CE 511 STRUCTURAL DESIGN 2 (STEEL AND TIMBER)

DESIGN DATA: 2. Weight of Pu


Span of Truss = 9 meter
Rise of Truss = 1.4 meter
Bay Length = 4 meter
Spacing of Purlins = 1.125 meter
Horizontal roof angle, degrees = 17.28149837 Ө

LOAD CARRIED BY THE TRUSS


A. WIND LOAD
B. DEAD LOAD AND LIVE LOAD

A. WIND LOAD

Since the windward side is more critical for


wind loading, the combination of dead load,
roof live load and windward wind load
provides the governing design condition for
purlins.

use:
Design Wind Pressure, p = 415 Pa
Ww = p x Sp

Ww = 466.88 N/m

B. DEAD LOAD AND LIVE LOAD LOADS NORMAL TO TH


WD =
1. Weight of Roofing, Wr WD =
2. Weight of Purlins, Wp
WN =
1. Weight of Roofing, Wr: WN =
Using Milano LongSpan Steel Brick Excluding Gutter and Ridge Roll
PR = 3.30 Pa LOADS TANGENT TO TH
Additional Uniform Live Load(Table 205-3, NSCP '10). WT =
0 1000 Pa WT =
Total Weight = 3.30 Pa + 1000 Pa
= 1003.30 Pa

Wr = Total Weight x Sp

Wr = 1128.71 N/m
DESIGN OF
PURLINS
2. Weight of Purlins, Wp: MOMENTS NORMAL AND TANGENT TO THE PU
try C3 x 4.1 MN = WNL2/12
Properties of the section: MN = 2136.20 N-m
W 6.14 kg/m
d 76.20 mm CHECK FOR COMPACTNESS OF THE SECTI
A 781.00 mm2 flange:
bf 35.80 mm bf/2tf ≤ 170/√Fy
tf 6.90 mm web:
tw 4.30 mm d/tw ≤ 1680/√Fy
Sx 18.14 x10³mm³
Sy 3.36 x10³mm³ bf/2tf = 2.59 >
Ix 691.00 x10³mm4 d/tw = 17.72 >
Iy 83.00 x10³mm4 Therefore, the section is compact.

Wp = (6.14kg/m) (9.81N/kg) CHECK AGAINST FLEXURE:


Wp = 60.23 N/m fa ≤
solve for Lc:
200bf/ √Fy = 454.66 mm
137900/ (d/Af)Fy = 1802.56 mm
use smaller value:
Lc = 454.66 mm
Lb = 400.00 mm (Assumed Brace Length)
Since the member is compact section and Lc > Lb, use Fa = 0.66Fy
fa = [ (MN/Sx)+(MT/Sy) ]
fa = 257.92 MPa

LOADS NORMAL TO THE ROOF SURFACE: Fa = 0.66 Fy


Wp + Wr Fa = 163.68 MPa
1188.95 N/m
fa = 257.92
Ww + WD cos Ө Therefore, failure.
1602.15 N/m

LOADS TANGENT TO THE ROOF SURFACE:


WD sin Ө
353.20 N/m
OF
NS
RMAL AND TANGENT TO THE PURLINS: CHECK ADEQUACY OF SECTION USING INTERACTION EQUATI
MT = WTL2/12 faN/Fax + faT/Fay ≤ 1.0
MT = 470.93 N-m
faN = MN/Sx Fax =
R COMPACTNESS OF THE SECTION: faN = 117.76 MPa Fax =

A36:
Fy = 248 MPa faT = MT/Sy Fay =
E= 2 x105 MPa faT = 140.16 MPa Fay =

faN/Fax + faT/Fay = 1.47


170/√Fy = 10.80
1680/√Fy = 106.68 faN/Fax + faT/Fay = 1.47 >

erefore, the section is compact. Therefore, purlins is not adequate.

ECK AGAINST FLEXURE: CHECK AGAINST DEFLECTION:


Fa
Ψmax actual = WL4/384EI
Ψallow = L/240

DEFLECTION ALONG NORMAL


ΨN = WNL4/384EIx
00.00 mm (Assumed Brace Length) ΨN = 7.73 mm
nd Lc > Lb, use Fa = 0.66Fy
MN/Sx)+(MT/Sy) ] DEFLECTION ALONG TANGENTIAL
ΨT = WTL4/384EIy
ΨT = 14.18 mm

Ψmax actual = √ (ΨN) 2+ (ΨT) 2


Ψmax actual = 16.15 mm
> Fa = 163.68
Therefore, failure. Ψmax actual = 16.15 <
Therefore the section is safe.

CONCLUSION:

use C3 x 4.1 as purlins for both main trusses and hip


CTION USING INTERACTION EQUATION:

0.66 Fy , Along strong axis


163.68 MPa

0.75 Fy , Along weak axis


186.00 MPa

1.0

re, purlins is not adequate.

AGAINST DEFLECTION:

Ψallow = L/240
Ψallow = 16.67 mm

Ψallow = 16.67 mm
efore the section is safe.

lins for both main trusses and hip trusses.


Designation Weight(W) Area(A) Depth(d) Web Thickness(tw) Flange x
kg/m mm2 mm m bf t mm
C3 x 4.1 6.14 781 76.2 4.3 35.8 6.9 11.07
C3 X 5 7.46 948 76.2 6.6 38 6.9 11.13
C3 X 6 8.93 1135 76.2 9 40.5 6.9 11.56
C4 X 5.4 8.07 1,026 101.6 4.7 40.2 7.5 11.61
C4 X 7.25 10.81 1,307 101.6 8.2 43.7 7.5 11.66
C5 X 6.7 10 1,207 127 4.8 44.5 8.1 12.29
C5 X 9 13.4 1,703 127 8.3 47.9 8.1 12.14
Axis-X Axis-Y
Ix Sx rx Iy Sy ry tw
x103 mm4 x103 mm3 mm x103 mm4 x103 mm3 mm mm
691 18.14 29.74 83 3.36 10.31 6.14
770 20.21 28.5 104 3.87 10.47 6.60
862 22.62 27.56 125 4.32 10.49 9.00
1,602 31.54 39.51 133 4.65 11.39 4.70
1,911 37.62 37.29 179 5.59 11.41 8.20
3,118 49.1 49.53 200 6.21 12.54 4.80
3,704 58.33 46.64 262 7.33 12.4 8.30