You are on page 1of 5

No.

Site Name Site ID POI Name NSA RTP Class Site

1 CITRARAYA TNG209 WATER WORLD CITRA Banten Kab Tangera Platinum


Jumlah Jumlah Backuptime at 49 V Backuptime Estimasi EAS
Rectifier Name Battery Name
Modul Battery (Minutes) (Minutes) Validation
Eltek FP2000 5 Shoto 6FMX100B 3 25 129 Valid
Keterangan

Battery Backup
1 Load
No. Type of Band DCDU ID
1 U2100 1
2 L2300, GL900 2
3 GL1800, 6 Sec L1800 3
Total Load

2 Battery Capacity
6 bank 100 Ah = 300
Battery condition = 80%
Ah = 240

3 LVD & DoD (Deep of Discharge)


Starting Voltage when discharge (OCV) = 50.4
Voltage refference = 49
LVBD = 43.2
DoD Start = 0%
DoD End = 100%

4 Backuptime Estimation Until End Voltage (43,2 V)


Backuptime Estimation = 2.14
= 129

5 Estimation Backuptime at Voltage Refference


DoD at refference voltage (estimation) = 19.44%
Backuptime at Voltage refference (estimation)= (DoD at refference voltage x Ah
= 0.42
= 25

Notes :
1 Kolom untuk diisi
2 Point 4 Estimasi Backuptime (Standard BUT > 4 Jam)
3 Point 5 Lama Backuptime sampai dengan tegangan Referensi
Load (A)

112

Ah

Ah

V
V
V

Hours
Minutes

128.5714
(DoD at refference voltage x Ah) / Total Load
Hours
Minutes