8MW/1500Vdc Outdoor Inverter


14 Jan 2020

WWW.TMEIC.COM

© Copyright TMEIC All rights reserved Confidential


SCOPE

xxxx Page 3
< Confidential to TMEIC INDIA> xxxxx
Supply Scope Matrix
S.No Item TMEIC Purchaser

1 4.8MW Inverter U-PCS with skid x


2 9.6MVA Inverter Transformer x
3 ICOG Panel x
4 DC/ AC Power, Control Cables and cabling accessories, x
cable tray
5 Earthing, Earth pits, LA’s x
6 ACDB cum UPS-DB x
7 UPS x
9 Transformer/ Soak pit Piping works x
10 SCADA x
11 Peripheral Lighting x

12 Civil Design and related works x


13 Statutory approvals, Fire alarm, Safety equipment, x
Relay coordination & BOP

xxxx Page 4
< Confidential to TMEIC INDIA> xxxxx
E & C Scope Matrix
S.No Item TMEIC Purchaser

1 4.8MW Inverter U-PCS with skid C E


2 9.6MVA Inverter Transformer - E&C
3 ICOG Panel - E&C
4 DC/ AC Power, Control Cables and cabling - E&C
accessories, cable tray
5 Earthing, Earth pits, LA’s - E&C
6 ACDB cum UPS-DB - E&C
7 UPS - E&C
8 Inverter Transformer/ Soak pit Piping works - E&C
9 BOP - E&C
NOTE: E : Erection C : Commissioning

xxxx Page 5
< Confidential to TMEIC INDIA> xxxxx
Brief Technical specification
• Modular Inverter Design
• Suitable for Marine environments (except heavy salt
damage area)
• Cooling system - Heat pipe technology
• Compact and light weight
INVERTER
• High Reliability, High Efficiency (~99%)
6 x 800kW UPCS
• ACB less, LCD less (Built-in Wi-fi), 3-level
• Each modular inverters consist of same hardware
regardless of inverter capacity
• Individual DC input & common AC output
• Individual MPPT for each inverter module

xxxx Page 6
< Confidential to TMEIC INDIA> xxxxx
Brief Technical specification

• 3 Winding (2 LV + 1HV) Inverter Duty Transformer


• Cooling : ONAN, Temperature rise 50/ 55 deg C
• No Load Loss : 10 kW with IS Tolerance
• Load Loss : 100 kW with IS Tolerance
INVERTER • Percentage Impedance : 7.15% with IS Tolerance
TRANSFORMER
• Vector Group Dy11y11
9.6 MVA
• Off Circuit Tap Changer +/- 5% range in 2.5% step
3 WINDING
• LV side Voltage suitable for offered Inverter
• HV Side Voltage either 22kV or 33kV as per site
• LV Side Cable Box 12R/Phase/LV x 1 C x 400sq.mm
• HV Side Cable Box 1R x 3C x 185sq.mm

xxxx Page 7
< Confidential to TMEIC INDIA> xxxxx
Brief Technical specification

ACDB
• 20kVA Auxiliary Transformer, 415V, 3 Phase, 50Hz
secondary winding for station loads
• Integrated inside Outdoor Metal enclosed Panel
ACDB/ UPS
• AC Distribution with MCB (2P/3P)

UPS
• 5kVA, 1 Phase Input 1 Phase Output, 230V, 50Hz
• Integrated inside Outdoor Metal enclosed Panel
• MF VRLA Battery for 1 Hour UPS Backup
• AC Distribution with MCB (2P)

xxxx Page 8
< Confidential to TMEIC INDIA> xxxxx
Brief Technical specification

• Rating 22kV or 33kV, 630A, 20kA/ 1Sec. Motorised


Vacuum circuit Breaker
• Outdoor Installation, IP 54
• Non Extensible, Metal Enclosed Switchgear
ICOG PANEL • Nominal frequency : 50 Hz
• External Power connection from Bottom side of panel
- Incoming : 1R x 3C x 185sq.mm Alu, Ar
- Outgoing : 1R x 3C x 185sq.mm, Alu, Ar
• Auxiliary Powered protection relay (50/51) with RS 485
communication

xxxx Page 9
< Confidential to TMEIC INDIA> xxxxx
9.6MW PROPOSED LAYOUT

Tentative Equipment Dimension [Length x Depth x Height in mm]:


A. Inverter (6 x 840kW) : 7050 x 1200 x 2150
B. Transformer : 7400 x 4300 x 4200
C. ICOG : 1200 x 2500 x 2400
D. ACDB/UPS : 600 x 1400 x 1800

INVERTERS, ICOG PANEL & ACDB/UPS WILL BE ON CIVIL FOUNDATION

xxxx Page 10
< Confidential to TMEIC INDIA> xxxxx
Thank you

xxxx Page 11