Professional Documents
Culture Documents
org
This is the published version of a paper presented at IECON 2014 – 40th Annual Conference of IEEE
Industrial Electronics Society,October 29 - November 1, 2014, USA.
N.B. When citing this work, cite the original published paper.
Abstract—This paper presents methods and results for modes of controller using Opal-RT’s eMEGAsim real-time
e xpe rimental performance assessment using Real-Time simulator. Power system stabilizer configuration of the
Hardware -in-the -Loop (RT-HIL) simulation of an Excitation controller together with RT-HIL simulation results for inter-
Control System (ECS) for both terminal voltage regulation and area oscillation damping of the Klein-Rogers-Kundur power
powe r oscillation damping. The ECS configured for this study is system model are discussed in Section IV. Section V discusses
Unitrol 1020 from ABB and its performance is assessed for both the experimental results obtained and in Section VI,
Automatic Voltage Regulator (Auto) and Field Current conclusions are drawn and future work is summarized.
Re gulator (Manual) modes. RT-HIL simulation is performed by
using Opal-RT’s eMEGAsim RT Simulator using a power system II. UNITROL 1020 OVERVIEW AND TEST CASE M ODELING
mode l including a synchronous generator. Finally, the Power
A. Unitrol 1020 Excitation Control System
Syste m Stabilizing feature of Unitrol 1020 is calibrated and
asse ssed. Unitrol 1020 is an automatic voltage regulator (AVR) that
provides excitation control of indirectly excited synchronous
Keywords—Excitation System, Synchronous Generator, machines and rotors [4]. The primary purpose of the device is
Automatic Voltage Regulator, Field Current Regulator, Power to maintain the generator’s terminal voltage while taking into
System Stabilizer, Real-Time Simulation, Real-Time Hardware-in- account all the operational limits associated to the generator
the-Loop Simulation, Opal-RT, Unitrol 1020, SmarTS-Lab
[5]. The regulator can also be switched over to function as field
I. INTRODUCTION current regulator (Manual Mode), reactive power or power
factor regulation. Figure 1 shows the single line diagram of a
Synchronous generators are widely used in power systems typical generator which is receiving mechanical power input
as a source of electrical energy. They are equipped with from a turbine and its field excitation is provided by an
sophisticated control systems to adapt to frequent dynamical excitation control system. Terminal voltage of the generator is
changes in the power system (e.g. load changes). One of such fed to the excitation system which compares this value to the
controls is the Excitation Control System (ECS) which set-point (reference voltage) and computes required field
provides direct current to the synchronous machine field current to bring the terminal voltage to the reference value.
winding and controls the terminal voltage [1]. In addition ECS
also provides protection functions to ensure that the capability Mechanical
limit of synchronous generators is never exceeded. Some of the Power (Pm)
Step Up
Transformer
important features of an ECS are synchronous generator’s TURBINE Pm Transmission
terminal voltage control, over and under excitation limiters, Generator Line
field current limiters and protections [2]. Vfield
thoroughly verified under both steady and dynamic conditions. Rotor Excitation Generator
Field Current System Terminal Voltage
This can be achieved by using the Real-Time Hardware-in-the
Loop (RT-HIL) [3] simulation approach. A performance Fig. 1. Interaction between synchronous generator and excitation system
assessment of ABB’s Unitrol 1020 Excitation Control System
[4] for both voltage regulation and its capability for enhancing B. Power System Test Case Modeling in MATLAB/Simulink
power system stability is carried out in this paper.
The paper is organized as follows: Section II provides Test case modeled in MATLAB/Simulink [6] for RT-HIL
information about the ABB’s Excitation System Unitrol 1020 testing of Unitrol 1020 is shown in Figure 2. The generator
and test case modeling in MATLAB/Simulink. Section III modeled is a Turbo Generator (Round Rotor) of 50 MVA and
presents the RT-HIL simulation for Automatic Voltage nominal voltage of 20 kV. The parameters settings for the
Regulation (Auto) and Field Current Regulation (Manual) synchronous generator are presented in Table 1. Steam turbine
and governor system provides mechanical power to the
This work was supported in part by Nordic Energy Research through the
STRONg2rid project and by Statnett SF, the Norwegian TSO.
M. S. Almas, and L. Vanfretti are with KTH Royal Institute of
Technology, Stockholm, Sweden. (e-mail: {msalmas, luigiv}@kth.se)
L. Vanfretti, is with Statnett SF, Research and Development, Oslo,
Norway (email: luigi.vanfretti@statnett.no)
synchronous generator and regulates its frequency by Real-Time
Simulator
increasing or decreasing the mechanical power input to the
generator. The electrical power output of the generator is fed to V and I
Amplifiers Amplified Generator
the user-controlled dynamic load through step up transformer. UAC : Generator
Voltage (ML1, ML3)
Terminal Voltage Amplified Generator
The generator receives the field voltage from Unitrol 1020. For IB: Generator current (MC2+, MC2-)
this purpose one of the Analog Output of Unitrol 1020 is Stator Current
Unitrol
configured for Pulse Width Modulation (PWM) which is scaled Rotor Field Current sent to analog input
of Unitrol as Ie External (AI1, BI1)
1020
between 0 and 100% to represent actual field voltage output of PWM scaled (0-10V) representing
actual field voltage 0.5-99%
0.5 to 99%. Generator’s terminal voltage (single phase), stator 2 3
Ethernet
current (single phase) and field current are fed to Unitrol 1020 Low level voltages and · 0-10 V input to amplifier Switch
currents from RTS are sent gives output of 0-100V
by using Analog Outputs of Opal-RT’s eMEGAsim Real-Time 1 to amplifier · 0-10 V input to current
Time Simulator
Fig. 3. Connection Diagram for interfacing Opal-RT with Unitrol 1020
Real-Time Simulator (RTS) can only provide voltages upto
±10 V and currents upto ±20 mA. These low-level signals Configuration settings for Unitrol 1020 are shown in Figure
(generator terminal voltage and stator current) are amplified 4 together with screenshots showing configuration of the
using linear amplifiers to scale voltage upto 100 V and currents analog I/Os for this study. The parameter setting for “Ie No
to 1 Ampere at rated power [8]. The field current measurement Load” is measured by executing the test case model under no-
is supplied to Unitrol 1020 using low-level ±10 Volts. For this load. The model initially executes with a fixed field voltage
purpose one of the inputs of Unitrol 1020 is configured for (configured inside the simulation model) to achieve steady
receiving an external excitation current. The complete state and then the user can send a command in real-time to
connection diagram is shown in Figure 3. switch to the field voltage measurements supplied by ABB
Excitation system.
III. RT-HIL A SSESSMENT OF VOLTAGE REGULATION
Mechanical
50 MW Turbo Generator
2-Pole, 20 kV
(A UTO) AND FIELD CURRENT REGULATION (M ANUAL) M ODES
Current
Power (Pm)
TURBINE Pm
Ifield
Transformer
1500:1
Bus 1 Bus 2 Bus 3 A. Automatic Voltage Regulation (Auto) Mode
Generator Transmission
Vfield VAC IB 20kV : 230 kV
Line
Length = 20 Km In AUTO mode, Unitrol acts as an AVR with all its
Voltage
Transformer
Step Up Transformer Voltage = 230 kV
100 MVA operational limiters active as shown in Figure 5. The model
20kV:100
was initially executed at no-load and with a fixed excitation
Generator
voltage configured in the model. Once the steady state is
Terminal Voltage Dynamic Load
Auxiliary Power Supply (UAUX) 230 kV, 50 Hz
reached, Unitrol 1020 takes over the exciter in the RTS model.
Generator
Stator Current
for powering up excitation A Series of disturbances were introduced by increasing both
UPWR,UAUX
unit and Power Electronics
Supply (UPWR) for IGBT circuit the active and reactive power consumption of the load. The
Field
Voltage
Rotor Field supplied from same source different experiments performed to assess the performance of
the Auto mode are presented in Table 2.
Current
PWM scaled from 0 to Excitation current of generator is scaled
100 % and represents between 9 to 10 V representing 0 to 150 % of
actual field voltage excitation current. This analog signal is fed to
output of 0.5 to 99% the Ie External of ABB Excitation System.
TABLE I
GENERATOR P ARAMETER S ETTINGS
Parameter Value
Nominal Power 50 MVA
Line-to-Line Voltage 20 kV
Frequency 50 Hz
Reactances (Xd, Xd’, Xd’’, Xq, Xq’, Xq’’, 2.20, 0.2, 0.20, 2.00, 0.4,
Xl) 0.20, 0.15 (pu)
Time constants (Tdo’, Tdo’’, Tqo’, Tqo’’) 4.0, 0.05, 1.5, 0.05 (s)
Inertia Cofficient H (s) 3
Pole Pairs 1
Fig. 4. Unitrol System Data and Analog I/Os configuration for RT -HIL
simulation.
Active Power Consumption of Load Reactive Power Consumption by Load
Vsetpoint 40 20
PID
TABLE 2
0 0
DISTURBANCES INCORPORATED IN THE T EST C ASE S YSTEM 0 100 200 300 400 500 0 100 200 300 400 500
Time (sec) Time (sec)
(AUTOMATIC VOLTAGE R EGULATION MODE) Load Current Voltage at Load Bus
Event Instance Disturbance Change in 1
9
(sec) Load 0.8
6
1.15
8
Current (pu)
0.6 1.1 2
1 t=0 Simulation starts (no load) 0 4
1.05
2 t = 47.1 ABB Excitation System takes over 0 0.4 3 5 3 4 6 8
3 t = 108.9 Load increase 10 MW and 10 MVAR +10MW, 0.2
1
+10MVAR 2 0.95 9
5 7
4 t = 171.3 Load increase to 20MW & 10 MVAR +10MW 0
0 100 200 300 400 500 0.9
Time (sec) 0 100 200 300 400 500
5 t = 222.0 Load increase to 30 MW & 10 MVAR +10MW Time (sec)
6 t = 272.4 Load increase to 35 MW & 10 MVAR +5MW
7 t = 319.5 Load increase to 35 MW & 15 MVAR +5MVAR Fig. 6. Load characteristics when subjected to disturbances as listed in Table
8 t = 407.1 Load increase to 37 MW & 15 MVAR +2MW 2. The number corresponds to the events as per Table-2. The voltage at load
bus decreases with an increase in load.
9 t = 482.1 Load cut off (no load condition) -37MW,
-15MVAR .
Field Voltage From ABB Exciter and Field Current Input to Exciter Mechanical Power Input to Generator vs Generator Active Power Output
3.5
3
1
Field current and Field Voltage (pu)
2.5
0.8
2
Active Power (pu)
1.5 0.6
1
0.4
0.5
Field Voltage Input from Unitrol 1020
Rotor Current Input to Unitrol as External Excitation Current 0.2
0
Mechanical Power Input by Turbine
Active Power Output by Generator
-0.5 0
0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200 250 300 350 400 450 500
Time (sec) Time (sec)
Reactive Power Output by Generator Generator Terminal Voltage
0.6 1.15
7
0.4
4 5 1.1
0.2
8 Generator Terminal Voltage
Reactive power (pu)
0
6 1.05
Voltage (pu)
-0.2
2 3 3 5 7
1
-0.4
2 6 8 9
-0.6 4
0.95
-0.8
9
-1 0.9
0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200 250 300 350 400 450 500
Time (sec) Time (sec)
Fig. 7. Generator characteristics when subjected to disturbances listed in Table 2. The Excitation is provi ded by Unitrol 1020 in Automatic Voltage Regulation
(Auto) Mode. Note that the generator terminal voltage (bottom right plot) is at 1 pu. The field voltage input provided by Unitrol 1020 (top left plot) increases with
the change in the load to keep terminal voltage of generator strictly to 1 pu. The highest positive peak in generator terminal voltage (bottom-right) correspond to
Event 9 when the complete load is cut-off (37MW, 15MVAR) and causes a momentarily increase in the terminal voltage. This is detect ed by Unitrol 1020 and it
regulates the field voltage to bring terminal voltage to the reference (1 pu). The positive peak can be reduced by narrowing the operational limits of terminal
voltage in Unitrol 1020. For this study the voltage regulation range is 80-120% of nominal terminal voltage.
The model was initially executed at no-load and with a
B. Field Current Regulation (Manual) Mode
fixed excitation voltage configured in the model. Once the
In manual mode Unitrol 1020 acts as field current regulator steady state is reached, Unitrol 1020 takes over the exciter in
as shown in Figure 8. The limiters are not active in this mode the RTS model. A series of disturbances were made by
and the generators terminal voltage is no more maintained. increasing the active power consumption of the load. The
Figure 9 shows the important parameter settings for manual variation in generator’s terminal voltage was compensated by
mode operation of Unitrol 1020. The same model used for manually increasing the field current setpoint of Unitrol 1020.
evaluating Auto Mode is used here. Only small disturbances were applied for testing the manual
mode in order to maintain the generator’s synchronism and
avoiding the real-time simulation from crashing. The
Analog input as
experiments carried out are presented in Table 3.
Ie External
Error PID TABLE 3
Ifieldsetpoint Field Voltage DISTURBANCES INCORPORATED IN THE T EST C ASE S YSTEM
Controller (PWM) (F IELD C URRENT R EGULATION MODE)
Ifieldmeasure
Event Instance Disturbance Change in
(sec) Load
Figure 8: Manual Mode of Unitrol 1020 1 t=0 Simulation starts (no load) 0
2 t = 44 ABB Excitation System 0
takes over
3 t = 193 Load increase 1 MW +1MW
4 t = 254.4 Load increase to 5MW +4MW
Voltage (pu)
Current (pu)
2 3 2 3 4
Time (sec) Time (sec)
Field Voltage from ABB Exciter and Field Current Input to Exciter Mechanical Power Input to Generator vs Generator Active Power Output
Field Current and Field Voltage (pu)
2.5 0.2
Field voltage input from Unitrol 1020
2 Field current input to Unitrol as External
Active Power (pu)
1.5
0.1
1
0.05
0.5 Mechanical Power Input by Turbine
Active Power Output by Generator
0 0
0 50 100 150 200 250 300 0 50 100 150 200 250 300
Time (sec) Time (sec)
-0.1
3 1.2
-0.15
4 3 4
-0.2 1
2
-0.25 0.8
0 50 100 150 200 250 300 0 50 100 150 200 250 300
Time (sec) Time (sec)
Fig. 11. Generator characteristics when subjected to disturbances listed in Table 3. The Excitation is provided by Unitrol 1020 in Field Current Regulation
(Manual) Mode. Note that the generator terminal voltage (bottom right plot) is no more kept constant to 1 pu. The field voltage output by Unitrol 1020 is
manually increased by changing manual set-point of the field current shown in Figure 9.
IV. POWER SYSTEM STABILIZER (PSS) CALIBRATION AND Generator
A SSESSMENT Terminal Voltage
Frequency
V1
Washout Lead-Lag
PSS Gain
Ust_max ΔVPSS
Filter Compensator
UM Calculation
Small disturbances such as changes in loads or large To ECS
Ust_min
f Tw1, Tw2
Lead Time KPSS
Constants:
compensator, and an output limiter. The general gain “K” is 900 MVA
Local
Loads
Area 1 to Area 2 Local
Loads
900 MVA
“d𝞈”. The phase-compensation system is represented by lead- Fig. 14. Single line diagram of the test case power system
lag transfer functions used to compensate the phase lag
between the excitation voltage and the electrical torque of the In order to analyze the response of the power system, a
synchronous machine. The output limiter ensures to bound the large disturbance in the form of three phase to ground fault (8
amount of control action of a PSS during a major system cycles i.e. 160 msec) at t = 20 sec is introduced in the middle
disturbance and thus avoids the PSS to adversely affect the of one of the two 220 km transmission line connecting Area 1
generator’s synchronism. with Area 2. The system response to this perturbation in
Washout Vreference absence of PSS is shown in Figure 15. This results in an un-
PSS Gain Filter Limiter Vmeasured Excitation VField damped oscillation of 0.64 Hz which is observable in the tie-
dw
K
1+T1s
1+T2s ΔVPSS
Control
System line power transfer between Area 1 and Area 2 as shown in
Low Pass Phase Compensation
Figure 13. This is an inter-area mode involving both the
Filter Lead-Lag Filter machines in Area 1 oscillate against the machines in Area 2.
Fig. 12. Model of a conventional Δω PSS [12]. The PSS capability of Unitrol 1020 is exploited to damp this
inter-area mode of 0.64 Hz.
B. PSS Feature of Unitrol 1020 Excitation System
The PSS parameter settings are configured according to the
PSS feature available in Unitrol 1020 ECS is represented recommendations in the IEEE Standard 421.5-2005 [5] and
by the IEEE Std. 421.5-2005 PSS 2A/2B model [5] and its are presented in Table-4. The gain of PSS is deliberately kept
simplified representation is shown in Figure 13. The PSS2A low along with low positive and negative limits of PSS output
type has dual structures that use two signals of angular to avoid major changes in the field voltage due to large
velocity “ω” and power “P” as compared to single input of disturbances which could lead to generator’s loss of
angular velocity ω in PSS1A model shown in Figure 12. synchronism and to minimize the influence of noise.
Case 1: No PSS Case 1: No PSS Case 1: No PSS
Rotor Angle Deviation of All Generators (d-theta) Active Power Transfer Between Area 1 and Area 2 Rotor Speed of All Generators (wm)
20 800 1.06
700
1.04
15
Machine 1 600
Machine 2 1.02
Machine 3 500
10
5 300 0.98
200 Machine 1
0.96
0 Machine 2
100 Machine 3
0.94
Machine 4
0 Active Power Transfer
-5 from Area 1 and Area 2
0.92
-100
Fig. 15. Response of Test Model when three phase to ground fault (8 cycles) is introduced at the middle of one of the 220 kV transmission lines at t=20 sec. Rotor
angle deviation of machines with reference to rotor angle deviation of Machine 4 (left), power transfer from Area 1 to Area 2 (middle) and rotor speed of all the
generators (right) are shown. Inter-area oscillation of 0.64 Hz is observable in the tie-line power (middle). The PSS capability of Unitrol 1020 is disabled in this
case.
Case 2: ABB Unitrol 1020 PSS at Generator 1 Case 2: ABB Unitrol 1020 PSS at Generator 1 Case 2: ABB Unitrol 1020 PSS at Generator 1
Rotor Angle Deviation of All Generators (d-theta) Active Power Tranfer Between Area 1 and Area 2 Rotor Speed all Generators (wm)
10 1000 1.01
8
800 Machine 1
Machine 2
6 1.005
Machine 3
Active Power (MW)
Rotor Angle (rad)
600
-4 -200 0.99
0 10 20 30 40 50 60 70 0 20 40 60 80 100 0 20 40 60 80
Time (sec) Time (sec) Time (sec)
Fig. 16. Response of Test Case model when three phase to ground fault (8 cycles) is introduced at the middle of one of the 220 kV tran smission lines at t=20 sec
when Generator 1 is equipped with PSS and AVR through Unitrol 1020 ECS. Inter-area oscillation of 0.64 Hz is adequately damped. The response of PSS can be
enhanced by fine tuning of PSS lead-lag compensation parameters and by increasing the PSS gain.
Case 2: ABB Unitrol 1020 PSS at Generator 1
Field Voltage Input from ABB ECS and Field Current Input to ABB ECS
Figure 16 shows the response of the PSS integrated within 4