200–300 kVA
Operation Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
WARNING
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent disturbances.
Powerware and X−Slot are registered trademarks and ConnectUPS is a trademark of Eaton Electrical
Inc. Modbus is a registered trademark of Modicon.
ECopyright 2004-2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this
document may be reproduced in any way without the express written approval of Eaton Corporation.
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
1.1 Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
1.2 For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−2
1.3 Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−2
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com i
Table of Contents
7 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−1
7.1 Locating the Communication Bays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−1
7.2 X−Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−2
7.3 LanSafe Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−3
7.4 Connecting Equipment to a Serial Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−3
7.5 Configuring the Serial Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−6
7.5.1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−7
7.5.2 Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−7
7.5.3 Data/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
7.5.4 Handshaking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
7.5.4.1 Disabled (No Handshaking) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
7.5.4.2 XON/XOFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
7.5.5 Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
7.5.6 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−8
ii EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Table of Contents
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W−1
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com iii
Table of Contents
List of Figures
Figure 2-1. Typical Powerware 9315 UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−2
Figure 2-2. Main Elements of the UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−3
Figure 3-1. Path of Current Through the UPS in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−2
Figure 3-2. Path of Current Through the UPS in Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−3
Figure 3-3. Path of Current Through the UPS in Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4
Figure 3-4. Location of the Monitor Panel and the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−5
Figure 4-1. UPS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4−1
Figure 5-1. UPS Monitor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−1
Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS) . . . . . . . . . . . 5−2
Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS) . . . . . . . . . . . . 5−5
Figure 5-4. Load Amps Meters Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−6
Figure 5-5. Event History Log Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−7
Figure 5-6. Active System Events Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−8
Figure 5-7. Unit Statistics Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−9
Figure 5-8. Mimic Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−10
Figure 5-9. Time Setup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−11
Figure 5-10. Setup Serial Port 1 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−12
Figure 6-1. External Connections for Building Alarm Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6−1
Figure 6-2. Summary Alarm Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6−2
Figure 6-3. Remote Monitor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6−3
Figure 6-4. Relay Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6−6
Figure 6-5. Supervisory Contact Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6−7
Figure 7-1. Location of Communication Bays on the UPS (Powerware 9315 300) . . . . . . . . . . . . . . . 7−2
Figure 7-2. Optional X−Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−3
Figure 7-3. Port 1 (DB−9) Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−4
Figure 7-4. Port 2 (DB−25) Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−4
Figure 7-5. Setup Serial Port 1 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−6
Figure 7-6. Event History Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−10
Figure 7-7. System Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−11
Figure 7-8. Battery Test Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−12
iv EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 1 Introduction
The Powerware® 9315 uninterruptible power supply (UPS) online power protection
prevents loss of valuable electronic information, minimizes equipment downtime, and/or
minimizes the adverse effect on equipment production due to unexpected power
problems.
The Powerware 9315 UPS continually monitors incoming electrical power and removes the
surges, spikes, sags, and other irregularities that are inherent in commercial utility power.
Working with your building’s electrical system, the UPS supplies clean, consistent power
that your sensitive electronic equipment requires for reliable operation. During brownouts,
blackouts, and other power interruptions, one or more optional battery cabinets can
provide emergency power to safeguard your operation.
The UPS functions automatically and require very little attention during normal operation.
However, you should read and understand the procedures described in this manual to
ensure trouble-free operation. In particular, you should be thoroughly familiar with the
Load Off procedure described in Chapter 11, Using the LOAD OFF Button."
A Bold type highlights important concepts in discussions, key terms in procedures, and
menu options, or represents a command or option that you type or enter at a prompt.
A Italic type highlights notes and new terms where they are defined.
Icon Description
[Keys] Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The
term UPS system refers to the entire power protection system – the UPS cabinet, battery
strings, and options or accessories installed.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 1−1
Introduction
Please call the Eaton Help Desk for Powerware products at:
1−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 2 Getting Started
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside
the UPS.
WARNING
A This UPS contains its own energy source (batteries). The output receptacles may carry live
voltage even when the UPS is not connected to an AC supply.
A Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
A To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
A Ensure all power is disconnected before performing installation or service.
CAUTION
A Batteries can present a risk of electrical shock or burn from high short−circuit current.
Observe proper precautions. Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized personnel away
from batteries.
A Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
A Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
A Keep the UPS doors closed to ensure proper cooling airflow and to protect personnel from
dangerous voltages inside the unit.
A Do not operate the UPS system close to gas or electric heat sources.
A The operating environment should be maintained within the parameters stated in this
manual.
A The UPS system is not intended for outdoor use.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2−1
Getting Started
A Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of
the equipment.
Each cabinet of the UPS system is shipped separately. As shown in Figure 2-1, you can
combine a UPS with any of the options described in this manual to meet your system
needs. The UPS and options are described in detail later in this manual. The following
descriptions provide a brief overview of standard UPS features and available
enhancements.
NOTE You should read this manual and have thorough knowledge of UPS operation
before attempting to operate any of the UPS switches, controls, or optional components.
2−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Getting Started
The power required by your equipment is called the critical load. The UPS supplies the
critical load with conditioned power that is synchronized with your utility power. Figure 2-2
shows the main elements of the UPS.
Battery Cabinet
Power Processing
Unit (PPU) Output
Transformer
AC Input to AC Output
Rectifier/ to Critical
Charger Load
Output
Rectifier/ Inverter Contactor
Charger
Input
Filter Digital
Metering
AC Input to Static
Bypass Switch
Bypass
Contactor
UPS Cabinet
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2−3
Getting Started
2−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Getting Started
2.5.1 Battery
You can enhance the protection provided by the UPS with one or more backup battery
supplies equipped with sealed lead-acid, maintenance-free batteries in a matching cabinet.
Each battery cabinet contains individual modular battery trays and a battery circuit breaker.
Several battery capacities are available.
The UPS battery cabinets can be paralleled; you can increase the battery backup time by
adding battery cabinets to your UPS system. The Powerware 9315 can support up to four
battery cabinets.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2−5
Getting Started
2−6 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Getting Started
2.5.10 Modem
An optional modem is available for use with the UPS Remote Notification feature
described in Remote Notification" on page 7−19. Refer to the manual supplied with the
modem for operating instructions.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2−7
Getting Started
RISK OF ELECTRIC SHOCK − Indicates that a risk of electric shock is present and the associated
warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for additional
information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS
may contain sealed, lead-acid batteries. Batteries must be recycled.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
2−8 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 3 Understanding UPS Operation
The UPS functions automatically to supply AC electrical power to the critical load. The UPS
always operates in one of three modes:
A In Normal mode, the critical load is supplied by the inverter, which derives its power
from rectified utility AC power. In this mode, the rectifier also provides charging current
for the battery.
A In Bypass mode, the critical load is directly supported by utility power.
A In Battery mode, the battery cabinet provides DC power, which maintains inverter
operation. The battery supports the critical load.
The UPS continually monitors itself and the incoming utility power, and automatically
switches between these modes as required, with no operator intervention. The
sophisticated detection and switching logic inside the UPS ensures that operating mode
changes are automatic and transparent to the critical load. The UPS switches operating
modes in response to these system events:
System events, alarm horns, and indicator lights are described in Chapter 10, Responding
to System Events."
Figure 3-1 shows the path of electrical power through the UPS system when the UPS is
operating in Normal mode.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3−1
Understanding UPS Operation
Bypass
Bypass
Input
K4
Rectifier Inverter
Output
CB1 K3
Rectifier
Input
(Closed)
Transformer
Battery
Path of electrical power
If the UPS system becomes overloaded, the UPS switches to Bypass mode. The UPS
automatically returns to Normal mode when the error condition is cleared and system
operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains
in that mode until the failure is corrected and the UPS is back in service.
3−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Understanding UPS Operation
CAUTION
The critical load is not protected while the UPS is in Bypass mode.
Figure 3-2 shows the path of electrical power through the UPS system when the UPS is
operating in Bypass mode.
Bypass
Bypass
Input
K4
Rectifier Inverter
Output
CB1 K3
Rectifier
Input
(Open)
Transformer
Battery
Path of electrical power
You can transfer the UPS from Normal mode to Bypass mode manually. However, the UPS
switches automatically to Bypass mode whenever the inverter can no longer supply the
critical load. If the UPS transfers to Bypass mode from Normal mode due to any reason
other than operator intervention, the UPS automatically attempts to transfer back to
Normal mode (up to three times within a 10-minute period). The fourth transfer will lock
the critical load on the bypass source and requires operator intervention to transfer.
Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS
is unable to return to Normal mode following an automatic transfer to Bypass mode, an
alarm condition is recorded.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3−3
Understanding UPS Operation
Figure 3-3 shows the path of electrical power through the UPS when operating in Battery
mode.
Bypass
Bypass
Input
K4
Rectifier Inverter
Output
CB1 K3
Rectifier
Input
(Closed)
Transformer
Battery
Path of electrical power
When the discharging battery voltage reaches the lower limit of UPS operation capability,
the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a
Shutdown Imminent" warning occurs. The warning time before critical load loss occurs is
approximately two minutes, depending on load configuration and the battery charge.
If incoming power returns to within specified parameters, the UPS automatically returns to
Normal mode and alarm indications clear. However, the process of returning to Normal
mode is not instantaneous. The rectifier gradually draws increasing power from the
incoming utility until Normal mode is achieved.
3−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Understanding UPS Operation
Control Panel
Monitor
Panel
Figure 3-4. Location of the Monitor Panel and the Control Panel
The Monitor Panel on the left front of the UPS continually indicates the present mode of
UPS operation. This panel contains an LCD screen, backlit status indicators, and the LOAD
OFF button. Use the LCD screen on the Monitor Panel to view performance meters or
graphic representations of UPS operation. The Monitor Panel is described in detail in
Chapter 5, Using the Monitor Panel." A quick reference label describing how to use the
Monitor Panel is located inside the UPS above the Control Panel.
Open the right front door of the UPS to view the Control Panel containing various controls
and switches. These control power to and from the UPS, and allow you to change the UPS
mode manually. The Control Panel is discussed in Using the Control Panel" on page 4−1.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3−5
Understanding UPS Operation
3−6 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 4 Starting and Stopping the UPS
This chapter describes how to use the Control Panel to start and stop the UPS.
NOTE Before starting the UPS, ensure all installation tasks are complete and a
preliminary startup has been performed by authorized service personnel. The
preliminary startup verifies all electrical interconnections to ensure the installation
was successful and the UPS system operates properly.
CAUTION
Incorrect use of the power controls on the Control Panel can cause a loss of power to the
protected equipment.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 4−1
Starting and Stopping the UPS
The following describes the switches on the Control Panel (see Figure 4-1):
A The MODE switch is a two-position rotary switch that controls the manual transfer of the
UPS to and from Bypass mode. The MODE switch is used to:
− Place the critical load in Bypass mode when the UPS is operating in Normal mode and
the bypass source is within acceptable limits. If the transfer does not occur within two
seconds, an alarm sounds.
− Prevent transfer to Normal mode when the UPS is in Bypass mode.
− Shut down the power processing unit (inverter and rectifier) of the UPS.
A The BATTERY switch is a two-position rotary switch that allows you to manually shunt
trip the battery breakers in remote cabinets.
A The circuit breaker (CB1) switch controls the operation of the rectifier and inverter. If
CB1 is on (closed), the rectifier turns on when the START switch is activated and the
proper voltage is at the input terminals.
A The PUSH TO RESET button is described in Resetting the UPS System after Load Off" on
page 11−2.
A The START switch activates the power controls on the Control Panel. The START switch
is center-biased (the key will rest only in the upright position). Its operation is similar to
that of an automobile ignition switch. After setting the operator controls, you turn the
START switch to the right momentarily to activate the controls. When you release it, it
returns to the upright position.
The following sections describe how to operate these controls to start, stop, or change the
operating mode of the UPS.
2. Verify that the Load Off PUSH TO RESET button is pressed in.
The rectifier turns on, then the inverter turns on. The UPS display and alarm alert
you to close the battery breaker.
4−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Starting and Stopping the UPS
When the inverter reaches full voltage, it turns on and supplies power to the
critical load. It takes less than one minute for the UPS to achieve Normal mode.
If a bypass source is available when you turn the START switch on, the critical load
is immediately supplied by the bypass source in Bypass mode until the inverter
turns on and the UPS transfers to Normal mode. The status indicators on the
Monitor Panel indicate when the UPS is in Bypass mode or Normal mode as
appropriate.
The UPS switches to Bypass mode. If the bypass source is not available, the power
processor remains on and an alarm sounds.
2. When the transfer is complete (the LCD screen reads On Bypass"), move the CB1
switch to OFF.
The bypass source supplies the critical load and the power processor de-energizes.
The Bypass mode indicator illuminates on the Monitor Panel.
1. Turn the MODE switch to BYPASS. (The remaining switches can be in any position.)
Power to the critical load is supplied by the bypass source. No backup is available.
4.1.4 To Shut Down Power to the Critical Load While in Bypass Mode
To perform maintenance or service on the critical load, you must shut it down first:
1. Turn off all equipment that is being powered through the UPS.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 4−3
Starting and Stopping the UPS
4−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 5 Using the Monitor Panel
This chapter describes the Monitor Panel and how to monitor and control UPS operation.
The Monitor Panel is a black rectangular area on the front of the UPS (see Figure 5-1).
The Monitor Panel contains a flat liquid crystal display (LCD) screen (1), a horizontal row
of buttons (2), a vertical column of backlit status indicators (3), and the red LOAD OFF
button (4). A quick reference label describing how to use the Monitor Panel is located
inside the UPS above the Control Panel. The following sections describe the Monitor Panel
in detail.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−1
Using the Monitor Panel
B
Battery Input Output G
Percent
100%
VAB VBC VCA FREQ VAB VBC VCA FREQ
480 480 480 60.0 480 480 480 60.0
IA IB IC IA IB IC IN
480 480 480 361 361 361 000
KVA KW PF KVA KW PF
399 379 0.95 300 240 0.80
C Meters
Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS)
A The UPS status area contains three lines that display the current state of the UPS. The first line
shows the present operational mode of the UPS. The second line shows the highest level of the
current active alarms, and the third line shows any notices the UPS has posted. (For more
information about alarms and notices, see Chapter 10, Responding to System Events.")
B The battery charge box shows the percentage of battery capacity available.
C The menu box shows the currently selected menu and lists the options available on that menu. The
title at the top of the menu box is also shown below on the menu bar (E). Press the and
buttons to scroll up and down through the options in the menu box.
D The currently selected option is highlighted in the menu box. Press the and buttons to move
the highlight up or down. The data in the information area (G) changes accordingly.
E The menu bar lists the titles of the menus. The title of the menu currently displayed in the menu
box is highlighted. When you press the and buttons to move the highlight left or right, the
data in the menu box and the information area change accordingly.
F The timestamp shows the current date and time. This date and time are recorded in the Event Log
when a notice or alarm is activated.
G The information area contains data about UPS status and operations. Select a menu option to
display statistics or graphics.
5−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using the Monitor Panel
You can use the LCD screen and the buttons beneath it to:
A Press the and buttons to move through the options in a menu, or to scroll through
the list of alarms and notices in the event log.
A Press the and buttons to move through the menu titles on the menu bar. Press
them simultaneously to silence the horn, or to test the lamps behind the status
indicators.
A Press the button to toggle the use of the and buttons between the menu box
and the information area.
CAUTION
All power to the critical load is lost when you press the LOAD OFF button. You should use the
LOAD OFF button only when you want to de-energize the critical load.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−3
Using the Monitor Panel
For more information about audible horns, see System Event Horns" on page 10−1.
To test the LEDs behind the status indicators, press the and buttons simultaneously
for three seconds. All the indicators should illuminate while you hold down these buttons.
If any indicator does not illuminate, its LED may need to be replaced. Contact your Eaton
service representative if you have a problem with the indicator LEDs.
A Meters − Displays UPS performance meters for the system or critical load.
A Events − Displays the list of Active System Events and a historical log of system events.
A Statistics − Displays statistical information about UPS operations for the battery, load, or
line.
5−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using the Monitor Panel
Figure 5-3 shows the LCD screen as it appears when you first start the UPS. The Meters
menu is displayed in the menu box, with the System option highlighted. In the information
area, the system meters show their current readings.
Battery
Input Output
Percent
100%
VAB VBC VCA FREQ VAB VBC VCA FREQ
480 480 480 60.0 480 480 480 60.0
IA IB IC IA IB IC IN
480 480 480 361 361 361 000
KVA KW PF KVA KW PF
399 379 0.95 300 240 0.80
Meters
Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the kVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area
displays the DC voltage (V) and the DC current (I).
Select Load Amps from the Meters menu to see a real-time bar graph of the output
current of the UPS. The graph shows the current for each phase.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−5
Using the Monitor Panel
100%
75%
Meters
50%
System
25%
Load Amps
0%
Phase A Phase B Phase C
5−6 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using the Monitor Panel
Select History from the Events menu to display the Event History Log. The Event History
Log lists up to 400 system events in chronological order, with the most recent event listed
last. The end of the log appears when you display the screen, and you must scroll upward
to view older event listings.
Battery
Percent Event History Log
100% Date / Time Event Description
May
A small return arrow ( ) appears in the upper right corner of the information area of
the Event History Log screen. This arrow is a reminder that you can press the button
on the Monitor Panel to toggle the scroll bar between the menu box and the information
area. When the scroll bar is in the information area, the return arrow is in the menu box.
When the scroll bar is in the menu box, the return arrow is in the information area.
When the scroll bar is in the information area, you can press the and buttons to scroll
through the Event History log.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−7
Using the Monitor Panel
Select Active from the Events menu to display a listing of all system events that are
currently active. The most recent system event is listed first. As events clear, they are
removed from the Active System Events listing.
Events
History
Active
5−8 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using the Monitor Panel
Select Unit from the Statistics menu to display a listing of statistics about UPS operation.
The left column shows the number of UPS incidents for the current month and total from
the start date shown at the top of the screen. The top right column shows the time that
the UPS was on bypass, battery, or generator, and the amount of time the UPS logic has
been functioning since the start date. The lower right column shows the percent of
availability of the UPS and the bypass source.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−9
Using the Monitor Panel
Select Mimic from the Graphics menu to display a real-time graphical representation of
the flow of current through the UPS.
Battery
Percent Bypass
100%
CB1 K3
Rectifier Inverter
Graphics
K2
Mimic
Battery
The Mimic screen shows the internal components of the UPS cabinet. The flow of current
through the components is highlighted.
5−10 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using the Monitor Panel
Select Time from the Setup menu to display the Time Setup screen. The Time Setup screen
allows you to set the internal timestamp of the UPS. The timestamp is used for logging
events in the Event History Log. Figure 5-9 shows the Time Setup screen.
Battery
Percent Set Time & Date
100%
DAY DT MON YR HR:MN SAVE
MON 07 APR 97 15:06 YES
Setup
Port 1
Port 2
Time
The small return arrow ( ) appears in the upper right corner of the Time Setup screen.
This arrow is a reminder that you can press the button on the Monitor Panel to toggle
the buttons between the menu box and the information area. When the scroll bar is in the
information area, the return arrow is in the menu box. When the scroll bar is in the menu
box, the return arrow is in the information area.
When the scroll bar appears in the information area, you can use the buttons to change
the timestamp settings. To change a setting in the timestamp, press the and buttons
to highlight the setting you want to change. To increase the setting (make it a higher
value), press the button. To decrease the setting (make it a lower value), press the
button. If you want to save the settings upon exit from this screen, be sure the SAVE field
is set to YES.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5−11
Using the Monitor Panel
Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens. The
Port Setup screens allow you to specify settings for the two serial communication ports on
the UPS. Figure 5-10 shows the Setup Serial Port 1 screen.
NOTE The X−Slot communication bay is connected internally to the DB−25 port by
default; the DB−25 is disabled for other uses. Contact your Eaton service representative
to purchase, install, and set up an external modem or an internal X−Slot Modem Card.
Battery
Percent Setup Serial Port 1
100%
MODE RATE DATA/STOP HANDSHAKING SAVE
TERMINAL 9600 8 1 XON / XOFF NO
Setup
Port 1
Port 2
Time
The small return arrow ( ) appears in the upper right corner of the Port Setup screen.
This arrow is a reminder that you can press the button on the Monitor Panel to toggle
the buttons between the menu box and the information area. When the scroll bar is in the
information area, the return arrow is in the menu box. When the scroll bar is in the menu
box, the return arrow is in the information area.
When the scroll bar appears in the information area, you can use the buttons to change
the port configuration. To change a setting, press the and buttons to move the
highlight to the setting you want to change. To scroll through the available options for that
setting, press the or button. To save the settings upon exit from this screen, be sure
the SAVE field is set to YES.
The setup screens for Port 1 and Port 2 are identical. For detailed information about
configuring the serial ports, see Chapter 7, Communication."
5−12 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 6 Using Features and Options
You can add available options and accessories to enhance the performance of your UPS
system. This chapter provides detailed descriptions of some of the features and options
introduced earlier in this manual.
TB1 TB2
1 BLDG ALARM 1 1 REMOTE EPO
2 BLDG ALARM 1 RTN 2 REMOTE EPO RTN RS−485
3 BLDG ALARM 2 3
4 BLDG ALARM 2 RTN 4 ON INV NOTE:
5 BLDG ALARM 3 5 ON INV RTN All building alarm inputs or remote
6 BLDG ALARM 3 RTN 6 ON BYPASS features require an isolated, normally
7 BLDG ALARM 4 7 ON BYPASS RTN open contact or switch (rated at
8 BLDG ALARM 4 RTN 8 BATTERY CONTACTOR CLOSED 24 Vdc 20 mA minimum) connected
9 BLDG ALARM 5 9 BATTERY CONT RTN between the alarm input terminal and
10 BLDG ALARM 5 RTN 10 RELAY 1 NO
common terminal as shown. All
11 BLDG ALARM 6 11 RELAY 1 NC
control wiring, relay, and switch
12 BLDG ALARM 6 RTN 12 ALARM RTN
contacts are customer−provided.
13 13 RELAY 2 NO
14 14 RELAY 2 NC RS−232
15 15 NOTICE RTN
Regardless of how you assign the building alarms, they display as Building Alarm 1, Building
Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use
twisted−pair wires for each alarm input and common.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−1
Using Features and Options
TB2
ALARM NO 10
ALARM NC 11
COMMON 12
NOTICE NO 13
NOTICE NC 14
COMMON 15
You can specify that each contact be either normally closed (NC) or normally open (NO). If
the state of the contact changes from the state you specify as normal, an alarm is issued.
You can connect these contacts to equipment at your facility (such as a light or an alarm
bell) to let you know when an alarm is active on the UPS. This feature is useful if the UPS is
located in a remote area where the UPS alarm horn may not be heard immediately.
CAUTION
Contacts should not be operated in excess of 30 Vac or 42.4V peak AC or DC @ 1A maximum.
6−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using Features and Options
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−3
Using Features and Options
The RMP contains a local horn and the following backlit status indicators:
SYSTEM NORMAL
The UPS is energized (either with utility power or battery
backup) and is supplying conditioned power to the critical
load.
NO REDUNDANCY
This indicator applies only to parallel systems when one
cabinet is not functioning. This feature is not available on this
system.
ON GENERATOR
This alarm means that the UPS input and bypass are being sup-
plied by the power from the generator, instead of from the utility
power.
ON BYPASS
The bypass source is supplying the critical load. Usually this
means that the UPS is not energized. The load is not protected
in Bypass mode, and a horn sounds after 30 seconds.
UPS ALARM
The UPS system is issuing an alarm. Conditions that affect the
current UPS mode are indicated by the indicators and horn on
the UPS.
ON BATTERY
The UPS battery backup is supplying the critical load. The
utility power is either interrupted or out of specification. The
SYSTEM NORMAL indicator is also lit.
BYPASS UNAVAILABLE
The UPS system is in Normal mode, but a bypass source is not
within specification. A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in
Battery mode and the DC voltage is approaching its low limit.
This indicator is accompanied by a horn.
6−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using Features and Options
The UPS battery cabinets can be paralleled. With this capability, you can increase your
battery backup time by adding battery cabinets to your UPS system. The Powerware 9315
can support up to four battery cabinets.
The breaker switch should be set to ON for normal UPS operation when DC power is
available at the UPS. When service personnel are performing maintenance on the UPS or
battery cabinet, the switch should be set to OFF.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−5
Using Features and Options
UPS AVAILABLE Pins 1 and 12 Contacts are closed when the UPS is operating in
Normal mode or ready to supply the load.
UPS OFF LINE Pins 3 and 13 Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in
Normal mode.
BATTERY WEAK Pins 5 and 14 Contacts are closed when approximately two
minutes of battery time is remaining, before the
critical load is lost.
UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected.
6−6 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Using Features and Options
TB2
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−7
Using Features and Options
6−8 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 7 Communication
This chapter describes the communication features of the Powerware 9315 UPS and
provides information about connecting hardware and using Terminal mode.
The X−Slot communication bay, used for optional X−Slot cards, allows the UPS to
communicate in a variety of networking environments and with different types of devices.
NOTE The X−Slot communication bay is connected internally to the DB−25 port by
default; the DB−25 is disabled for other uses. Contact your Eaton service representative
to purchase, install, and set up an external modem or an internal X−Slot Modem Card.
Figure 7-1 shows the location of these items inside the UPS.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−1
Communication
ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓ
ÓÓÓ
Port 2 (DB−25F)
RS−232 Connection
(disabled by default)
Figure 7-1. Location of Communication Bays on the UPS (Powerware 9315 300)
7−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
A Modem Card − provides out−of−band" remote notification and monitoring using modem
communication directly to cell phones and pagers.
A Multi−Server Card − has six serial communication ports that can communicate
simultaneously with other computers using LanSafe Power Management Software
(provided on the Powerware Software Suite CD).
A Single−Port Card − connects to the Powerware Expansion Chassis to enable multiple
communication options.
LAN and telephone drops, for use with X−Slot connectivity cards, must be provided by
facility planners or the customer.
For installation and setup of an X−Slot card, please contact Powerware (see page 1−2). Refer
to the manual supplied with the X−Slot card for user instructions.
LanSafe software uses an RS−232 serial link to communicate with the UPS, and it provides
you with up−to−date graphics of UPS power and system data and power flow. It also gives
you a complete record of critical power events, and it notifies you of important UPS or
power information. With custom views for monitoring status and metering information,
various user groups can select the most useful view for their specific needs.
The cables you use for connection depend on the equipment you are connecting to the
UPS. Cables should be no longer than 16m (50 ft). The connectors for Port 1 and Port 2 on
the Communication Panel in the UPS are female, so the cables should be male. Figure 7-3
shows the pin assignments for Port 1, and Table 7-1 describes them. Figure 7-4 shows the
pin assignments for Port 2, and Table 7-2 describes them.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−3
Communication
+24V 1
6 NOT USED
RS-232 TXD
2 485+
RS-232 RXD 7
3 485–
NOT USED 8
4 RETURN
RETURN 9
5
NOTE The X−Slot communication bay is connected internally to the DB−25 port by
default; the DB−25 is disabled for other uses. Contact your Eaton service representative
to purchase, install, and set up an external modem or an internal X−Slot Modem Card.
GND 1
14 NOT USED
RS-232 TXD
2
15 NOT USED
RS-232 RXD 3
16 NOT USED
RS-232 RTS
4 NOT USED
RS-232 CTS 17
5 NOT USED
RS-232 DSR 18
6 NOT USED
RTN 19
7 RS-232 DTR
+12V 20
8 NOT USED
NOT USED 21
9 –12V
NOT USED 22
10 NOT USED
NOT USED 23
11 NOT USED
NOT USED 24
12 NOT USED
NOT USED 25
13
7−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−5
Communication
Select Port 1 from the Setup menu to display one of the Setup Port screens. The screens
for Port 1 and Port 2 are identical, and allow you to specify settings for the two serial
communication ports. Figure 7-5 shows the Setup Serial Port 1 screen.
NOTE You should configure only Port 1 unless field service has performed a wiring
change for Port 2.
Battery
Percent
100%
Setup Serial Port 1
Setup
Port 1
Port 2
Time
A small return arrow ( ) appears in the upper right corner of the Setup Port screen. This
arrow is a reminder that you can press the button on the Monitor Panel to toggle the
buttons between the menu box and the information area.
If the scroll bar is in the menu box, press the button to toggle to the information
area. The first setting (Mode) is highlighted. Press the or button to move the highlight
to the setting you want to change. To scroll through the available options for that setting,
press the or button.
To save the settings upon exit from this screen, be sure the Save field is set to YES.
7−6 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
Table 7-3 shows which options are available for each port. The sections that follow
describe the configuration settings you can change.
7.5.1 Mode
The operational mode of the port. Each communication port operates in one of the
following modes:
Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be
operating in different modes. The modes are described later in this chapter.
7.5.2 Rate
The baud rate of the equipment connected to this port. The baud rate determines the
speed of data transferred between the UPS and the connected equipment. For Remote
Monitor mode, the baud rate must be set to 300. All other modes should operate at the
highest baud rate available with the connected equipment. 300 baud is not recommended
for any mode except Remote Monitor.
You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19200.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−7
Communication
7.5.3 Data/Stop
The data size and stop bits of the equipment connected to this port. These settings
determine the number of bits transmitted per ASCII character. The data size and stop bits
you specify depend on the configuration of your equipment.
For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data
bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
7.5.4 Handshaking
This setting controls handshaking. You can select XON/XOFF or Disabled for this setting.
7.5.4.2 XON/XOFF
If handshaking is enabled, the UPS uses special characters (XON and XOFF) to handshake
with the host terminal. The XON character is defined to be ASCII value 11 hex, and the
XOFF character is defined to be ASCII value 13 hex. Upon receiving an XOFF command, the
UPS halts transmission until an XON command is received. In the same way, if the terminal
receives an XOFF command, the UPS expects the terminal to halt transmission until the
UPS sends an XON command.
7.5.5 Save
Set to YES to save any changes to configuration settings upon exit from the Setup screen.
Set to NO if you do not want to save any changes.
Each communication port on the UPS operates in one of five modes, which you select
when configuring the port using the Setup Port screen.
7−8 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
Symbol Description
MMM Month (3 letters)
DD Day (2 digits)
HH Hour (2 digits)
MM Minute (2 digits)
SS Second (2 digits)
hh Hundredths of Second (2 digits)
KYWD MESSAGE Keyword (ALARM, NOTICE, COMMAND, or STATUS)
:::: System Diagnostic Information
<CR> Carriage Return Character (ASCII 13)
<LF> Line Feed (ASCII 10)
An alarm message is prefixed by the word CLEAR" whenever an alarm is entered into the
Event History Log with a cleared status.
To use a key combination, hold down the Control key and press the letter key.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−9
Communication
The Event History Log lists up to 400 system events in chronological order with the most
recent event listed last. Figure 7-6 shows a sample Event History Log printout.
7−10 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
Bypass Battery
VAB VBC VCA V I
480 480 480 540 + 0
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−11
Communication
The Date/Time field is the date and time of the battery test.
The Volts field is a measured value of the battery voltage during the test. This field
displays 000.0 if the test did not run to completion.
The Health field is a relative measurement of the battery condition. This number can be
used to chart the condition of the batteries. If a sudden change of this number occurs
relative to the previous test results, it is an indication that the batteries may need
attention. This display is 0.00 if the test does not run to completion.
The Data field is a value to be used by your field service engineer to gain more information
about the battery tests.
If the battery test does not complete, the Volts and Health field reads zero and the UPS
Event History Log reports either Battery Test Failed, Battery Test Aborted (Load), or Battery
Test Aborted (Utility). If the test ran to completion, Battery Passed Test appears in the UPS
Event History Log.
7−12 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−13
Communication
Enable/Disable (Function)
Enabled Building Alarm Number(s)
1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
Where (Function) indicates the function the building alarm is being programmed for. The
line following the Enabled Building Alarm Number(s) label indicates which building alarms
are currently enabled for the function. (In this example, Building Alarms 1 and 4 are
enabled.) A building alarm can only be programmed for one special function at a time
from these menus. Enabling a building alarm for a special function automatically enables
the alarm. If you disable a special function, the building alarm is also disabled.
If you select entry 4 from this menu, the following menu appears:
7−14 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−15
Communication
The current unit name is displayed on the second line of the display and in the headers of
prints from Terminal mode. If a change is desired, the new unit name should be entered at
the prompt. The unit name is 45 characters maximum and includes spaces and any
punctuation. If the user wants to center the text portion of the name, the appropriate
number of leading spaces should be included when entered.
Change Password
Enter New Password:
Verify New Password:
7−16 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
If entry 4 is selected from the Battery Test Setup menu, you are prompted to enter Y" to
cancel all pending tests. This selection cancels only pending tests and does not stop a test
currently in progress.
If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test is scheduled,
the following menu is displayed:
If entry 5 is selected and there are no tests scheduled, the following text appears:
NOTE The UPS performs only one battery test in any 24−hour period.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−17
Communication
NOTE Low Battery Time should be no greater than 999. Press <ENTER> to return with
no change.
NOTE Calibration mode is for use by service personnel ONLY. To prevent inadvertent
modification, this mode can be accessed only by trained personnel.
7−18 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Communication
For connection and setup of a modem or to enable Remote Notify features within the UPS,
please contact Powerware (see page 1−2).
Remote Notification provides the UPS with the capability to use a standard off-the-shelf PC
modem as a telephone interface. The features provided by this option are as follows:
A Automatic answering (user−configurable) for access to the Terminal mode of the UPS.
A Remote and local ability to clear Call Out alarms and events.
Remote Notification provides the user with the option of receiving alarms and notices at a
remote location. Using the Terminal mode, the user calls the UPS to perform basic
monitoring. In the event of a UPS alarm or notice, the user is notified at the remote
location. The UPS calls through the modem to the user’s computer or pager and leaves a
message.
Remote Notification is an extension of the Terminal mode with the additional support
algorithms necessary to control an external modem. Connection to the UPS is made when
a user calls the UPS on the phone. The user has exactly the same capabilities as if using a
terminal connected directly to the UPS RS−232 port.
Remote Notification differs from the basic Terminal mode with the addition the following
functions:
A Call Answer – The Call Answer function allows the user to call into the UPS from a
remote location and enter Terminal mode.
A Call Out – The Call Out function allows the UPS to be configured to call either a remote
computer or numeric paging service over the phone line. Call Out allows the UPS to call
a remote computer and leave a one-line descriptive message of the alarm or notice
condition. Numeric paging support allows the UPS to call a paging service and send
numeric messages.
A Housekeeping – The Housekeeping function maintains the link between the UPS and
modem.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−19
Communication
7−20 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 8 Maintaining the UPS System
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the battery
installation and maintenance. Risk of electrical shock.
The components inside the UPS cabinet are secured to a sturdy metal frame that is
supported by the UPS magnetics. This design allows authorized service personnel to
remove repairable components with very little disassembly. All repairable parts and
assemblies are located in the front of the UPS, allowing all routine maintenance and
servicing to be performed with front panel access.
You must schedule periodic performance checks of your UPS to keep it running properly.
Regular routine checks of operation and system parameters will enable your UPS system to
function efficiently for many trouble-free years.
WARNING
A Batteries can present a risk of electrical shock or burn from high short−circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
A ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
A Replace batteries with the same number and type of batteries as originally installed in the
UPS.
A LETHAL VOLTAGE PRESENT. This UPS should not be operated with the cabinet doors open
or protective panels removed. Do not make any assumptions about the electrical state of
any cabinet in the UPS system.
A If the battery cabinet requiring service was not provided by the UPS manufacturer, refer to
the battery cabinet manufacturer’s operating manual for instructions on battery cabinet
installation and maintenance, or contact your Eaton service representative.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 8−1
Maintaining the UPS System
WARNING
A Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal
of batteries is required. Refer to your local codes for disposal requirements.
A Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed of properly. For more information, contact your local
recycling or hazardous waste center.
AVERTISSEMENT!
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre les
précautions qui s’imposent.
A Pour le remplacement, utiliser le même nombre et modéle des batteries.
A L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.
A Check the area surrounding the UPS. Ensure the area is not cluttered, allowing free
access to the UPS.
A Ensure the air intakes (vents on the front doors) and exhaust opening (on top of the
UPS cabinet) are not blocked.
A Ensure the operating environment is within the parameters specified in Chapter 9,
Product Specifications."
A Ensure the UPS is in Normal mode (Normal status indicator is lit). If an alarm lamp is lit
or the Normal status indicator is not lit, contact your Eaton service representative.
A Ensure all status indicator lamps are operative. (Press the and buttons
simultaneously to test the lamps.)
A Monitor system parameters as described in Chapter 5, Using the Monitor Panel."
A Check the air filters (located behind the front doors) and replace them as necessary (the
filter size is 16″ 20″ 1″).
A Record the results of your checks and any corrective actions in a suitable log.
8−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Maintaining the UPS System
BATTERY maintenance − Contact your nearest field service office for battery
maintenance. Battery replacement and maintenance should be performed only by
authorized service personnel.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 8−3
Maintaining the UPS System
8−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 9 Product Specifications
The UPS systems are housed in freestanding, double-front cabinets with safety shields
behind the doors. The UPS systems are available in 50/60 Hz with various output power
ratings. Smaller models within a system may be upgraded in the field to larger models:
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 9−1
Product Specifications
9−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Product Specifications
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 9−3
Product Specifications
9−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 10 Responding to System Events
When the UPS system is running in Normal mode, it continually monitors itself and the
incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you
know exactly what event caused the change from Normal mode. System events can be
indicated by horns, lights on the UPS, or both.
Select Active from the Events menu on the LCD screen to look at the Active System Events
screen. This screen shows any currently active alarms, notices, or commands.
A When the UPS detects an alarm that requires your attention, the horn beeps at
½-second intervals.
A When a notice occurs, the horn beeps at 2-second intervals.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 10−1
Responding to System Events
10−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Responding to System Events
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 10−3
Responding to System Events
10−4 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Chapter 11 Using the LOAD OFF Button
Load Off is initiated by the covered, red LOAD OFF button on the Monitor Panel. This
button is protected by a clear plastic shield to prevent accidental activation. In an
emergency, you can press this button to instantaneously open the input breaker and
interrupt UPS output. The UPS is cut off from utility power, and the critical load is
de-energized. All power to the critical load is lost. The UPS (including Bypass) remains
locked off until you reset the LOAD OFF button.
WARNING
All power to the critical load is lost when you press this button. You should use this feature
only in an emergency or when you want to de-energize the critical load.
To restart the UPS after pressing the LOAD OFF button, follow the procedure Resetting
the UPS System after Load Off" on page 11−2 before starting the UPS.
NOTE The Remote Emergency Load Off option functions the same way as the LOAD
OFF button on the Monitor Panel.
The breaker and contactors open (you can hear them opening). The CB1 switch
trips, and the Load Off PUSH TO RESET button on the UPS Control Panel pops out.
The UPS system shuts down.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is
opened.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 11−1
Using the LOAD OFF Button
The Load Off PUSH TO RESET button is a small white button on the UPS Control Panel. The
PUSH TO RESET button pops out and the CB1 switch trips when the LOAD OFF button on
the Monitor Panel is activated.
1. Press the Load Off PUSH TO RESET button until it clicks in and remains recessed.
2. Move the CB1 switch from the center (tripped) position to OFF. The switch should
be difficult to move from the TRIPPED position.
3. The UPS system is now reset. To restart the UPS system, follow the procedure in
Chapter 4, Starting and Stopping the UPS."
11−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
Warranty
LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE® UPS PRODUCTS
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation (Eaton").
LIMITED WARRANTY: This limited warranty (this Warranty") applies only to the original end−user (the End−User") of the Powerware
Three−Phase UPS Products (the Product") and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by
Eaton for resale to an End−User.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in the fifty (50) United States
and the District of Columbia is twelve (12) months from the date of Product start−up or eighteen (18) months from the date of Product
shipment, whichever occurs first, for parts coverage and 90 days from the date of Product start−up for labor coverage. The period covered by this
Warranty for Product installed [and currently located] outside of the fifty (50) United States and the District of Columbia is twelve (12) months
from the date of Product start−up or eighteen (18) months from the date of Product shipment, whichever occurs first, for parts coverage.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Powerware three−phase UPS electronics, Eaton−built
accessories, and Powerware−built battery cabinets (individually and collectively, the "Warranted Items") are free from defects in material and
workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton’s sole obligation
will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton. The
Warranted Item will be repaired or replaced onsite at the End−User’s location or such other location as determined by Eaton. Any parts that are
replaced may be new or reconditioned. All parts replaced by Eaton shall become the property of Eaton.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to
properly store the Product before installation, including the "trickle charge" of batteries no later than the date indicated on the packaging; (b)
shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, fire, flood, lightning, vandalism, acts of God, Customer’s
neglect, abuse, misuse, misapplication, incorrect installation; (d) repair or alteration not authorized in writing by Eaton personnel or performed by
an authorized Eaton Customer Service Engineer or Agent; or (e) improper testing, operation, maintenance, adjustment, or any modification of
any kind not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent.
This Warranty is not valid: (a) unless an authorized Eaton Customer Service Engineer (in the USA) or Agent (outside of the USA) performs startup
and commissioning of the Product; (b) if the Product is moved to a new location by someone other than an authorized Eaton Customer Service
Engineer (in the USA) or Agent (outside of the USA); or (c) if the Product’s serial numbers have been removed or are illegible. Any Warranted
Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms
thereof. Labor warranty is not provided for Product located outside of the fifty (50) United States or the District of Columbia. Any equipment,
parts, or materials included in the Product and not manufactured by Eaton are warranted solely by the manufacturer of such
equipment, parts, or materials and are not included as part of this Warranty. Batteries are not warranted by Eaton.
THIS WARRANTY IS THE END−USER’S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER EXPRESSED OR
IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY
PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED).
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special, or consequential damages of any kind or type
whatsoever, or based on any claim or cause of action, however denominated. Eaton shall not be responsible for failure to provide service or parts
due to causes beyond Eaton’s reasonable control. In no case will Eaton’s liability under this Warranty exceed the replacement value of the
Warranted Items.
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product in a normal way, follow the
Product’s installation, operation and maintenance manual, and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Eaton’s obligations under this Warranty are expressly conditioned upon receipt by Eaton of all payments due to it
(including interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance
with the contract terms under which the Product is sold, Eaton shall have no obligation under this Warranty. Also during such time, the period of
this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not expressly provided for by the
terms of this Warranty, including without limitation site calls involving an inspection that determines no corrective maintenance is required. Any
costs for replacement equipment, installation, materials, freight charges, travel expenses, or labor of Eaton representatives outside the terms of
this Warranty will be borne by the End−User.
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800−843−9433. Outside of the USA, call your
local Eaton sales or service representative, or call the Eaton Customer Reliability Center in the USA at 919−870−3028. For comments or questions
about this Limited Factory Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com W−1
Warranty
W−2 EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
*164201036G*
164201036 G