-
where the contamination or an owner, you are liable application of the standard. ing coils near the occupied
is likely to occur. for ASHRAE 15-1994 simply Building Code spaces. In Indirect Systems,
Are there any pits (low by being aware of the stan- Compliance. The major U.S. the refrigerant runs only
areas) in the room? Check dard. Compliance to the building code jurisdictions through the chiller and
the condition of any pits or standard is also mandated in are currently in various chilled water in a separate
other areas below floor level. the following situations: stages of incorporating circuit produces the cooling
They may house a host of Contracts. The specifica- ASHRAE 15-1994 into their in the airside system.
unwanted chemical residues tion that equipment and ser-
such as acids, spilled refriger- vice “must be in compliance
ant, cleaning solvents, etc. with the latest ASHRAE 15”
Discharge Capacity of Rupture Member
Where do the floor drains has become standard con-
empty? Most floor drains tract language for installa- C = 0.64 p1 d
2

were constructed to handle tion submittals and service


wash-water and empty into agreements. d = 1.25(c/p1 ) 0.5
the sewer system. But if your Equipment Design. Manu-
chiller and occupied space facturers’ labels reference C = rated discharge capacity in pounds of
air per minute (kg/s) and
share the same floor, they compliance with the standard.
d = smallest of the internal diameter of the inlet
may also share drainage sys- Safety Stewardship. Pro- pipe, retaining flanges, fusible plug, and
tems. Check to see if drains fessionals who can prove that rupture member in inches (mm)
in the occupied space (i.e., they have gone to the fur- p = (rated pressure psig [kPa gage] x 1.10)
in restrooms) are connected thest extent possible to pro- + 14.7 (101.33)
to those in the mechanical mote safety will minimize
room. Imagine losing a full their legal liability.
charge and “finding” it in Mechanical Room
a restroom! Changes. The CFC produc- FIGURE 4

3
tions. When blends leak, above, even the highest-effi-
Maximum Length of Discharge Piping the highest-pressure com- ciency purges lose some
pound exits first, mixed with refrigerant. When warm gas
L = 9 P 2d 5 / 16Cr2 the next highest-pressure hits a cold pipe it will con-
compound. The lowest-pres- dense down into the pipe,
C r = rated discharge capacity as sure compound, then, is depositing refrigerant
stamped on the device by likely to be left in the vessel, against the safety rupture
the manufacturer in pounds of and in this state the mixture disk. These disks are usually
air per minute (kg/s) may be flammable. A recent a 0.03” thick layer of carbon
d = internal diameter of pipe in inches (mm) addendum to ASHRAE 34- and are not tolerant of cor-
L = length of discharge pipe in feet (m) 1992 reflects the fact that rosive conditions.
the flammability classifica- Sizing of Relief and
tion of a blend may change Rupture Devices. ASHRAE
FIGURE 5
as it leaks. The addendum 15-1994 specifies the appro-
states that a blend will be priate sizing of pressure
Indirect systems include Refrigerant classified to reflect the high- relief devices based on a
Double Indirect Open Spray est potential flammability of minimum required dis-
Systems, Indirect Closed Classifications its components. charge capacity in pounds of
Systems and Indirect Vented In its 1992 update, air per minute. The equa-
Systems (all described in ASHRAE 15 introduced a Complying with tion, shown in Fig. 3,
ASHRAE 15-1994). refinement in the way refrig- includes an “f factor,” which
The probability of refrig- erants are classified for toxi-
ASHRAE 15-1994 is identified in the standard
erant reaching the occupied city. Refrigerant com- When examining a for most refrigerants (if not,
spaces depends in large part pounds were divided into mechanical equipment consult your equipment or
upon the type of system two groups, low-toxicity and room for compliance with refrigerant manufacturer).
involved. To characterize high-toxicity, designated by ASHRAE 15-1994, here are When converting a chiller to
the degree of risk, ASHRAE the letters A and B. some of the primary issues a new refrigerant, it is criti-
15-1994 introduces the Refrigerants with allowable to consider: cal to check the size of exist-
broad categories of Low- exposure limits (AELs) of Maximum Refrigerant ing safety devices to be sure
Probability and High- more than 400 ppm are Without a Mechanical they are suitable. The new
Probability Systems. Low- classed as type A (lower toxi- Room. In Table 1 of the standard also includes rating
Probability Systems are those city) refrigerants, and those ASHRAE Standard, formulas for Discharge Capa-
in which the leakage of with AELs of less than 400 allowances for all refriger- city of Rupture Members
refrigerant from a failed ppm are type B (higher ants are listed in pounds of and Maximum Length of
component cannot enter toxicity). refrigerant per thousand Discharge Piping (Fig.’s 4, 5).
the occupied spaces. ASHRAE 15-1994 further cubic feet of occupied space. Refrigerant Sensors.
Examples of Low-Probability classifies refrigerants accord- Often misinterpreted, the According to ASHRAE 15-
Systems include Indirect ing to their degree of flam- figures in Table 1 (of 1994, all mechanical rooms
Closed Systems, Double mability: (1) no flame prop- ASHRAE 15) represent the must have a sensor capable
Indirect Systems and agation, (2) low-flammabili- maximum refrigerant levels of detecting refrigerant loss.
Indirect Open Spray Systems ty, and (3) high-flammability allowable without a separate The sensor should be posi-
where the secondary coolant (Fig. 2). Ammonia, for mechanical equipment tioned in areas where vapor
pressure exceeds refrigerant example, is considered a room. If you have more from a refrigerant leak
pressure. low-flammability refrigerant, than the allowable amount would most likely concen-
Conversely, High- while refrigerants like of refrigerant, the system trate, thus providing person-
Probability Systems are HCFC-22 and HFC-134a must be housed in a sepa- nel with a means to avoid
described in the standard as have no flame propagating rate mechanical room. catastrophic refrigerant loss
those in which leakage of properties. Purge System and Relief (Fig. 6). Sensors should
refrigerant from a failed It should be noted that Devices. The standard spec- be calibrated so that the
component will enter the the ingredients R-600a and ifies that all purge systems, allowable exposure limit for
occupied space. High- R-1270a, found in some including high-efficiency sys- the refrigerant will not be
Probability Systems include blends, are flammable and tems, and other relief exceeded.
all Direct Systems as well as would fall into Class 2 or 3 if devices must vent outside. Rather than a refrigerant
Indirect Open Spray Systems they were used as single Note: It may be economical detector, the preceding stan-
where the refrigerant pres- compounds. Although their to tap into existing rupture dard, ASHRAE 15-1992
sure always exceeds the sec- flammability is mitigated disk lines, but do consider required an oxygen depriva-
ondary coolant pressure. when they are mixed into a putting a drain valve in the tion sensor for Class A1
blend, flammability may still line or wrapping the line in refrigerants. The standard
be an issue in leak situa- heater tape. As discussed stated that the sensor should

4
supply. Large mechanical appropriately sized mechani-
Examples of Sensor Locations rooms may require an cal room as one that allows
(examples not in standard)
extended air supply in an access to all equipment,
emergency situation. including adequate space for
Relief Discharge Location. service and maintenance as
Open Drive Seals
Ventilation The discharge location of well as operation.
Entrance / Exits relief devices must be posi- Periodic Testing.
Refrigerant
tioned at least 20 feet away Ventilation systems and sen-
Storage from any ventilation open- sors must be periodically test-
Just Above floor
Next to Chillers
ings, and not less than 15 ed in accordance with the
Pits
Drains feet above ground level (to manufacturer’s recommen-
avoid spraying someone with dation and/or local jurisdic-
refrigerant). tion. This is particularly
FIGURE 6 Combustion Device (i.e., important for refrigerant
Boiler) Limitation. ASHRAE sensors that are detecting
FIGURE 6 15-1994 prohibits the loca- compounds with low allow-
tion in a mechanical room of able exposure limits. Many
be capable of detecting a dard should not exceed 330 any open-flame device using of these sensors require fre-
.5% decrease in room oxy- lbs.” This is designed to combustion air from inside quent recalibration.
gen levels (air is typically allow owners to take sepa- the room. On the other
20% oxygen, so the sensor rate, approved storage tanks hand, an open-flame device Read ASHRAE
would detect a drop to and store adequate quanti- such as a boiler may be locat-
19.5%). In this old scenario, ties of refrigerant for chiller ed in a mechanical room if 15-1994
67,000 ppm refrigerant con- servicing. This is completely combustion air is drawn Clearly, there are many
centrations could accumu- allowable under EPA, and from outside. Two accept- issues for professionals to
late before the sensor issued many owners are opting to able alternatives are to duct consider in order to achieve
a warning! Safety steward- contain their CFC chillers outside, sealed ventilated air compliance with ASHRAE
ship and refrigerant contain- and safely store service in or to install a sensor that 15-1994. Your best strategy is
ment are better served by refrigerant on-site. It should shuts the flame off in the to obtain a copy of the stan-
using a quality refrigerant be noted, however, that the presence of refrigerant gas. dard and read it thoroughly,
sensor with all refrigerants. ASHRAE recommendation is Most refrigerant sensors are perhaps using this article as a
Mechanical Ventilation to for a maximum of 330 lbs. multi-port, so they can run to point of reference.
the Outdoors. Mechanical per system. Local building several spots in the mechani- ASHRAE 15-1994 offers
rooms must be vented to the and fire codes should be ref- cal room and be pro- many good, safe solutions.
outdoors using mechanical erenced for possible exceptions. grammed to shut the boiler Not only is it a good idea to
ventilation. The formula Self-Contained Breathing down if a chiller leak is follow the new standard, it
ASHRAE provides for calcu- Apparatus. The updated detected. Yet another option may very soon be the law in
lating ventilation capacity standard requires that a self- (though not specified in your jurisdiction. To find
requirements is shown in Fig. 7. contained breathing appara- ASHRAE 15) is to isolate out how the standard is being
Access Restrictions. The tus (SCBA) be located out- the boiler or open-flame adopted in your area, invite
revised standard specifies side of the mechanical room, device with a wall or separate your local code inspector to
that access to mechanical along with a second SCBA enclosure. discuss ASHRAE-15 1994...
rooms should be restricted for back-up. It’s a good idea Room Dimensions. The before you make any changes
to authorized personnel. In to check OSHA regulations new standard defines an to your mechanical room.
addition, the room must regarding SCBA use (i.e.,
have tight-fitting doors that SCBAs cannot be worn by
open and close freely (i.e., personnel with beards, and
Mechanical Ventilation
no fire doors), and any other potential users must pass a
0.5
opening that would permit
the passage of refrigerant
pulmonary test). Another
issue is the optimum location
Q = 100 x G
must be sealed. of the SCBA gear in applica-
Refrigerant Storage. tions where the mechanical Q = the air flow in ft.3 per min.
(liters per second)
Section 11.5 of ASHRAE 15- room opens to the outdoors:
1994 reads: “The total Should the gear be housed G = the mass of refrigerant in lbs.
amount of refrigerant stored in an enclosure? Should the (kgs) in the largest system,
in a machinery room in all enclosure be locked? How any part of which is located
containers not provided with does that affect access? in the machinery room
relief valves and piped in Be sure to purchase a
accordance with the stan- SCBA with an adequate air FIGURE 7

5
Highlights: ASHRAE 15: Implications for Mechanical
Room Design in Different Types of Facilities
• ASHRAE Standard 15 was revised in
The type of occupancy of a building determines which system application
1992 and 1994 to address the phaseout rules of ASHRAE 15 apply. For buildings that fall under more than one
of CFC production and the increased classification, the Standard asks if the areas are isolated from the rest of the
use of alternative refrigerants. building by tight walls, floors, ceilings and self-closing doors. If so, each
space may be treated as a separate area. However, if the occupancies are
• The Standard is being adopted nearly not isolated, the classification with the most stringent rules applies for the
verbatim by many model code associations. entire building.

• Professional engineers, manufacturers ASHRAE 15 classifies buildings by the ability of people to respond to
and owners are liable for the Standard potential refrigerant exposure as follows:
simply by being aware of it.
Education - An educational facility, such as a college or school, may contain
• Owners and engineers can use the residential and/or public assembly spaces. Public assembly is defined as a
premise where large numbers of people congregate and cannot quickly
Standard to conduct a complete vacate. A residential structure is one that provides residents with complete
mechanical room safety check. living facilities, including permanent provisions for living, sleeping, eating,
cooking and sanitation.
• If the type of refrigerant in a system
changes, ASHRAE 15-1994 applies. Health Care - Whether it is a hospital or an extended care facility, a health
Mechanical room upgrades typically care building is likely to fall under the institutional classification in
add 11-13% to the total cost of a chiller ASHRAE 15. This is defined by ASHRAE 15 as a building that occupants
conversion/replacement project. cannot readily leave without the assistance of others.

• Which system application rules apply Hospitality - Similar to an educational facility, a hotel or motel may contain
both residential and public assembly areas.
depends on the type of building occu-
pancy, refrigerant system and refriger- Manufacturing - A manufacturing facility may have both commercial and
ant classification. industrial areas. A commercial space is one where people transact business,
receive a service or purchase products. This includes office space and work
• The Standard specifies the maximum or storage areas that do not qualify as industrial. Industrial areas are
amount of refrigerant that can be defined as not open to the public and used to manufacture, process or
stored on site with and without a store goods such as chemicals, food, ice, meat or petroleum.
mechanical room.
Office - Many office buildings will fall under the commercial space defini-
tion. However, they could also include areas of industrial or large mercan-
• All mechanical rooms must have
tile space.
a sensor capable of detecting
refrigerant loss. Retail - Most big retail stores and shopping malls are considered to be large
mercantile by the Standard. This is defined as a space where more than 100
• Mechanical rooms must ventilate to the people congregate to purchase merchandise. A small retail establishment,
outdoors using mechanical ventilation. such as a restaurant, may be considered to be a public assembly space.

• There is no substitute for reading the Apartments - Multi-family, multi-story dwellings are considered to be
standard itself. Obtain a copy and use residential premises.
this newsletter as a reference.
Warehouse - Depending on the use of the facility and the types of goods
stored there, a warehouse may fall under the commercial or industrial clas-
sifications.

In addition, equipment (other than piping) located within 20 feet of any


building opening is governed by the classification of the building.

® How are these classifications used in the Standard?

The classification of a building determines the refrigerant quantities and


types of systems allowed. Please refer to the Standard for more information.

You might also like