GETTING RESULTS GUIDE


ENTERPRISE ONLINE CONFIGURATION UTILITY

PUBLICATION XMOCU-GR001E-EN-E–November 2008


Supersedes Publication XMOCU-GR001D-EN-D
EOLConfig GRG.book Page ii Wednesday, January 14, 2009 8:00 AM

Contact Rockwell Customer Support Telephone — 1.440.646.3434


Online Support — http://www.rockwellautomation.com/support/

Copyright Notice © 2008 Rockwell Automation Technologies, Inc. All rights reserved. Printed in USA.
This document and any accompanying Rockwell Software products are copyrighted by Rockwell Automation
Technologies, Inc. Any reproduction and/or distribution without prior written consent from Rockwell Automation
Technologies, Inc. is strictly prohibited. Please refer to the license agreement for details.
Trademark Notices Allen-Bradley, Datapac, Emonitor, Emonitor Odyssey, Enlab, Enlube, Enpac, Enshare, Entek, Entrx, Enwatch,
eProcedure, FactoryTalk, MotorMonitor, PlantLink, Rockwell Automation, Rockwell Software, RSLinx, RSView, the
Rockwell Software logo, and XM are registered trademarks of Rockwell Automation, Inc.

The following logos and products are trademarks of Rockwell Automation, Inc.:
RSBizWare, the RSBizWare logo, RSMACC, FactoryTalk AssetCentre, RSLogix, RSView, RSView32, FactoryTalk
Activation, Intelligent Advisory, RSLinx Classic, RSLinx Enterprise, RSNetWorx, RSNetWorx for DeviceNet,
RSNetWorx for EtherNet, and RSNetWorx for EtherNet/IP.

Other Trademarks ActiveX, Microsoft, Microsoft Access, SQL Server, Windows, Windows NT, Windows 2000, Windows Server 2003,
and Windows XP are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or
other countries.
Adobe, Acrobat, and Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the
United States and/or other countries.
ControlNet is a registered trademark of ControlNet International.
DeviceNet is a trademark of the Open DeviceNet Vendor Association, Inc. (ODVA).
Ethernet is a registered trademark of Digital Equipment Corporation, Intel, and Xerox Corporation.
OLE for Process Control (OPC) is a registered trademark of the OPC Foundation.
Oracle, SQL*Net, and SQL*Plus are registered trademarks of Oracle Corporation.
All other trademarks are the property of their respective holders and are hereby acknowledged.

Warranty This product is warranted in accordance with the product license. The product’s performance may be affected by system
configuration, the application being performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in this document do not cover all the
details or variations in the equipment, procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This product’s implementation may vary among
users.
This document is current as of the time of release of the product; however, the accompanying software may have
changed since the release. Rockwell Automation, Inc. reserves the right to change any information contained in this
document or the software at anytime without prior notice. It is your responsibility to obtain the most current information
available from Rockwell when installing or using this product.
Emonitor Version 3.40

Enterprise Online Configuration Utility version 3.40

ii
EOLConfig GRG.book Page iii Wednesday, January 14, 2009 8:00 AM

Contents

1 • Introduction 1
About the documentation set (or, Where do I start?) . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Online help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
About this book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
About the Enterprise Online Configuration Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
How the Online Configuration Utility works with XM modules. . . . . . . . . . . . . . 2
Statement of Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Phone Support Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Effective Support Dates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Exemptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2 • Installing and starting Enterprise Online Configuration Utility 7


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Hardware requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Software requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
FactoryTalk Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installing the Online Configuration Utility software . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Starting the Online Configuration Utility software . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3 • Getting started with Enterprise Online Configuration Utility 11


Welcome to the Enterprise Online Configuration Utility . . . . . . . . . . . . . . . . . . . . . . 11
Initial steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configure networks online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configure networks offline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
View data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Main windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Tree View window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Graph View window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Information Message window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Plot windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Current Value window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

iii
EOLConfig GRG.book Page iv Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Exploring the Online Configuration Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17


Title bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Menu bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Right-click shortcut menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Network tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Quick Start steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Quick Start initial steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Quick Start steps to configure your network online . . . . . . . . . . . . . . . . . . . . . . 24
Quick Start steps to configure your network offline . . . . . . . . . . . . . . . . . . . . . . 29
Quick Start steps for viewing data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Specifying default settings for the Online Configuration Utility . . . . . . . . . . . . . . . . 34

Index 35

iv
EOLConfig GRG.book Page 1 Wednesday, January 14, 2009 8:00 AM

1 Introduction
The Enterprise Online Configuration Utility is an application program that allows you to
configure and view live data from XM® modules. The Allen-Bradley® XM Series from
Rockwell Automation, Inc. is a family of DIN rail-mounted condition monitoring and
protection modules that operate both in stand-alone applications or integrate with
programmable logic controllers (PLCs) and control system networks. You install and
operate the Online Configuration Utility as part of an Emonitor® system that includes XM
Online Data.
The Online Configuration Utility is always started from the XM Online Data program.
The Online Configuration Utility runs in its own window. The Online Configuration
Utility not a driver or a service, and should not be left running after you have finished
configuring your XM modules and networks.

Exiting the Online Configuration Utility when it is not needed conserves system resources and
reduces network traffic.

About the documentation set (or, Where do I start?)

This document comes with

XM Module User’s Guides XM hardware modules


Enterprise Online Configuration Utility Getting Results Enterprise Online Configuration Utility
Guide
Doc ID XMOCU-GR001E-EN-E

You use the Enterprise Online Configuration Utility to configure XM modules. In addition
to the manuals, the Online Configuration Utility provides online help.
The documents are intended to be used in the following order:
1. Follow the instructions in the individual XM Module User Guides to install the XM
modules on a DeviceNet™ network.
2. Follow the instructions in the Enterprise Online Configuration Utility Getting Results
Guide to configure the XM modules.
This book is intended to give a general overview of the Online Configuration Utility
software. Please refer to the online help for more detailed information.

1
EOLConfig GRG.book Page 2 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Online help
Online help is available from the Help menu or by pressing F1. To view the help for the
Online Configuration Utility, open the application, and then click the Help menu.

About this book


This book provides you with information on how to get started using the Online
Configuration Utility to configure XM modules. It is not intended to be a comprehensive
user’s guide. For complete information on all Online Configuration Utility features, tasks,
and interface elements, refer to the online help.
This book is written for people who install, configure, and monitor XM modules. We
assume you are familiar with:
„ Microsoft® Windows® operating systems
„ RSLinx® communication software
„ DeviceNet and Ethernet® networks
Please use the feedback form, which you will find packaged with your software, to report
errors and/or let us know what information you would like to see added in future editions
of this document.

About the Enterprise Online Configuration Utility


The Online Configuration Utility communicates with XM modules over Ethernet and
DeviceNet. This allows you to configure XM modules from your computer, regardless of
the location of the XM modules.

How the Online Configuration Utility works with XM modules


The following diagram illustrates how the Online Configuration Utility communicates
with XM modules. The computer and the network gateway modules communicate over an
Ethernet network. Each network gateway communicates with other XM modules over a
separate DeviceNet network, as shown below.

2
EOLConfig GRG.book Page 3 Wednesday, January 14, 2009 8:00 AM

• • • • •
1 • INTRODUCTION

In general, the Online Configuration Utility communicates with XM modules through an Ethernet
network and an Ethernet-DeviceNet gateway such as the XM-500 module or 1788-EN2DN
device. However, you can also connect directly to a DeviceNet network, using the Enterprise
Online Configuration Utility. See the online help for more information.

Typically, in an Emonitor Online System, the Online Configuration Utility is installed and
run on an Unload Station computer in an Emonitor Online system. The Enterprise Online
Configuration Utility can only be started from the XM Online Data program. The XM
Online Data program must be installed with the Enterprise Online Configuration Utility.
Both are installed with Emonitor.
The Online Configuration Utility stores the network and XM module configuration in a
network configuration file. Other programs, such as XM Online Data also use this
network configuration file to get, display, and export data from the XM modules.
The Online Configuration Utility can work in either online or offline modes.
„ When you are working online, (the computer hosting the Online Configuration
Utility is connected to the network) you can browse networks. You can communicate
with XM modules to upload and download configuration parameters, and to view
data.

3
EOLConfig GRG.book Page 4 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

„ When you are working offline, you can edit the network and XM module
configuration parameters and save them to the network configuration file. You can
download the configuration parameters later when online.

Statement of Technical Support

Phone Support Programs


COMPLIMENTARY SUPPORT
Rockwell Automation provides a variety of web-based technical information and self-
service support tools at http://support.rockwellautomation.com. These include product
manuals, technical knowledgebase, MySupport and software reset codes (limited to one
per registered serial number each year). Knowledgebase content includes: FAQs, tech
notes, application notes, technical tips, sample code, documentation, detailed explanations
of error codes and links to hotfixes/service packs. MySupport, a personalized subscription
service, sends email notifications when new product update(s) or tech note(s) of interest
are published online.
New Customer Initial Support. New customers of Rockwell Automation, or existing
customers buying a product for the first time in a new product family, as defined by the
support program, are eligible for the DirectConnect (8a-5p) level of support
(TechConnect); or Bronze Level Support (E-Safe) at no charge for a period of one year.
Contact your local distributor or Rockwell Automation sales office to validate eligibility.
Rockwell Automation offers the following phone support programs:
„ TechConnect Support
„ Emergency Reinstatement Software Support
„ E-Safe Support
„ TeamSupport
„ Team Support360

PHONE SUPPORT PROGRAM STANDARD FEATURES


Technical Phone Support. Real-time assistance for installing, configuring, troubleshooting
and diagnosing problems; basic programming instruction and best-practice
recommendations. Standard phone support hours are 8:00 am to 5:00 pm Monday-Friday
(local time) for TechConnect, and 8:00 am to 7:00 pm EST Monday-Friday for E-Safe1.
Extended coverage (24x7x365) is available for an additional charge.

1. Hours may vary for some products. Phone support is not available on selected holidays.

4
EOLConfig GRG.book Page 5 Wednesday, January 14, 2009 8:00 AM

• • • • •
1 • INTRODUCTION

Online Support Requests. Rockwell Automation support specialists answer technical


questions submitted online at http://support.rockwellautomation.com/supportrequests/.
Product Updates/Replacement Media. Product enhancements or updates and service
packs are available for download 24x7x365. Media is available for shipping upon request
(limited to one media set per serial number). Product upgrades are sold separately.
For additional information on the specific features of our phone support programs, visit
http://www.rockwellautomation.com/services/phone/.

Effective Support Dates


The contract term for a phone support program is typically one year, but the length may
vary by program type or specially negotiated terms. Support programs are upgradeable
and renewable. In the event that a support program is not renewed prior to program
expiration, prices may be subject to reinstatement fees. Support programs are available for
sale from your local authorized distributor or local Rockwell Automation sales office.

Conditions
Products Covered. TechConnect Support programs are available for most Rockwell
Software products, selected Reliance Electric Drive Control products, and Allen-Bradley
Automation Control, Industrial Motion Control, and Drives Control products, as defined
by product families selected or unless otherwise specified in the program.
E-Safe Support is available for ICM Hardware (excluding XM Modules), ICM Software
(Emonitor-Factory, Workstation, or Enterprise and Odyssey-Basic, Classic, or Deluxe),
and En-Watch.
Emergency Reinstatement Software Support is available for RSLogix 5/500/5000,
RSView, PanelBuilder, RSLinx, and RSNetworx packages.
TeamSupport and TeamSupport360 programs are available for Rockwell Software,
Reliance Electric, Allen-Bradley, and selected third party products.
Site Coordinator. A customer site coordinator must be identified to manage support
program(s). This person will receive shipment of all information and product related to
the program and is responsible for managing and maintaining the support program.
Terms of Support. At the end of any support program term, Rockwell Automation may
withdraw support as defined in the agreement or delete any obsolete or discontinued
products at any time at the end of any support term. Support does not extend to the
following products:
„ Product that has been modified or altered.

5
EOLConfig GRG.book Page 6 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

„ Product that has been used on computer equipment other than equipment specified as
being supported in Rockwell Automation published product descriptions.
„ Product that, in the judgment of Rockwell Automation, has failed due to improper
installation, operation, alteration, modification or misuse.
„ Product which has not been updated with the most recent correction, modification or
enhancement made available by Rockwell Automation.
„ Product that, in the judgment of Rockwell Automation, is being used in violation of
the license agreement.
Cancellation Policy: Cancellation of a support service is subject to a 25% charge, together
with reimbursement for direct costs. Support services cannot be canceled if updates
cannot be returned unopened, were downloaded electronically or if the remaining term of
service is less than two months.

Exemptions
New Purchase Warranty. The product warranty provisions for the initial purchase of
hardware, firmware and/or software products are described in the applicable End-Users
License Agreement and the General Terms and Conditions of Sale, Publication 6500.
Rockwell's technical support programs may include complimentary support for certain
product purchases if the product meets the criteria set forth above. For basic
troubleshooting assistance of product failures that occur within the first 24 hours of
operation, call your local distributor or New Product Satisfaction Return 440-646-3223.
Onsite Support. Phone support programs do not include any onsite services unless
otherwise stated. OnSite support services are available at applicable rates and terms.
Technical Application Services. Phone support programs do not include technical
consulting for programming applications such as code design, development or debugging.
This service is available at applicable rates and terms.
Taxes. Rockwell Automation is not responsible for any and all taxes and duties associated
with the support provided under a support program, excluding taxes based upon net
income. Applicable taxes and duties are added at time of invoicing.

TERMS AND CONDITIONS


Services provided under any technical support programs are subject solely to the General
Terms and Conditions of Sale, Publication 6500.
This statement of technical support is strictly provided as a reference for Rockwell
customers. Support Programs may vary by Geographical Region.

6
EOLConfig GRG.book Page 7 Wednesday, January 14, 2009 8:00 AM

2 Installing and starting Enterprise Online


Configuration Utility
Introduction
This chapter explains how to install and start the Online Configuration Utility software.
Typically, the Online Configuration Utility is installed with the XM Online Data program
on an Unload Station computer (as part of an Emonitor Online system). The Online
Configuration Utility can be accessed only from the computer on which it is installed.
After installing the software, we recommend that you read the release notes. The release
notes may contain more up-to-date information than was available when this document
was published. To view the release notes, start the Online Configuration Utility software
(see Starting the Online Configuration Utility software on page 8), then select Help >
Release Notes.

System requirements
To use Online Configuration Utility software effectively, your personal computer must
meet the following hardware and software requirements.

Hardware requirements
The hardware requirements are the same as for Emonitor.

Software requirements
The software requirements are the same as for Emonitor.
„ In addition, RSLinx® Classic Lite or RSLinx Classic version 2.54.00 or later must be
installed on the same computer on which the Online Configuration Utility software
will be installed. One copy of RSLinx Classic Lite software is included with the
Emonitor software.

FactoryTalk Activation
The Online Configuration Utility uses a new, streamlined process to activate your
software using license files. As part of the Online Configuration Utility installation
process, you must install the FactoryTalk Activation software. Normally, the software is
installed when you install Emonitor. For more information on FactoryTalk Activation,
refer to the FactoryTalk Activation file. To display the file, follow these steps:
1. Insert the Emonitor Install DVD into your computer.

7
EOLConfig GRG.book Page 8 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY RESULTS GUIDE

2. After the Autorun screen appears, click Read Documentation. The list of available
documentation appears in your default HTML browser.
3. Click FactoryTalk Activation, located under Release Notes.

Installing the Online Configuration Utility software


The Online Configuration Utility is automatically installed when you install Emonitor.

Starting the Online Configuration Utility software


The Online Configuration Utility can only be started from the XM Online Data program.
It cannot be run as a stand-alone application.
To start the Online Configuration Utility:
1. Start the Emonitor Online Data Management Console (Start > Programs > Rockwell
Software > Emonitor > Online > Online Data Management Console.).
2. Click Log In. You must log in with an Emonitor Administrator-level username and
password (set in Emonitor) and click OK.
3. In the Online Data Management Console window, select an XM Online Data data
source. Refer to the XM Online Data Getting Results Guide and the online help for
XM Online Data and the Online Data Management Console for the steps to create a
data source for XM Online Data.
4. Click Edit. This starts the XM Online Data program.
5. In the XM Online Data main window, click the EOL Configuration button.

Troubleshooting
If Online Configuration Utility does not start up or run properly or if you encounter
problems with activation, refer to the following sections as a troubleshooting aid.

Installation
Ask yourself the following questions if you encounter problems in an installation.

DOES MY COMPUTER HAVE ENOUGH MEMORY?

Running the Online Configuration Utility software requires a minimum of 512 MB of


RAM.

8
EOLConfig GRG.book Page 9 Wednesday, January 14, 2009 8:00 AM

• • • • •
2 • INSTALLING AND STARTING ENTERPRISE ONLINE CONFIGURATION UTILITY

IS THE CORRECT VERSION OF RSLINX OR RSLINX LITE INSTALLED?

The Online Configuration Utility software requires RSLinx Classic or RSLinx Classic
Lite version 2.54.00 or later. Normally RSLinx Classic Lite is installed as a part of the
installation process for Emonitor.

IS ONLINE CONFIGURATION UTILITY SOFTWARE ACTIVATED?

If, upon attempting to run Online Configuration Utility, you see a message indicating that
activation for Online Configuration Utility is missing, you must get an activation for the
software. See FactoryTalk Activation on page 7.

9
EOLConfig GRG.book Page 10 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY RESULTS GUIDE

10
EOLConfig GRG.book Page 11 Wednesday, January 14, 2009 8:00 AM

3 Getting started with Enterprise Online


Configuration Utility
Welcome to the Enterprise Online Configuration Utility
The Enterprise Online Configuration Utility is a program that allows you to configure XM
modules and the networks that connect them to your computer. You can also view data
from XM modules using the Online Configuration Utility.
Before you can use the Online Configuration Utility with your XM modules, there are a
set of initial steps that you must use to prepare your system.

Initial steps
There are several steps that you must follow before using the Online Configuration Utility
to communicate with your XM modules. These include installing and commissioning
your XM modules, registering the electronic data sheets (EDS files) for the XM modules,
and configuring the Ethernet driver with RSLinx. See Quick Start initial steps on page 22.

Configure networks online


You use the Online Configuration Utility to configure your XM system when online.

Working “online”
When you are working online, the computer hosting the Online Configuration Utility is connected
to the network. You can browse networks and upload configuration parameters from XM
modules. You can then edit them as needed, and then download them back to the XM module. In
addition, you can also monitor data from the XM module, including the configuration parameters.

The system includes several components. The computer and the network gateway
modules communicate over an Ethernet network. Each network gateway communicates
with other XM modules over a separate DeviceNet network, as shown below.

11
EOLConfig GRG.book Page 12 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

In general, the Online Configuration Utility communicates with XM modules through an Ethernet
network and an Ethernet-DeviceNet gateway such as the XM-500 module or the 1788-EN2DN
device. However, you can also connect directly to a DeviceNet network, using the Enterprise
Online Configuration Utility. See the online help for more information.

The Online Configuration Utility stores the network and XM module configuration in a
network configuration file. Other programs, such as XM Online Data also use this
network configuration file to get, display, and export data from the XM modules. See
Quick Start steps to configure your network online on page 24.

You can also use a programmable logic controller (PLC) as the Ethernet-DeviceNet gateway, in
the place of a network gateway module. However, you cannot use the Online Configuration
Utility to configure or communicate with a PLC. Contact Technical Support for more information.

12
EOLConfig GRG.book Page 13 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

Configure networks offline


You can also use the Online Configuration Utility to configure your XM system when
online.

Working “offline”
When you are working offline, you can edit the network and XM module configuration parameters
and save them to the network configuration file. You can download the parameters to the network
later when you go online. The XM module configuration parameters that appear when working
offline are either:
the parameters you last saved to the configuration file, or
the factory defaults from the electronic data sheet.

When you configure your system offline, you create a network configuration file, just as
you do when you configure your system online. The difference is that when you work
offline, you must describe your system in the Online Configuration Utility, instead of
having the Online Configuration Utility scan for DeviceNet networks and XM modules.
See Quick Start steps to configure your network offline on page 29.

View data
The Online Configuration Utility displays data from XM modules in both interactive Plot
windows and numeric data tables. The available plot types depend on the type of XM
module, and can include trend, spectrum, spectrum map, and time waveform plots. You
can only view data when online. See Quick Start steps for viewing data on page 34.

13
EOLConfig GRG.book Page 14 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Main windows
The Online Configuration Utility software is comprised of three main windows and two
additional types of window:
Tree View window
This window shows all the networks and XM modules
for the current network configuration file. The Graph
View window replaces the Tree View window.

Tree View and Graph View tabs Information Message window


These tabs allow you to switch This window shows text messages
between the Tree View window and that describe events as you
the Graph View window perform various tasks

Tree View window


The Tree View window shows you a picture of your network, including both the Ethernet
network side and the DeviceNet network side. There are typically 4 levels in the tree. The
following table describes the levels, and gives typical names for items at each level. Note
that the levels depend on the way RSLinx is configured to access the network.

14
EOLConfig GRG.book Page 15 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

Level Description

1 Workstation level. This is the highest level, and represents your computer.
XM Ethernet Network
2 Driver level. This represents the driver configured in RSLinx that allows your
computer to communicate with XM modules.
RSLinx Driver AB_ETH-1 Station Number 63
3 Gateway level. This represents the network gateway module that communicates
between the Ethernet network and the DeviceNet Network.
Ethernet Station Number: 000 - XM-500 EtherNet/IP Gateway
4 Device level. This represents the individual devices (XM modules) on the DeviceNet
network. The device name is preceded by the node address.
01, XM-120 BRG 1

The network gateway appears twice because it acts as both an Ethernet device and a DeviceNet
device. You cannot configure the Ethernet side of the network gateway in the Online
Configuration Utility. You can, however, configure the DeviceNet side of the network gateway.

The following table describes the icons that appear in the Tree View window.

Icon Description

Indicates a network gateway module, either the Ethernet side or the DeviceNet side of
the module

Indicates an XM measurement or relay module

Indicates an active XM measurement or relay module in communication with the


Online Configuration Utility

Indicates an active XM measurement or relay module that is in Program mode

Indicates an XM measurement or relay module that appears in the Online


Configuration Utility network configuration, but is not in communication with the
Online Configuration Utility

Other DeviceNet devices may appear in the Tree View. The text for these devices is colored
gray. You cannot communicate with non-XM devices.

Click the Tree View window, then press F1 to display the help topic for the window.

15
EOLConfig GRG.book Page 16 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Graph View window


The Graph View window shows you a picture of the selected DeviceNet network.

Each network gateway (such as an XM-500 module or 1799-EN2DN device) defines a separate
DeviceNet network. For networks with multiple network gateway modules, select the desired
DeviceNet network in the Tree View tab before clicking the Graph View tab.

Click the Graph View window, then press F1 to display the help topic for the window.

Information Message window


The Information Message window displays text messages that describe events as you
perform various tasks with the Online Configuration Utility. The following table shows
the icons that may appear to the right of each message:

Icon Description

Error message

Warning message

Informational message

16
EOLConfig GRG.book Page 17 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

For more on the Information Message window, click the Information Message window in
the Online Configuration Utility, then press F1 to display the help topic.

Plot windows
A plot window contains one or more graphical displays of data from an XM measurement
module. Plot formats include spectrum, time waveform, and spectrum map plots. For
more information on plots, see Quick Start steps for viewing data on page 34. You can
also press F1 when a Plot window is active to display the help topic for that plot.

Current Value window


The Current Value window shows the current value data from an XM module, including
single-value data, and alarm and relay status. For XM measurement modules (including
the XM-120, XM-121, and XM-320) the Current Value window also shows a trend plot of
the overall or position data. For more information on plots, see Quick Start steps for
viewing data on page 34. You can also click any part of the Current Value window, then
press F1 to display the help topic for that part of the Current Value window.

Exploring the Online Configuration Utility


The following sections discuss navigation through the Online Configuration Utility
software. The Online Configuration Utility software includes the following navigation
aids:
„ Online Configuration Utility window with a title bar, menu bar, and toolbar
„ Right-click shortcut menus
„ Network tree

Title bar
The title bar shows the Online Configuration Utility icon, the name of the software
(Enterprise Online Configuration Utility), the name of the current network configuration
file, and the Minimize, Maximize, and Close buttons.
Click for the The number of XM The name of the current Minimize Maximize Close
Control Menu module channels allowed network configuration file
from the activation and window

17
EOLConfig GRG.book Page 18 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

To see the Control Menu, click the Online Configuration Utility icon on the title bar. The
following items appear on the Control Menu:

Item Description

Restore Choose Restore when you want to restore the window to its former size after you
have enlarged it by using the Maximize command or shrunk it by using the
Minimize command.
Move Choose Move when you want to reposition the window on the desktop by using the
arrow keys on the keyboard or the mouse.
Size Choose Size when you want to resize the window by using the arrow keys on the
keyboard or the mouse.
Minimize Choose Minimize when you want to shrink the window to an icon located on the
task bar. This performs the same function as if you clicked the Minimize button on
the title bar.
Maximize Choose Maximize when you want to enlarge the window to occupy the entire
screen. This performs the same function as if you clicked the Maximize button on
the title bar.
Close Choose Close when you want to exit the Online Configuration Utility. This
performs the same function as if you clicked the Close button on the title bar.

Menu bar

You can open any menu by holding the Alt key and pressing the underlined letter in the
menu name. For example, press Alt-v to display the View menu. You can also click the
icon at the left end of the menu bar to open the Control menu for the current window (Tree
View and Graph View windows).

Toolbar
The Online Configuration Utility toolbar contains the toolbar buttons. Each button is a
shortcut to a feature, all of which are also available from the Online Configuration Utility
menus.

18
EOLConfig GRG.book Page 19 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

The following table lists the Online Configuration Utility toolbar buttons and provides
you with a brief description of the function of the button and its corresponding menu bar
selection.

Button Description

Add a new XM module to the selected DeviceNet network. This performs the same
function as Edit > Add Device from the Menu bar.

Create a new network configuration file. This performs the same function as File > New
from the Menu bar.

Open an existing network configuration file. This performs the same function as File >
Open from the Menu bar.

Save the current network configuration file. This performs the same function as File >
Save As from the Menu bar.

Print the contents of the Tree View or Graph View window. This performs the same
function as File > Print from the Menu bar.

Cut the selected XM module from the Network tree and copy its device parameters to the
Clipboard. This performs the same function as Edit > Cut from the Menu bar. This
button is available when an XM module is selected in the Tree View or Graph View
window.
Copy the device parameters from the selected XM module to the Clipboard. This
performs the same function as if you chose Edit > Copy from the Menu bar. This button
is available when an XM module is selected in the Tree View or Graph View window.
Paste the XM module device parameters from the Clipboard to the selected XM module.
The selected XM module must be the same type as the copied parameters. This performs
the same function as Edit > Paste from the Menu bar. This button is available after you
cut or copy an XM module to place its parameters on the Clipboard.
Toggle the Online Configuration Utility between online and offline modes. This
performs the same function as Network > Go Online or Network > Go Offline from
the Menu bar.
Identify the selected XM module to determine if the Online Configuration Utility can
communicate with it. This performs the same function as Device > Identify Device
Online from the Menu bar. This button is available when the Online Configuration
Utility is online and an XM module is selected in the Tree View or Graph View window.
Upload the current configuration from all XM modules on the selected DeviceNet
network. This performs the same function as Network > Upload from Network from
the Menu bar. This button is available when the Online Configuration Utility is online
and a DeviceNet network is selected in the Tree View or Graph View window.

19
EOLConfig GRG.book Page 20 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Button Description

Download the configuration parameters for all XM modules on the selected DeviceNet
network from the Online Configuration Utility. This performs the same function as
Network > Download to Network from the Menu bar. This button is available when the
Online Configuration Utility is online and a DeviceNet network is selected in the Tree
View or Graph View window.
Display spectrum plots from the selected XM module. This performs the same function
as View > Spectrum Plot from the Menu bar. This button is available when the Online
Configuration Utility is online and an XM vibration measurement module is selected in
the Tree View or Graph View window (such as the XM-120 or XM-121).
Display gSE spectrum plots from the selected XM-122 gSE module. This performs the
same function as View > gSE Spectrum Plot from the Menu bar. This button is
available when the Online Configuration Utility is online and an XM-122 gSE module is
selected in the Tree View or Graph View window.
Display time waveform plots from the selected XM module. This performs the same
function as View > Time Waveform Plot from the Menu bar. This button is available
when the Online Configuration Utility is online and an XM vibration measurement
module is selected in the Tree View or Graph View window (such as the XM-120 or
XM-121).
Display spectrum map plots from the selected XM module. This performs the same
function as View > Spectrum Map Plot from the Menu bar. This button is available
when the Online Configuration Utility is online and an XM vibration measurement
module is selected in the Tree View or Graph View window (such as the XM-120 or
XM-121).
Display current value data from the selected XM module, including trend plots. This
performs the same function as View > Current Value from the Menu bar. This button is
available when the Online Configuration Utility is online and an XM module is selected
in the Tree View or Graph View (not available for XM-500 or other modules without
relays or measurement data).
Lock or unlock the current Plot window. Locking the plot prevents it from updating with
new data. This performs the same function as View > Lock from the Menu bar. This
button is available when the Online Configuration Utility is online and a Plot window is
active.
Enlarge the contents of the Tree View window or the Graph View window. This performs
the same function as View > Zoom-In from the Menu bar. This button is available when
the Tree View or Graph View window is active.
Reduce the contents of the Tree View window or the Graph View window. This performs
the same function as View > Zoom-Out from the Menu bar. This button is available
when the Tree View or Graph View window is active.

20
EOLConfig GRG.book Page 21 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

Right-click shortcut menus


To open a shortcut menu with tasks specific to the current selection:

Select an item, such


as an XM module, and
click the right mouse
button.

Network tree
The network tree displays the current network configuration.
„ When online, if you have uploaded your network and XM module configurations, the
network tree represents your actual networks and XM modules.
„ When offline, the network tree displays the contents of the current network
configuration file.

If you make any changes to the network configuration in the Online Configuration Utility, the
network tree no longer accurately represents the actual network configuration until you download
the changes to the network when online.

To the left of each network branch is either a + sign or a - sign. The + sign indicates that
the branch is closed; to expand the branch and display the underlying network structure,
click once. The - sign indicates that the branch is open, displaying the underlying network.

21
EOLConfig GRG.book Page 22 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Branch is
open (click to
close)

Branch is
closed (click to
open)

Quick Start steps


The following steps explain how to perform these tasks using the Online Configuration
Utility software:
„ initial steps to begin
„ configure a system online
„ configure a system offline
„ view data
„ specify default program settings
To use the quick start steps, select a task then perform all of the quick start steps for that
task. For detailed information on tasks or on using specific dialog boxes in Online
Configuration Utility, refer to the online help.

Quick Start initial steps


The following quick start steps describe the things you must do before you can use the
Online Configuration Utility to configure your networks and XM modules.

STEP 1 „ INSTALL AND CONNECT XM MODULES

If you are going to configure your network online, you must first install your XM
modules. This requires the following steps.
1. Install your XM modules and connect them to the transducers.
2. Connect the XM modules to the DeviceNet network.
3. Install the network gateway module or modules.

22
EOLConfig GRG.book Page 23 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

4. Connect the network gateway modules to the Ethernet network.

You can also use a programmable logic controller (PCL) as the Ethernet-DeviceNet gateway,
in the place of a network gateway module. However, you cannot use the Online Configuration
Utility to configure or communicate with a PLC. Contact Technical Support for more
information.

Refer to the documentation for the individual XM modules for assistance.

STEP 2 „ COMMISSION XM MODULES

Before you can add any XM module to a DeviceNet network, it may need to be
commissioned. This means that a node address and a baud rate must be programmed into
the XM module.
Most DeviceNet devices are factory commissioned with default values per the DeviceNet
specification. Usually, the node address is set to 63 and the data rate is set to 125K baud.
As long as the factory default parameters do not conflict with those of other devices
already on the network, you can connect the new device to the network and then use Tools
> Node Commissioning to change the node address and baud rate. If the date rate or
address conflicts, use a separate network to commission the device or use the XM Serial
Configuration Utility program with a local (serial cable) connection between the XM
module and the computer. The XM Serial Configuration Utility is included with the XM
modules.

If you have not set up your DeviceNet network yet, and cannot connect to an XM module with the
Online Configuration Utility, use the XM Serial Configuration Utility program with a local (serial
cable) connection between the XM module and the computer.

STEP 3 „ REGISTER EDS FILES

Before using the Online Configuration Utility with XM modules, you must first register
the electronic data sheets (EDS) for those modules. This stores the configuration and
identification information for the XM modules in the EDS library, and allows you to
access that information from the Online Configuration Utility.
1. Start the EDS Registration program. Click the Windows Start button, then select
Programs > Rockwell Software > RSLinx > Tools > EDS Hardware Installation
Tool.
2. In the Hardware Installation Tool, click Add to launch the EDS Wizard to add the
EDS files.
3. Follow the directions in the Wizard to register all the EDS files for the XM modules.
The EDS files are located in the Online Configuration Utility program directory. The
default directory for the EDS files is \Program Files\Rockwell Software\Emonitor.
4. Close the Hardware Installation Tool when finished.

23
EOLConfig GRG.book Page 24 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

STEP 4 „ RUN RSLINX TO CONFIGURE THE ETHERNET DRIVER

Before using the Online Configuration Utility, you must configure the driver that
communicates with the XM modules.
1. Start RSLinx. Click the Start button, then select Programs > Rockwell Software >
RSLinx > RSLinx Classic.
2. In RSLinx, select Communication > Configure Drivers.
3. In the Configure Drivers dialog, under Available Driver Types, select Ethernet
devices.
4. Click Add New.
5. Click OK to accept the default name for the driver (or you can change the name).
6. Enter the IP addresses of the network gateway modules in the Configure Driver
dialog.
7. Click Close to close the Configure Drivers dialog.

STEP 5 „ CHECK THE ETHERNET DRIVER WITH RSWHO


You can check the communication between your computer and the network gateway
modules after you have configured the Ethernet driver.
1. Start RSLinx if it is not already running (Start > Programs > Rockwell Software >
RSLinx > RSLinx).
2. Select Communication > RSWho.
3. Make sure the Autobrowse check box is selected in the RSWho window.
4. Double-click the Ethernet driver you configured with RSLinx. You should see the
network gateway modules you added for the Ethernet driver.
5. Close the RSWho window.
6. Close RSLinx.

Quick Start steps to configure your network online


The following quick start steps apply to the task of using the Online Configuration Utility
to configure your network and XM modules online. You can also configure your network
offline, as described in Quick Start steps to configure your network offline on page 29.

Make sure you have properly set up the Ethernet network communication as described in Quick
Start initial steps on page 22.

24
EOLConfig GRG.book Page 25 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

STEP 1 „ START THE ONLINE CONFIGURATION UTILITY


Click the EOL Configuration button in XM Online Data main window (see Starting the
Online Configuration Utility software on page 8 if necessary).

STEP 2 „ CREATE A NEW CONFIGURATION ONLINE

XM Online Data does not create a new network configuration file. In the Online
Configuration Utility, select File > New to create a new network configuration file.
Remember that you must manually load the new network configuration file when you
return to the XM Online Data.

STEP 3 „ BROWSE FOR AN ONLINE NETWORK

First, select the RSLinx driver for your network. Second, browse the network to locate all
the devices on that network.
1. If the Tree View is not displayed in the Online Configuration Utility program, click
the Tree View tab.
2. Click XM Ethernet Network in the Tree View to select the correct workstation level.
Select the
XM Ethernet network

3. Select Setup > Select Driver and select the Ethernet Devices driver you configured in
RSLinx. The driver appears in the Tree View under the XM Ethernet Network
workstation.
4. If the Online Configuration Utility is not already online, select Network > Go Online.
The word “Online” appears in the status bar at the bottom-right of the program
window.
5. Select Network > Refresh Network. The program browses the network to locate any
network gateway modules. The network gateway communicates between your
Ethernet network and the DeviceNet network.
6. After the program locates the network gateways connected to your Ethernet network,
browse the DeviceNet network attached to each network gateway module. Select the
first network gateway module by clicking it, then select Network > Refresh
Network. This locates all the devices (including XM modules) on the DeviceNet
network connected to that network gateway.
7. Repeat step 6 for each network gateway module.

You can also select Network > Auto Browse Network. The program automatically browses the
network, updating the Tree View and Graph View periodically. Auto browsing increases the
amount of network traffic, which may increase the response time from devices on the network.

25
EOLConfig GRG.book Page 26 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

STEP 4 „ UPLOAD AND CONFIGURE THE DEVICENET NETWORK

1. Select the first DeviceNet network by clicking the first network gateway module in
the Tree View.
Select the first network
gateway module

2. Select Network > Upload from Network.


3. You are prompted to upload the entire network; click Yes.
An upload dialog appears, indicating that the configuration of each XM module on the
network is being uploaded. This ensures that the online and offline configurations are
synchronized.
4. If you have multiple network gateway modules, repeat step 1 through step 3 for each
network gateway module to upload all DeviceNet networks.

STEP 5 „ CONFIGURE XM MODULES

You can configure only XM modules with the Online Configuration Utility. Other
DeviceNet devices can appear in the Tree View and Graph View, but you cannot upload
data from them or change their configuration parameters.
1. In either the Tree View or the Graph View, click the XM module that you want to
configure and select either Device > Properties or Device > Advanced Setup.

Select the first XM


module to
configure

26
EOLConfig GRG.book Page 27 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

The property pages for the selected XM module appear.

We recommend that you use Advanced Setup to configure XM modules. The fields in the
Advanced Setup dialogs are clearly labeled, and any associated parameters are
automatically updated. If you have used Rockwell Software products such as RSNetWorx™
and RSLinx, however, you may find the Properties dialogs more familiar.

2. Review each property page and configure your XM module, as necessary.

Remember to use the online help to obtain additional information. Press F1 or click the Help
button on the dialog to display the help topic for that dialog.

3. Click a different tab, or click OK to save the XM module information.


4. If you want to save the changes to the XM module, click Download.
5. Repeat step 1 through step 4 for each XM module that you want to configure on the
DeviceNet network.
6. If you want to rename the XM module, select Edit > Rename Device. Note that this
only saves the name of the XM module in the network configuration file. The name is
not stored in the XM module itself, so the same XM module can appear to have a
different name when using a different configuration file.
At various times, you may want to save the work you have completed on your network
configuration. To save a network configuration file (*.dcf), select File > Save.

STEP 6 „ CONFIGURE XM SCANNERS

You can configure only XM scanner modules with the Online Configuration Utility. Other
DeviceNet scanners can appear in the Tree View and Graph View, but you cannot upload
data from them, or change their configuration parameters.
1. In either the Tree View or the Graph View, click a scanner (for example, the XM-500,
XM-440, or 1788-EN2DN) that you want to configure, and then select either Device >
Properties or Device > Advanced Setup. For the network gateway in the Tree View,
click the network gateway in the DeviceNet section (NOT the network gateway
labeled Ethernet Station).

27
EOLConfig GRG.book Page 28 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

In the picture below, the Ethernet Station Number 000 represents the “Ethernet side”
of the XM-500 module. The XM-500 Ethernet/IP Gateway at node address 04
represents the “DeviceNet side” of the same XM-500 module.

Select the XM
scanner to configure

The property pages for the selected XM scanner appear.

We recommend that you use Advanced Setup to configure XM modules. The fields in the
Advanced Setup dialogs are clearly labeled, and any associated parameters are
automatically updated. If you have used Rockwell Software products such as RSNetWorx
and RSLinx, however, you may find the Properties dialogs more familiar.

2. Review each property page and configure your XM scanner, as necessary.


3. Click a different tab, or click OK to save the XM scanner information.
4. To save the changes to the XM scanner, click Download.
5. Repeat step 1 through step 4 for each XM scanner that you want to configure.

STEP 7 „ SAVE THE NETWORK CONFIGURATION ONLINE

Select File > Save to save the current network configuration file.
The Online Configuration Utility saves the network configuration file, using the file name
and directory selected when the file was first created.

While you can also use File > Save As to save the network configuration in a network configuration
file with a different name, we do not recommend doing so unless you want to create a backup file.
„ The Online Configuration Utility does not load the file created with File > Save As. You must
manually load it with File > Open.
„ In XM Online Data, you must manually select the new network configuration file.

28
EOLConfig GRG.book Page 29 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

Quick Start steps to configure your network offline


There are several steps that you must follow when using the Online Configuration Utility
to configure your network and XM modules offline. You can also configure your network
online; see the previous section, starting on page 24.

Make sure you have properly set up the Ethernet network communication as described in Quick
Start initial steps on page 22.

STEP 1 „ START THE ONLINE CONFIGURATION UTILITY


From the XM Online Data, click the EOL Configuration button in XM Online Data main
window (see Starting the Online Configuration Utility software on page 8 if necessary).

STEP 2 „ CREATE A NEW CONFIGURATION OFFLINE

XM Online Data does not create a new network configuration file. In the Online
Configuration Utility, select File > New to create a new network configuration file.
Remember that you must manually load the new network configuration file when you
return to XM Online Data.

STEP 3 „ SELECT THE DRIVER FOR THE NETWORK

1. If the Tree View is not displayed in the Online Configuration Utility program, click
the Tree View tab.
2. Click XM Ethernet Network in the Tree View to select the correct workstation level.
Select the
XM Ethernet network

3. Select Setup > Select Driver and select the Ethernet Devices driver you configured
in RSLinx. The driver appears in the Tree View under the XM Ethernet Network
workstation.

STEP 4 „ ADD THE NETWORK GATEWAYS

In this step you add one or more network gateway modules to the network configuration.
A network gateway module is a unique device that acts as both an Ethernet network
device and a DeviceNet network device. This makes it a “gateway” between the two
networks. The examples in this section use an XM-500 network gateway module, but you
use the same steps to add any network gateway.
„ In these steps, you first add and configure the Ethernet side of the network gateway
module. See the network gateway User's Guide for setting the IP address and other
hardware-related information.

29
EOLConfig GRG.book Page 30 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

„ Then you add the DeviceNet side of the network gateway module. Configuring the
DeviceNet side of the network gateway module is covered on page 32.

You must manually configure the RSLinx driver with the IP addresses of the network gateway
modules as described in Quick Start initial steps on page 22.

This picture shows a part of the Tree View. The Ethernet Station Number 000 represents
the “Ethernet side” of the XM-500 module. The XM-500 Ethernet/IP Gateway at node
address 04 represents the “DeviceNet side” of the same XM-500 module.

1. In the Tree View, click the RSLinx Driver for the Ethernet network.
Select the
RSLinx Driver

2. Select Edit > Add Device to start the Wizard to add an XM-500 module.
3. Select the XM-500 module, then click Next.
4. Enter the station number, DeviceNet address, and a description for the XM-500
module.

Write down the station number and DeviceNet address. You will need them later in this
procedure when you add the DeviceNet side of the XM-500.

5. Click Finish to add the XM-500 module. The XM-500 appears as an Ethernet Station
in the tree.
6. Make sure the XM-500 module is selected in the tree, then select Edit > Add Device
to add the DeviceNet side of the XM-500 module.
7. Select the XM-500 module, then click Next.
8. Enter the station number, DeviceNet address, and a description for the XM-500
module. The addresses must match the addresses you entered for the module in step 4.

30
EOLConfig GRG.book Page 31 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

9. Click Finish to add the DeviceNet side of the XM-500 module. The XM-500 appears
as a device under the Ethernet Station in the tree.
10. Repeat step 1 through step 9 for each network gateway module in the network.

STEP 5 „ ADD AND CONFIGURE XM MODULES

1. In the Tree View, click the network gateway Ethernet Station for which you want to
add XM modules.
Select the network
gateway module

2. Select Edit > Add Device to start the Wizard to add an XM module.
3. Select the desired module type, then click Next.
4. Enter the node address and a description for the module.
5. Click Finish to add the XM module. The XM module appears in the tree. Modules are
sorted by node address.
6. Make sure the XM module you just added is selected, then select either Device >
Properties or Device > Advanced Setup. The property pages for the selected XM
module appear.

We recommend that you use Advanced Setup to configure XM modules. The fields in the
Advanced Setup dialogs are clearly labeled, and any associated parameters are
automatically updated. If you have used Rockwell Software products such as RSNetWorx
and RSLinx, however, you may find the Properties dialogs more familiar.

7. Review each property page and configure your XM module, as necessary.

Remember to use the online help to obtain additional information. Press F1 or click the Help
button on the dialog to display the help topic for that dialog.

8. Click a different tab, or OK to save the XM module information.


9. Repeat step 1 through step 8 for each XM module that you want to configure on the
DeviceNet network.
At various times, you may want to save the work you have completed on your network
configuration. To save a network configuration file (*.dcf), select File > Save.

31
EOLConfig GRG.book Page 32 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

STEP 6 „ ADD AND CONFIGURE XM SCANNERS

To configure the DeviceNet side of a network gateway, skip to step 7. For the steps to add
the DeviceNet side of a network gateway to the tree, see Add the Network Gateways on
page 29. The examples in this section use an XM-500 as the network gateway module, but
you use the same steps to add any network gateway.
1. In the Tree View, click the XM-500 Ethernet Station for which you want to add an
XM scanner (such as the XM-440).
2. Select Edit > Add Device to start the Wizard to add an XM scanner module.
3. Select the XM scanner module, then click Next.
4. Enter the addresses and a description for the XM scanner.
5. Click Finish to add the XM scanner to the tree. The XM scanner appears in the tree.
Modules are sorted by node address.
6. Make sure the XM module you just added is selected. For the XM-500 in the Tree
View, click the XM-500 in the DeviceNet section (NOT the XM-500 labeled Ethernet
Station). Select either Device > Properties or Device > Advanced Setup.
In the picture below, the Ethernet Station Number 000 represents the “Ethernet side”
of the XM-500 module. The XM-500 Ethernet/IP Gateway at node address 04
represents the “DeviceNet side” of the same XM-500 module.

Select the XM
scanner to configure

We recommend that you use Advanced Setup to configure XM modules. The fields in the
Advanced Setup dialogs are clearly labeled, and any associated parameters are
automatically updated. If you have used Rockwell Software products such as RSNetWorx
and RSLinx, however, you may find the Properties dialogs more familiar.

The property pages for the selected XM scanner appear.

32
EOLConfig GRG.book Page 33 Wednesday, January 14, 2009 8:00 AM

• • • • •
3 • GETTING STARTED WITH ENTERPRISE ONLINE CONFIGURATION UTILITY

7. Review each property page and configure your XM scanner, as necessary.

Remember to use the online help to obtain additional information. Press F1 or click the Help
button on the dialog to display the help topic for that dialog.

8. Click a different tab, or OK to save the device information.


9. Repeat step 1 through step 8 for each XM scanner that you want to add and configure
on the DeviceNet network.

STEP 7 „ SAVE THE NETWORK CONFIGURATION OFFLINE

Select File > Save to save the network configuration in the current network configuration
file.
The Online Configuration Utility saves the network configuration file, using the file name
and directory selected when the file was first created.

While you can also use File > Save As to save the network configuration in a network configuration
file with a different name, we do not recommend doing so unless you want to create a backup file.
„ The Online Configuration Utility does not load the file created with File > Save As. You must
manually load it with File > Open.
„ In XM Online Data, you must manually select the new network configuration file.

STEP 8 „ DOWNLOAD THE NETWORK CONFIGURATION WHEN ONLINE

After you have configured your network offline, you must go online to download the
configurations to the XM modules when the computer can communicate with the
network.
1. If the Online Configuration Utility is not already online, select Network > Go Online.
The word “Online” appears in the status bar at the bottom-right of the program
window.
2. Select the first DeviceNet network by clicking the first network gateway module in
the Tree View.
3. Select Network > Download to Network.
4. You are prompted to download the entire network; click Yes.
A download dialog appears, indicating that the configuration of each XM module on
the network is being downloaded. This ensures that the online and offline
configurations are synchronized.
5. If you have multiple network gateway modules, repeat step 2 through step 4 for each
network gateway module to download all DeviceNet networks that you want to
configure.

33
EOLConfig GRG.book Page 34 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

Quick Start steps for viewing data


The Online Configuration Utility displays data from XM modules in both interactive Plot
windows and numeric data tables. The following plot types are available, depending on
the type of XM module.
„ Trend plot: A graph of the amplitude of a measurement against time.
„ Spectrum plot: A graph of amplitude against frequency.
„ Spectrum Map plot: A three dimensional graph of amplitude against frequency
against time. Spectrum map plots show multiple spectrum plots over time, allowing
you to see the variations in individual frequencies.
„ Time Waveform plot: A graph of amplitude against time.

The Online Configuration Utility must be online to view data in plots.

1. In the Tree View or Graph View, select the XM module for the plot.
2. Select one of the plot commands from the View menu:
‡ View > Spectrum Plot
‡ View > Time Waveform Plot
‡ View > Spectrum Map Plot
‡ View > Current Value (for trend plots)
For more information on any plot, click the plot to make it active, and then press F1 to
display the help topic for the plot.

Specifying default settings for the Online Configuration Utility


Select Setup > Preferences from the menu bar. This command allows you to set the
Online Configuration Utility defaults:
„ automatically browse the selected DeviceNet network when the Online Configuration
Utility goes online
„ select the nodes to browse for the selected DeviceNet network
„ prompt to save the network configuration file when closing the file
„ set the device communication timeout
Press F1 in the Preferences dialog to display the online help topic with a description of
each item in that dialog.

34
EOLConfig GRG.book Page 35 Wednesday, January 14, 2009 8:00 AM

Index

1788-EN2DN devices, configuring „ 27, 32 network gateway „ 29


uploading „ 26
A downloading
network configuration files „ 33
about Online Configuration Utility „ 11
scanner configuration „ 28
activation „ 7
XM module configuration „ 27
adding
drivers
network gateways offline „ 31, 32
checking „ 24
scanner modules offline „ 32
configuring Ethernet „ 24
XM modules offline „ 31
selecting Ethernet „ 25, 29
B E
backup files „ 28
EDS Hardware Installation Tool „ 23
baud rate, commissioning „ 23
electronic data sheets (EDS), registering „ 23
browsing
Emonitor Online System „ 3
DeviceNet network „ 25
Ethernet drivers
Ethernet network „ 25
checking communication „ 24
naming „ 24
C Ethernet network
checking Ethernet driver „ 24 browsing „ 25
commissioning checking driver „ 24
XM modules „ 23 configuring driver „ 24
XM Serial Configuration Utility „ 23 network gateway „ 29
configuring selecting driver „ 25, 29
1788-EN2DN devices „ 27, 32 exploring Online Configuration Utility „ 17
Ethernet driver „ 24
network gateways „ 27, 32 F
scanner modules „ 27, 32
FactoryTalk Activation, installing „ 7
XM modules „ 26, 31
XM-440 modules „ 27, 32
XM-500 modules „ 27, 32 G
configuring networks getting started with Online Configuration
offline „ 13 Utility „ 11
online „ 11 Graph View window „ 16
Current Value window „ 17
Customer Support „ 4 I
icons
D Information Message window „ 16
data, viewing „ 13 Tree View window „ 15
DeviceNet network Information Message window „ 16
browsing „ 25 initial steps „ 11

35
EOLConfig GRG.book Page 36 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE

installing release notes „ 7


FactoryTalk Activation „ 7 right-click shortcut menus „ 21
Online Configuration Utility „ 7, 8 running „ 8
troubleshooting „ 8 software requirements „ 7
installing Online Configuration Utility „ 3 starting „ 25, 29
system requirements „ 7
M Online Data Management Console „ 8
online help „ 2
menus
menu bar „ 18
right-click „ 21 P
plot types
N spectrum „ 34
spectrum map „ 34
naming
time waveform „ 34
Ethernet drivers „ 24
trend „ 34
network configuration files „ 25, 28
Plot windows „ 17
XM modules „ 27
programmable logic controllers „ 12, 23
navigating Online Configuration Utility „ 17
network configuration files
backup files „ 28 Q
creating „ 25, 29 Quick Start steps „ 22
downloading „ 33 configuring networks offline
in Online Configuration Utility „ 12 adding network gateways „ 29
in XM Online Data „ 12, 25 adding XM modules „ 31
naming „ 25, 28 adding XM scanners „ 32
saving „ 28, 33 configuring XM modules „ 26
network gateways configuring XM scanners „ 27
adding offline „ 29, 31, 32 creating new configurations „ 29
configuring „ 27, 32 downloading network configurations
network tree „ 21 „ 33

networks overview „ 29
adding gateways „ 29 saving network configurations „ 28, 33
configuring offline „ 13 selecting network drivers „ 29
configuring online „ 11 starting the Online Configuration Utility
saving configuration files „ 28, 33 „ 29

selecting driver „ 25, 29 uploading DeviceNet networks „ 26


node address, commissioning „ 23 configuring networks online
browsing for networks „ 25
O creating a new configuration „ 25
overview „ 24
“offline”, definition „ 13
starting the Online Configuration Utility
“online”, definition „ 11
„ 25
Online Configuration Utility
initial steps
about „ 1
checking Ethernet drivers „ 24
hardware requirements „ 7
commissioning XM modules „ 23
installation „ 3
configuring Ethernet drivers „ 24
main windows „ 14

36
EOLConfig GRG.book Page 37 Wednesday, January 14, 2009 8:00 AM

• • • • •
INDEX

initial steps (continued) configuring network gateway modules „ 15


installing XM modules „ 22 configuring XM modules locally „ 23
overview „ 22 selecting DeviceNet networks „ 16
registering EDS files „ 23 using programmable logic controllers „ 12,
viewing data „ 34 23
using Save As „ 28
R viewing plots „ 34
working online „ 11
registering electronic data sheets „ 23
Tree View window „ 14
release notes „ 7
trend plots „ 34
right-click menus „ 21
troubleshooting installation „ 8
RSLinx
checking Ethernet driver „ 24
configuring Ethernet driver „ 24 U
RSWho „ 24 Unload Station computer „ 3
RSWho „ 24 uploading
running the Online Configuration Utility „ 8 DeviceNet network „ 26
XM module configurations „ 26
S
saving network configuration files „ 28, 33 V
scanner modules viewing data, XM modules „ 13, 34
adding offline „ 32
configuring „ 27, 32 W
download configuration „ 28
warranty service „ 4
selecting Ethernet driver „ 25, 29
working offline „ 4, 13
software requirements „ 7
working online „ 3, 11
specifying default settings „ 34
spectrum map plots „ 34
spectrum plots „ 34 X
starting Online Configuration Utility „ 8, 25, XM modules
29 adding offline „ 31
baud rate „ 23
T commissioning „ 23
configuring „ 26, 31
Technical Support
downloading configuration „ 27
Online Support Requests „ 5
installing and connecting „ 22
product updates/replacement media „ 5
naming „ 27
Technical Phone Support „ 4
node address „ 23
Technical Support Website „ 4
uploading configurations „ 26
warranty service „ 4
viewing data „ 13, 34
time waveform plots „ 34
XM Serial Configuration Utility „ 23
Tips
XM-440 modules, configuring „ 27, 32
Advanced Setup vs. Properties „ 27
XM-500 modules, configuring „ 27, 32
auto browsing networks „ 25

37
EOLConfig GRG.book Page 38 Wednesday, January 14, 2009 8:00 AM

• • • • •

ENTERPRISE ONLINE CONFIGURATION UTILITY GETTING RESULTS GUIDE