CHAPTER

PLC COMMUNICATIONS
6
In This Chapter...
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2
DirectLOGIC PLCs Password Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .6–5
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .6–6
AutomationDirect PLCs RS-232C Serial: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–7
AutomationDirect PLCs RS-422A/RS-485A: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–10
Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON: . . . . . . . . . . .6–16
Direct LOGIC Universal Converter, p/n F2-UNICON: . . . . . . . . . . . . . . . . . . . . . . .6–17
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples . . . . . . . . . . . . . . . . . . . .6–18
Allen-Bradley: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–22
GE: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
GE VersaMax Micro: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
Mitsubishi: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
Omron: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–29
Modicon ModBus RS-232: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Modicon Micro Series: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Modicon ModBus with RJ45: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Siemens: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–31
Chapter 6: PLC Communications

Introduction
1 The C-more family of touch panels is capable of communicating with a wide variety of
Programmable Logic Controllers. C-more is capable of communicating over RS232, RS422 and
2 RS485 serial networks as well as Ethernet networks. It communicates with all
AutomationDirect PLC's utilizing various protocols. C-more also communicates with other
brands of PLCs by their different protocols. The table on the next page lists all of the various
3 PLCs and protocols that can be configured. The page after the protocol table lists the various
serial communication cables that are available to purchase. The rest of this chapter is devoted to
4 show the pin to pin connections of all the available cables plus wiring diagrams that the user can
refer to in order to construct their own cables, along with wiring diagrams of cables that are not
available for purchase. To simplify RS422/RS485 wiring schemes, we have included wiring
5 diagrams showing connections for available terminal connectors such as our ZIPLink
Communication Adapter Module, p/n ZL-CMA15, used for example with our DL-06 and D2-
6 260 PLCs and C-more D-Sub 15-pin to Terminal Block Adapter p/n EA-COMCON-3.
If you have difficulty determining whether the particular PLC and/or protocol you are using
7 will work with the C-more series of touch panels, please contact our technical support group at
770-844-4200

8 DirectLOGIC PLCs Password Protection


9 NOTE: Many DirectLogic PLCs support multi-level password protection of the ladder program. This allows
password protection while not locking the communication port to an operator interface. The multilevel
10 password can be invoked by creating a password with an upper case "A" followed by seven numeric
characters (e.g. A1234567). Please refer to the specific PLC user manual for further details.

11
C-more
Touch Panel
12
DL-06 PLC
13
14
C-more to
A Direct LOGIC
VGA 15-pin port
Port 2 serial cable
B p/n EA-2CBL-1
C
D

6–2 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

PLC Protocol & Cables

Model
Compatibility Table
Protocols
1
Productivity3000
P3000 Serial
P3000 Ethernet
2
CLICK Modbus (CLICK)
K-Sequence 3
all Direct NET
DL05/DL06

H0-ECOM/H0-ECOM100
Modbus (Koyo addressing)
Direct LOGIC Ethernet
4
DL105 all
D2-230
K-Sequence
K-Sequence
5
K-Sequence
D2-240
Direct NET 6
K-Sequence
DL205 D2-250/D2-250-1/D2-260 Direct NET
Modbus (Koyo addressing)
7
Direct NET
D2-240/D2-250-1/D2-260
Using DCM Modbus (Koyo addressing)
8
H2-ECOM/H2-ECOM100 Direct LOGIC Ethernet
D3-330/330P (Requires the use of a Data Communications Unit) Direct NET 9
D3-340 Direct NET
AutomationDirect
DL305 D3-350
K-Sequence
Direct NET
10
Modbus (Koyo addressing)

D3-350 DCM
Direct NET 11
Modbus (Koyo addressing)

D4-430
K-Sequence 12
Direct NET

D4-440
K-Sequence
Direct NET
13
K-Sequence
DL405
D4-450 Direct NET 14
Modbus (Koyo addressing)

All with DCM


Direct NET A
Modbus (Koyo addressing)
H4-ECOM/H4-ECOM100
H2-WinPLC (Think & Do) Live V5.2 or later and Studio any version
Direct LOGIC Ethernet
Think & Do Modbus RTU (serial port)
B
H2-WinPLC (Think & Do) Live V5.5.1 or later and Studio V7.2.1 or later Think & Do Modbus TCP/IP (Ethernet port)

GS Drives
GS Drives Serial C
GS Drives TCP/IP (GS-EDRV)
SOLO Temperature Controllers SOLO Temperature Controller D
PLC Compatibility Table continued on the next page.

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–3


Chapter 6: PLC Communications

PLC Protocol & Cables (cont’d)


1 Compatibility Table (cont’d)
Model Protocols
2 MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-01/02/03, PLC5 DH485/AIC/AIC+
MicroLogix 1000, 1100, 1200, 1400 and 1500
3 SLC 5-03/04/05 DF1 Half Duplex; DF1 Full Duplex
ControlLogix™, CompactLogix™, FlexLogix™
4 Allen-Bradley
PLC-5 DF1 Full Duplex
ControlLogix, CompactLogix, FlexLogix - Tag Based DF1 Half Duplex; DF1 Full Duplex
5 ControlLogix, CompactLogix, FlexLogix - Generic I/O Messaging EtherNet/IP Server
ControlLogix, CompactLogix, FlexLogix - Tag Based
6 MicroLogix 1100, 1400 and SLC 5/05, via native Ethernet port EtherNet/IP Client
MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-03/04/05, all via ENI adapter
7 GE 90/30, 90/70. Micro 90, VersaMax Micro SNPX
FX Series FX Direct

8 Mitsubishi
Q02, Q02H, Q06H, Q12H, Q25H Q CPU
Q, QnA Serial QnA Serial

9 Q, Qna Ethernet QnA Ethernet


984 CPU, Quantum 113 CPU, AEG Modicon Micro Series 110 CPU: 311-xx, 411-xx, Modbus RTU
512-xx, 612-xx
10 Modicon
Other devices using Modicon Modbus addressing
Modbus RTU
Modbus TCP/IP

11 C200 Adapter, C500 Host Link


Omron CJ1/CS1 Serial
FINS
12 CJ1/CS1 Ethernet
S7-200 CPU, RS-485 Serial PPI
Siemens
13 S7-200 CPU, S7-300 CPU, S7-1200 CPU; Ethernet Ethernet ISO over TCP

14
A
B
C
D

6–4 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams


Purchased Cable
Description
Cable
Part Number
1
AutomationDirect Productivity Series, CLICK,
Direct LOGIC PLC RJ-12 port, DL05, DL06, DL105, EA-2CBL 2
DL205, D3-350, D4-450 & H2-WINPLC (RS-232C)
Direct LOGIC (VGA Style) 15-pin port
DL06, D2-250 (250-1), D2-260 EA-2CBL-1 3
(RS-232C)
Direct LOGIC PLC RJ-11 port, D3-340
(RS-232C) EA-3CBL Part No. EA-2CBL 4
Direct LOGIC DL405 PLC 15-pin D-sub
port, DL405 (RS-232C) EA-4CBL-1
5
Direct LOGIC PLC 25-pin D-sub port,
DL405, D3-350, DL305 DCU and EA-4CBL-2
all DCM’s (RS-232C) 6
Allen-Bradley MicroLogix 1000, 1100,
EA-MLOGIX-CBL
1200, 1400, 1500 (RS-232C)
Allen-Bradley SLC 5-03/04/05,
7
ControlLogix, CompactLogix, FlexLogix, MicroLogix EA-SLC-232-CBL
DF1 port (RS-232C)
Allen-Bradley PLC-5 DF1 port
8
(RS-232C) EA-PLC5-232-CBL Part No. EA-2CBL-1

Allen-Bradley MicroLogix, SLC 5-01/02/03, PLC5


EA-DH485-CBL
9
DH485 port (RS-232C)
GE 90/30, 90/70, Micro 90, VersaMax Micro
15-pin D-sub port (RS-422A) EA-90-30-CBL 10
MITSUBISHI FX Series 25-pin port
(RS-422A) EA-MITSU-CBL 11
MITSUBISHI FX Series 8-pin mini-DIN
EA-MITSU-CBL-1
(RS-422A)
OMRON Host Link
12
C200 Adapter, C500 EA-OMRON-CBL
(RS-232C) Part No. EA-3CBL
13
NOTE 1: The above list of pre-made communications cables may be purchased. See further in this chapter for
14
wiring diagrams of additonal user constructed cables. This chapter also includes wiring diagrams for the pre-
made cables. A
NOTE 2: EZTouch serial PLC communication cables are compatible with C-more touch panels. B
8 1 C
C-more PLC Serial D-Sub 15-pin female
Communications Port on rear of touch panel
15 9
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–5


Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams


1
2
3
4 Part No. EA-4CBL-1 Part No. EA-4CBL-1

5
6
7
Part No. EA-MLOGIX-CBL Part No. EA-SLC-232-CBL
8
9
10
11 Part No. EA-PLC5-232-CBL Part No. EA-DH485-CBL

12
13
14
A Part No. EA-90-30-CBL Part No. EA-MITSU-CBL

B
C
D
Part No. EA-MITSU-CBL-1 Part No. EA-OMRON-CBL

6–6 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams (cont’d)


The following series of wiring diagrams show the connectors and wiring details for the 1
communication cables that are used between the C-more touch panels and various PLC
controllers. Part numbers are included with the pre-made cables that can be purchased from
AutomationDirect. The information presented will allow the user to construct their own cables
2
if so desired.
AutomationDirect PLCs RS-232C Serial: EA-2CBL 3
Productivity Series, Do-more, CLICK and Direct Logic PLC RJ12 port:
To PLC DL05, DL06, DL105, DL205, DL350, DL450, H2-WINPLC
To C-more Touch
Panel PLC Port 4
RJ12 Port
RS-232C (p/n EA-2CBL)
5
RJ12 6-pin 15-pin
Phone Plug D-sub
1 = Sig GND
(6P6C) Wiring Diagram 8 = do not use
7 = do not use
(male) 15 = do not use
14 = do not use
6
2 = do not use TXD 4 3 RXD 6 = do not use 15 13 = do not use
3 = RXD 5 = Logic GND 12 = do not use
4 = TXD
5 = do not use 123456
RXD
GND
3
1
2
5
TXD
4 = do not use
3 = RXD (232C)
11 = do not use
10 = do not use
7
6 = do not use 1 2 = TXD (232C) 9 = do not use
shield 1
1 = Frame GND
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
8
EA-2CBL-1 9
Direct Logic PLC (VGA style) 15-pin HD port:
To PLC
15-Pin HD Port
D2-250, D2-250-1, D2-260, DL06
To C-more Touch Panel
Serial Port2 10
RS-232C (p/n EA-2CBL-1)
11
15-pin Wiring Diagram 15-pin
HD D-sub
8 = do not use
7 = Sig GND
(male) 15 = do not use
14 = do not use
TXD 2
RXD 3
3 RXD
2 TXD
8 = do not use
7 = do not use
D-sub
(male) 15 = do not use 12
15 15 14 = do not use
6 = do not use 13 = do not use GND 7 5 6 = donot use 13 = do not use
5 = CTS
4 = RTS
3 = RXD 1 6
12 = do not use
11 = do not use RTS
10 = do not use CTS
4
5
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
13
2 = TXD 9 = do not use 2 = TXD (232C) 1 9 = do not use
1 = +5 VDC - N/C
HD = High Density shield
1 1 = Frame GND
14
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–7


Chapter 6: PLC Communications

AutomationDirect PLCs RS-232C Serial (cont’d):


1 EA-3CBL
Direct Logic PLC RJ11 port: D3-340 To C-more Touch
2 To PLC
RJ11 Port
RS-232C (p/n EA-3CBL) Panel PLC Port

3 RJ11 4-pin 15-pin


Phone Plug D-sub
(4P4C) Wiring Diagram 8 = do not use (male) 15 = do not use
4 1 = RXD TXD 2 3 RXD
7 = do not use
6 = do not use
14 = do not use
15 13 = do not use
2 = TXD 1 2 5 = Logic GND 12 = do not use
RXD TXD
3 = do not use 4 = do not use 11 = do not use
5 4 = Sig ground 1234
GND 4
shield
5
1
3 = RXD (232C)
2 = TXD (232C) 1
10 = do not use
9 = do not use
1 = Frame GND

6 Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

7
8
9
10
11
12
13
14
A
B
C
D

6–8 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

AutomationDirect PLCs RS-232C Serial (cont’d):


EA-4CBL-1 1
To PLC Direct Logic PLC 15-pin D-sub port: DL405, To C-more Touch
15-Pin Port
RS-232C (p/n EA-4CBL-1) Panel PLC Port
2
Wiring Diagram 3
TXD 2 3 RXD
15-pin 15-pin
D-sub
8 = YOM Sense (male) 15 = Logic GND
RXD
online
3
4
2
5
TXD
D-sub
8 = do not used (male) 15 = do not use
4
7 = CTS 14 = Logic GND 7 = do not used 14 = do not use
6 = do not use
15
13 = Logic GND GND 13 15
6 = do not used 13 = do not use
5 = do not use
4 = Online
12 = do not use
11 = do not use
GND 14
GND 15
5 = Logic GND
4 = do not used
12 = do not use
11 = do not use
5
3 = RXD (232C) 10 = do not use 3 = RXD (232C) 10 = do not use
2 = TXD (232C) 9 = do not use YOP 1
2 = TXD (232C) 1 9 = do not use
1 = YOP Sense 1
CTS
7
8
1 = Frame GND 6
See PLC user manual YOM
for pin out details. 1
shield
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
7
8
EA-4CBL-2
To PLC
25-Pin Port
Direct Logic PLC 25-pin D-sub port: To C-more Touch
Panel PLC Port
9
DL405, D3-350, DL305 DCU, and all DCMs,
RS-232C (p/n EA-4CBL-2)
10
Wiring Diagram

13 = do not use
25-pin
D-sub
(male) 25 = do not use TXD 2 3 RXD 8 = do not use
15-pin
D-sub
11
12 = do not use (male) 15 = do not use
25 24 = do not use 3 2 7 = do not use 14 = do not use
23 = do not use RXD TXD
11 = do not use
10 = do not use
9 = do not use
22 = do not use GND 7
21 = do not use 4
5
6 = do not use
5 = Logic GND
15 13 = do not use
12 = do not use
12
8 = do not use 4 = do not use 11 = do not use
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
5
6 = do not use
5 = CTS
19 = do not use
18 = do not use
17 = do not use
CTS

1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use 13
4 = RTS shield
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
14
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–9


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A:


When using the RS-422A/RS-485A capabilities of the C-more PLC communications port, the
1 termination resistor is placed between the RXD– and RXD+ terminals on the PLC side of the
connection between the touch panel and PLC. The Termination Resistor value is based on the
2 characteristic impedance of the cable being used. To enable the built-in 120 Ohm Termination
Resistor, jumper pin 13 to pin 9 (RXD+) on the C-more 15-pin PLC communications port.
3 To PLC Direct LOGIC DL-06, D2-250, D2-250-1, D2-260 (all Port 2) To C-more Touch
Panel PLC Port
15-Pin Port RS-422A
4 User Constructed
Wiring Diagram
5 15-pin
HD D-sub
TXD+ 9
13
9
Term.
RD+
15-pin
D-sub
(male) 8 = do not use (male) 15 = do not use
TXD– 10 10 RD– 7 = do not use 14 = do not use
6 8 = do not use
7 = Sig GND 15
15 = CTS–
14 = CTS+
RXD+ 13
6
11
12
SD+
6 = do not use
5 = Logic GND
15
13 = Termination
12 = SD– (RS422)
6 = RXD– RXD– SD– 4 = do not use 11 = SD+ (RS422)
5 = do not use 13 = RXD+
7 5 3 = do not use 10 = RD– (RS422)
7 4 = do not use
3 = do not use 1 6
12 = RTS-
11 = RTS+
10 = TXD–
GND
RTS– 12
2 = do not use 1
1 = Frame GND
9 = RD+ (RS422)
2 = do not use CTS– 15
1 = do not use 9 = TXD+
8 RTS+
CTS+
11
14
shield 1
9 Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

10 To PLC Direct LOGIC D2-DCM*, D3-DCM* & D4-DCM* To C-more Touch


25-Pin Port
RS-422A Panel PLC Port

11 User Constructed
12 25-pin
D-sub 25 = do not use
Wiring Diagram 13 Term. 15-pin
D-sub
13 = CTS– (male)24 = do not use TXD+ 14 9 RD+
8 = do not use (male) 15 = do not use
12 = CTS+ 23 = do not use
13 11 = RTS–
10 = RTS+
25 22 = do not use TXD–
21 = do not use RXD+ 17
15 10 RD– 7 = do not use
11 SD+ 6 = do not use
15
14 = do not use
13 = Termination
9 = do not use 20 = do not use 5 = Logic GND 12 = SD– (RS422)
8 = do not use 16 12 SD– 4 = do not use
19 = do not use RXD– 11 = SD+ (RS422)
14 7=0V
6 = do not use
5 = do not use
18 = do not use
17 = RXD+
0V
RTS–
7
11
5 3 = do not use
2 = do not use 1
10 = RD– (RS422)
9 = RD+ (RS422)
(RS422) 1 = Frame GND
4 = do not use 13
16 = RXD–
A 3 = do not use
2 = do not use
1 = do not use 1
(RS422)
15 = TXD–
CTS–
RTS+ 10 * Note: The DCM modules must be set for:
CTS+ 12 Direct NET Slave, HEX mode.
(RS422)

B 14 = TXD+
(RS422)
shield 1

Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

C
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
D than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.

6–10 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


User Constructed 1
To PLC Direct LOGIC D4-430/D4-440/D4-450 Port 1 and D3-350 Port 2
25-Pin Port To C-more Touch
RS-422A Panel PLC Port
2
25-pin
D-sub
Wiring Diagram 13 Term. 15-pin
D-sub
3
13 = do not use (male) 25 = do not use TXD+ 14 9 RD+
12 = do not use 8 = do not use (male) 15 = do not use
11 = CTS+
10 = RXD–
24 = do not use
25 23 = CTS–
22 = do not use
TXD–
RXD+
16
9
10
11
RD– 7 = do not use
SD+
6 = do not use 15
14 = do not use
13 = Termination
4
(RS422) 21 = do not use 5 = Logic GND 12 = SD– (RS422)
9 = RXD+ RXD– 10 12 SD– 4 = do not use 11 = SD+ (RS422)
(RS422)
8 = do not use
7=0V
20 = do not use
19 = RTS+
18 = RTS–
0V 7
18
5 3 = do not use
2 = do not use 1
10 = RD– (RS422)
9 = RD+ (RS422)
5
RTS– 1 = Frame GND
6 = do not use 17 = do not use
23
5 = do not use
4 = do not use
3 = do not use 1
16 = TXD–
(RS422)
15 = do not use
CTS–
RTS+ 19 6
2 = do not use CTS+ 11
14 = TXD+
1 = do not use (RS422) shield 1
7
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

8
User Constructed
To PLC
25-Pin Port
Direct LOGIC D4-450 Port 3 To C-more Touch
9
RS-422A Panel PLC Port
RTS and CTS are not present on this port.
10
13 = TXD–
25-pin
D-sub 25 = RXD–
12
Wiring Diagram 13
9
Term. 15-pin
D-sub
11
(male) (RS422) TXD+ RD+
(RS422) 8 = do not use (male) 15 = do not use
12 = TXD+ 24 = RXD+ 13 10
(RS422)
11 = do not use
25 (RS422)
23 = do not use
TXD–
RXD+ 24 11
RD– 7 = do not use
SD+
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
12
10 = do not use 22 = do not use 25 12
9 = do not use RXD– SD– 4 = do not use 11 = SD+ (RS422)
21 = do not use
8 = do not use
7=0V
6 = do not use
20 = do not use
19 = do not use
0V 7
shield
5
1
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) 13
5 = do not use 18 = do not use
17 = do not use
4 = do not use
3 = do not use
2 = do not use 1
16 = do not use
15 = do not use
14
1 = do not use 14 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. A
B
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–11


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


1 User Constructed
To PLC Direct LOGIC DL-06, D2-260 (both Port 2) To C-more Touch
Panel PLC Port
15-Pin Port RS-485A
2
3 15-pin
HD D-sub
RXD+ 13
Wiring Diagram 13
9
Term.
RD+
15-pin
D-sub
(male)
(male) 8 = do not use 15 = do not use
TXD+ 9 11 SD+ 7 = do not use 14 = do not use
4 8 = do not use
7 = Sig GND 15
15 = CTS–
14 = CTS+
TXD– 10
6
10
12
RD–
6 = do not use
5 = Logic GND
15
13 = Termination
12 = SD– (RS485)
6 = RXD– RXD– SD– 4 = do not use 11 = SD+ (RS485)
5 = do not use 13 = RXD+
7 5 3 = do not use
5 4 = do not use
3 = do not use 1 6
12 = RTS-
11 = RTS+
GND
RTS– 12
2 = do not use 1
1 = Frame GND
10 = RD– (RS485)
9 = RD+ (RS485)
2 = do not use 10 = TXD– 15
9 = TXD+ CTS–
1 = do not use
6 RTS+
CTS+
11
14
shield 1
7 Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.

8
NOTE: The RS-485 wiring diagram shown above is not for multi-drop networks involving connecting more
9 than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.

10
11
12
13
14
A
B
C
D

6–12 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-485A – PLC D2-260 or DL06 only – Port 2
1
Terminal Block Adapter
RS-232 RXD
RS-232 TXD Wiring Diagram
plugs into C-more 15-pin
PLC Serial Comm. Port 2
TERMINATE

ZL-CMA15L
+5V
SIGNAL GND GND 3
RS-422/485 RX– RD–

RS422/485
RXD

TXD
232
RS-422/485 TX–
RS-422/485 RX+
SD–
SD+
4
TX+
RX+

TXD
RXD
+5V
TX-
RX-

RS-422/485 TX+ RD+


SG

shield
See ZL-CMA15L specifications on
TERM EA-COMCON-3 5
ZL-CMA15L termination resistor jumper.

Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. 6
7
Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-422A – PLC D2-250 (-1), D2-260 or DL06 – Port 2 8
Terminal Block Adapter
plugs into C-more 15-pin
RS-232 RXD
RS-232 TXD Wiring Diagram
PLC Serial Comm. Port
9
TERMINATE +5V

ZL-CMA15L
SIGNAL GND
RS-422/485 RX–
GND
SD–
10
RXD
RS-422/485 RX+ SD+

RS422/485
TXD
232
RS-422/485 TX– RD– 11
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

RS-422/485 TX+ RD+


shield TERM EA-COMCON-3

ZL-CMA15L See ZL-CMA15L specifications on


termination resistor jumper.
12
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
13
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving
connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more
14
than one PLC will be connected to a panel.
A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–13


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


1
Productivity3000 PAC RS485 Port to EA-COMCON-3 Terminal Block Adapter
2 Wiring Diagram
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port

3 SIGNAL GND GND


TXD / RXD – RD –
*
4 TXD / RXD +

Productivity3000
SD –
SD +
PS485 Port RD +

5 * 120 Ω resistor
shield TERM

EA-COMCON-3
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
6
7
8
AutomationDirect Productivity PAC
9 Removable Connector
included with RS-485
To C-more Touch
Panel Serial Port2
Productivity3000 CPU

10
Wiring Diagram 13 15-pin
11 TXD+ / RXD+ 3 9
Term.
RD+
D-sub
8 = do not use (male) 15 = do not use
TXD+ / RXD+ + Term. 11 SD+ 7 = do not use 14 = do not use
15
6 = do not use
12 TXD- / RXD-
Ground
-
G
TXD- / RXD- 8 10
12
RD–
SD–
5 = Logic GND
4 = do not use
13 = Termination
12 = SD– (RS485)
11 = SD+ (RS485)
Ground 5 5 3 = do not use 10 = RD– (RS485)

13 shield 1
2 = do not use 1
1 = Frame GND
9 = RD+ (RS485)

Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
14
A
B
C
NOTE: The RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more
D than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC
will be connected to a panel.

6–14 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):

AutomationDirect CLICK PLC


1
CLICK To C-more Touch
Analog CPU
Com Port 3
RS-485
Panel Serial Port2
2
Wiring Diagram 13 Term. 15-pin
3
D-sub
RS-485 3 9 RD+
RS-485 Signal A +
Signal A
Term. 11 SD+
8 = do not use (male) 15 = do not use
7 = do not use
6 = do not use 15
14 = do not use
13 = Termination
4
RS-485 8 10 RD–
RS-485 Signal B - Signal B 5 = Logic GND 12 = SD– (RS485)
Logic Ground LG
Logic
Ground
5
12
5
SD– 4 = do not use
3 = do not use
11 = SD+ (RS485)
10 = RD– (RS485)
5
2 = do not use 1 9 = RD+ (RS485)
shield 1 1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
6
7
8
9
10
11
12
13
14
A
B
C
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving
connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more
than one PLC will be connected to a panel.
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–15


Chapter 6: PLC Communications

Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON:


1 FA-ISOCON Universal Isolated Network Adapter
RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
2 Wiring Diagram Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
A COM B GND
3 RX– SD–
RX+ SD+
RXD

4 TXD
TXD EN
TX–
TX+
RD–
RD+
B TXD shield TERM

5 C
RXD
CTS
C-A
+V
Ground the shield only at the equipment
end where the FA-ISOCON is located. EA-COMCON-3
C-A
D

6 TX+
TX–
RX–
RX+
See FA-ISOCON specificaitons to
properly configure the adapter. Note: When using multiple PLCs
C-B connected to one C-more touch
panel, only jumper the Term
7 FA-ISOCON
terminal to the RD+ terminal
when the panel is the last device
at one end of the network.

8 Port 2

9
10 Modular cable included
with the FA-ISOCON
PW
RU
CP
TX1
R

N
U
DL05 PLC
1
RX
TX2

11
2
RX

12 Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

13
14
A
B
C
D

6–16 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

Direct LOGIC Universal Converter, p/n F2-UNICON:

F2-UNICON Universal Converter


1
RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
Wiring Diagram Terminal Block Adapter
plugs into C-more 15-pin
2
PLC Serial Comm. Port
GND GND
RXD– SD– 3
RXD+ SD+
TXD–
TXD+
RD–
RD+
4
shield TERM
Ground the shield only at the equipment
end where the F2-UNICON is located. EA-COMCON-3
5
F2-UNICON
See F2-UNICON specificaitons to
properly configure the converter.
Note: When using multiple PLCs
connected to one C-more touch
panel, only jumper the Term
6
terminal to the RD+ terminal
when the panel is the last device
at one end of the network.
PWR
BATT
RUN
CPU 7
DL240
RUN

D2-240 PLC
CPU TERM

CH 1
8
CH 2

CH 3

CH 4 9
PORT 1

10
PORT 2

Modular cable included


with the F2-UNICON 11
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. 12
13
14
A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–17


Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples


1 DL06 and DL205 used for illustration purposes

2 DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave)
Cable Adapter
RXD
DL205 PLC
5
TXD
RS422/485 232

(example device communicating

TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)

Port 2
6
Shielded Cable
ZL-CMA15L

When connecting to a DirectLogic PLC


RXD

Cable Adapter
7
TXD

use connector ZL-CMA15L or ZL-CMA15


RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
8
9
10 Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
To DL06 PLC port 2 To D2-250-1 PLC port 2
11 (example RS-422 connection) (example RS-422 connection)
RXD+

RXD+
RXD–

RXD–
TXD+

RTS+

CTS+

TXD+

RTS+

CTS+
TXD–

RTS–

CTS–

TXD–

RTS–
CTS–
GND

GND

12 7 10 9 6
*
13 11 14 12 15 7 10 9 6 13 11 14 12 15

13 15-pin
HD D-sub
8 = do not use (male)
7 = Sig GND
15 = CTS–
14 = CTS+
6 = RXD– 15 13 = RXD+

14 5 = do not use
4 = do not use
3 = do not use
2 = do not use 1
6
12 = RTS-
11 = RTS+
10 = TXD–
9 = TXD+
1 = do not use
HD = High Density
A RXD+ RXD+

RXD– RXD–

B TXD+

TXD–
TXD+

TXD–
Signal GND Signal GND

C * Termination resistors required at both ends of the


shield

network receive data signals to match the impedance


of the cable (between 100 and 500 ohms).

D Typical RS-422 Multi-Drop Wiring Diagram


using DirectLogic pin numbers to illustrate

6–18 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


DL06 and DL205 used for illustration purposes 1
C-more
DirectLOGIC
DL06 PLC
Touch Panel
2
(example device communicating
across RS-422 connection)
3
4
(Slave)
5
e
(Master)
Port 2
6
e cod
Dat Origin
of
ntry
Cou .
., LTD
S CO

TERM
RIE

N-3
UST
IND

RD+
ON COICS

-COM

RD–
CTR
O ELE
EA

SD+
KOY

SD–
GND
ZL-CMA15L

RXD

Cable Adapter
7
TXD
RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
10
To DL06 PLC port 2 To C-more Touch Panel
(example RS-422 connection) 11

* Term.
RXD+
RXD–
TXD+

RTS+

CTS+
TXD–

RTS–

CTS–

SHD
RD+
RD–

SD+
GND

SD–
GND

EA-COMCON-3
7 10 9 6 13 11 14 12 15 5 10 9 12 11 13 1
12
7 = Sig GND
15-pin
HD D-sub
8 = do not use (male) 15 = CTS–
14 = CTS+ 8 = do not use
15-pin
D-sub 15 = do not use
13
6 = RXD– 15 13 = RXD+ 7 = do not use (male) 14 = do not use
5 = do not use 12 = RTS-
4 = do not use
3 = do not use
2 = do not use 1
6
11 = RTS+
10 = TXD–
9 = TXD+
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
15 13 = Termination
12 = SD– (RS422)
11 = SD+ (RS422)
10 = RD– (RS422)
14
1 = do not use 2 = do not use 9 = RD+ (RS422)
HD = High Density 1 = Frame GND 1

RXD+ RXD+
A
RXD– RXD–

TXD+

TXD–
TXD+

TXD–
B
Signal GND Signal GND
shield
* Termination resistors required at both ends of the
shield
C
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-422 Multi-Drop Wiring Diagram (cont-d) 13 to 9 on the C-more Touch Panel 15-pin connector
to place the 120q internal resistor into the network. If D
the cable impedance is different, then use an external
using DirectLogic pin numbers to illustrate resistor matched to the cable impedance.

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–19


Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


1 DL06 and DL205 used for illustration purposes

2 DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave) RXD
DL205 PLC
Cable Adapter
5
TXD
RS422/485 232

(example device communicating

TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)

Port 2
6
Shielded Cable
ZL-CMA15L

When connecting to a DirectLogic PLC


RXD

Cable Adapter
7
TXD

use connector ZL-CMA15L or ZL-CMA15


RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
8
9
10 Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)

11 To DL06 PLC port 2 To D2-250-1 PLC port 2


(example RS-485 connection) (example RS-485 connection)

12
RXD+

RXD+
RXD–

RXD–
TXD+

RTS+

CTS+

TXD+

RTS+

CTS+
TXD–

RTS–
CTS–

TXD–

RTS–
CTS–
GND

GND

7 6 10 13 9 11 14 12 15 7 6 10 13 9 11 14 12 15

13 *

15-pin
HD D-sub

14 8 = do not use (male)


7 = Sig GND
6 = RXD–
5 = do not use
15
15 = CTS–
14 = CTS+
13 = RXD+
12 = RTS-
4 = do not use 11 = RTS+

A 3 = do not use
2 = do not use 1
1 = do not use 6
10 = TXD–
9 = TXD+

HD = High Density

B TXD– / RXD–

TXD+ / RXD+
TXD– / RXD–

TXD+ / RXD+

Signal GND Signal GND


shield
C * Termination resistors required at both ends of
the network to match the impedance of the cable
(between 100 and 500 ohms).

D Typical RS-485 Multi-Drop Wiring Diagram


using DirectLogic pin numbers to illustrate

6–20 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


DL06 and DL205 used for illustration purposes
1
C-more
DirectLOGIC
DL06 PLC
Touch Panel
2
(example device communicating
across RS-422 connection)
3
4
(Slave)
5
e
(Master)
Port 2
6
e cod
Dat Origin
of
ntry
Cou .
., LTD
S CO

TERM
RIE
IND N-3
UST

CO

RD+
ICS
ON

-COM
CTR

RD–
O ELE
EA

SD+
KOY

SD–
GND
ZL-CMA15L

RXD

Cable Adapter
7
TXD
RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
10
To DL06 PLC port 2 To C-more Touch Panel
11
(example RS-485 connection)

* Term.
12
RXD+
RXD–

TXD+

RTS+

CTS+
TXD–

RTS–
CTS–

SHD
RD+
RD–

SD+
GND

GND

SD–
EA-COMCON-3
7 6 10 13 9 11 14 12 15 5 10 12 9 11 13 1

15-pin
13
HD D-sub
15-pin
8 = do not use (male)
7 = Sig GND
6 = RXD–
5 = do not use
15
15 = CTS–
14 = CTS+
13 = RXD+
12 = RTS-
8 = do not use
6 = do not use
D-sub
7 = do not use (male)
15
15 = do not use
14 = do not use
13 = Termination
14
4 = do not use 11 = RTS+ 5 = Logic GND 12 = SD– (RS485)
3 = do not use 10 = TXD– 4 = do not use 11 = SD+ (RS485)
2 = do not use 1
1 = do not use 6
9 = TXD+

HD = High Density
3 = do not use
2 = do not use
1 = Frame GND 1
10 = RD– (RS485)
9 = RD+ (RS485) A
TXD– / RXD–

TXD+ / RXD+
TXD– / RXD–

TXD+ / RXD+
B
Signal GND Signal GND
shield shield

* Termination resistors required at both ends of the


C
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-485 Multi-Drop Wiring Diagram (cont-d) 13 to 9 on the C-more touch panel 15-pin connector
to place the 120q internal resistor into the network. If D
the cable impedance is different, then use an external
using DirectLogic pin numbers to illustrate resistor matched to the cable impedance.

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–21


Chapter 6: PLC Communications

Allen-Bradley:
EA-MLOGIX-CBL
1 Allen-Bradley MicroLogix™ 1000/1100/1200/1400/1500 To C-more Touch
To AB MicroLogix RS-232
RS-232C (p/n EA-MLOGIX-CBL) Panel PLC Port

2 communication channel

3 1 = do not use
Mini Din
8-pin Male Wiring Diagram 8 = do not use
15-pin
D-sub
(male) 15 = do not use
2 = Sig GND 7 = do not use 14 = do not use
4 3 = do not use TXD 7 3 RXD 6 = do not use 15 13 = do not use
0.290”
4 = RXD 6 7 8
5 = Logic GND 12 = do not use
3 4 5
RXD 4 2
5 = do not use 1 2
TXD
4 = do not use 11 = do not use
6 = do not use GND 2 5 3 = RXD (232C) 10 = do not use
0.35”
5 7 = TXD
8 = do not use
DIA. Nonstandard
keying shield 1 2 = TXD (232C) 1
1 = Frame GND
9 = do not use

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6
EA-SLC-232-CBL
7 To PLC
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix, To C-more Touch
9-Pin Port FlexLogix, MicroLogix, DF1, RS-232C (p/n EA-SLC-232-CBL) Panel PLC Port

8
9 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
7 = do not use 14 = do not use
1 = do not use 1 6 = do not use TXD 3 3 RXD 6 = do not use 15
10 2 = RXD
3 = TXD
7 = do not use
8 = do not use RXD
2 2 TXD
5 = Logic GND
4 = do not use
13 = do not use
12 = do not use
11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9
11 shield 1 2 = TXD (232C) 1
1 = Frame GND
9 = do not use

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

12
EA-PLC5-232-CBL
13 To PLC
25-Pin Port
Allen-Bradley PLC5 DF1 To C-more Touch
RS-232C (p/n EA-PLC5-232-CBL) Panel PLC Port

14
Wiring Diagram
A 25-pin
D-sub
13 = do not use (male) 25 = do not use TXD 2 3 RXD 8 = do not use
15-pin
D-sub
(male) 15 = do not use
12 = do not use 25 24 = do not use 3 2 TXD 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD
B 10 = do not use
9 = do not use
22 = do not use GND 7
21 = do not use
5
1
6
5
=
=
do not
Logic
use
GND
4 = do not use
15 13 = do not use
12 = do not use
8 = do not use shield 11 = do not use
7 = Signal GND 20 = do not use 3 = RXD (232C) 10 = do not use
C 6 = do not use
5 = do not use
4 = do not use
19 = do not use
18 = do not use
17 = do not use
2 = TXD (232C) 1
1 = Frame GND
9 = do not use

3 = RXD 16 = do not use


D 2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6–22 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

Allen-Bradley (cont’d): EA-DH485-CBL


To AB SLC500
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485
Point-to-Point
To C-more Touch
Panel PLC Port 1
DH-485 Port
RS-485A (p/n EA-DH485-CBL)

Wiring Diagram
2
RJ45 8-pin

1 = TXD/RXD+
Phone Plug
(8P8C)
1
13
9
Term.
15-pin
D-sub
8 = do not use (male)
3
2 = TXD/RXD– TXD/RXD+ RD+ 15 = do not use
3 = do not use 2 10 7 = do not use 14 = do not use
4 = Signal GND
5 = LE
TXD/RXD–
11
RD–
SD+
6 = LE
5 = Logic GND
15 13 = Termination
12 = SD– (RS485)
4
6 = do not use 12 4 = do not use 11 = SD+ (RS485)
SD– 3 = do not use
7 = Signal GND 10 = RD– (RS485)
8 = do not use LE *
GND
5
4
6 LE * 2 = do not use 1
1 = Frame GND
9 = RD+ (RS485) 5
GND 7 5 * Note: The LE signal is wired in the cable

shield 1
as shown, but not required for
point-to-point communications. 6
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 9842 shielded cable or equivalent.

Allen-Bradley SLC500™, 5/01, /02, /03 DH-485/AIC to Multiple C-more Touch Panels
7
RS-485A (using C-more cable p/n EA-DH485-CBL)
8
Allen-Bradley DH-485 Link
SLC 500 Modular (See manufacturer’s litature for details.)
PLC Controller

DH-485 DH-485
9
10
Peripheral Peripheral
J2 J2

CPU CPU
J1 J1

Channel 1 must be Power Power


set to DH485.

AB 1747-AIC
DH485 Link Coupler
AB 1747-AIC
DH485 Link Coupler
11
AB 1747-C11 A
Cable
12
13
14
C-more
Touch Panel
C-more
Touch Panel
A
B
C-more
EA-DH485-CBL
C-more
EA-DH485-CBL
C
Cable Cable

Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network
using the AB DH485 Link Coupler, p/n 1747-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–23


Chapter 6: PLC Communications

Allen-Bradley (cont’d):
1 Allen-Bradley SLC500™ 5/03 DH-485/AIC to Multiple C-more Touch Panels
(using C-more cables p/n EA-MLOGIX-CBL, EA-SLC-232-CBL)

2 Allen-Bradley DH-485 Link


SLC 5/03 Modular (See manufacturer’s litature for details.)

3 PLC Controller

4
Channel 0 must be
set to DH485.

5 AB 1761-NET-AIC
AIC + Advanced
AB 1761-NET-AIC
AIC + Advanced
Interface Converter Interface Converter

6 C-more
EA-MLOGIX-CBL
Cable

7 AB 1747-CP3
RS-232 Cable

8 To additional
C-more
Touch Panel

9 C-more C-more
Touch Panel Touch Panel

10
C-more
11 EA-MLOGIX-CBL
Cable
C-more
EA-SLC-232-CBL
Cable

12 Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the
AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.

13
14
A
B
C
D

6–24 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

Allen-Bradley (cont’d):
Multiple Allen-Bradley PLCs connected to multiple C-more Touch Panels 1
(using AB Ethernet Network Interface p/n 761-NET-ENI with EtherNet/IP protocol)

Allen-Bradley
SLC 5/03 Modular
Allen-Bradley
Allen-Bradley
MicroLogix 1500
2
MicroLogix 1000 PLC Controller
PLC Controller PLC Controller
3
4
AB mini DIN to D-shell
cable p/n 1761-CBL-AP00
AB mini DIN to mini DIN
cable p/n 1761-CBL-AM00 5
6
ETHERNET
RS232
FAULT

Ethernet
TX/RX ETHERNET
RS232
FAULT

Hub or Switch
IP

10/100 Base-T
TX/RX
PWR

ETHERNET

IP
FAULT
RS232

TX/RX
CABLE

EXTERNAL
IP

CABLE

EXTERNAL
PWR

7
AB 1761-NET-ENI

8
PWR

AB 1761-NET-ENI
CABLE

EXTERNAL

Ethernet/IP
Network
AB 1761-NET-ENI
9
C-more
Touch Panel 10
C-more
Touch Panel
11
12
13
14
A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–25


Chapter 6: PLC Communications

Allen-Bradley (cont’d): User Constructed


1 To PLC
25-Pin Port
Allen Bradley PLC5 DF1
RS-422
To C-more
PLC Port

2
25-pin Wiring Diagram 15-pin
3 13 = do not use
D-sub
(male) 25 = do not use TXD + 2 10 RD – 8 = do not use
D-sub
(male) 15 = do not use
12 = do not use 25 24 = do not use 3 12 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD + SD – 15 13 = do not use
4 10 = do not use
9 = do not use
8 = do not use
22 = do not use GND
21 = do not use
TXD – 14
7 5
6 = do not use
5 = Logic GND
9 RD + 4 = do not use
12 = SD –
11 = SD +
7 = Signal GND 20 = do not use 3 = do not use 10 = RD –
19 = do not use RXD – 16 11 SD +
5 6 = do not use
5 = do not use
4 = do not use
18 = do not use
17 = do not use shield 1
2 = do not use 1
1 = Frame GND
9 = RD +

3 = RXD + 16 = RXD –
2 = TXD + 15 = do not use
6 1 = do not use
Notes:
1
14 = TXD –

1. Polarities must be swapped.

7 2. Handshaking is turned off


3. Use the above wiring diagram if you need to make your own cable. We recommend using 8103 shielded cable or equivalent.
4. Refer to the PLC-5 Programmable Controllers User Manual Switch Setting Reference for details on switch settings to define
the controller's serial port electrical interface.

8
9
10
11
12
13
14
A
B
C
D

6–26 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

GE: EA-90-30-CBL
To PLC
15-Pin Port
GE 90/30 and 90/70 15-pin D-sub port,
RS-422A (p/n EA-90-30-CBL)
To C-more Touch
Panel PLC Port
1
2
Wiring Diagram 13
15-pin Term. 15-pin
8 = CTS(B’)
7 = Logic GND
D-sub
(male)
15 = CTS(A’)
14 = do not use
SD(B) 13
12
9
10
RD+
D-sub
8 = do not use (male) 15 = do not use
3
15 SD(A) RD– 7 = do not use 14 = do not use
6 = do not use 13 = SD(B) 15
11 11 SD+ 6 = do not use 13 = Termination
5 = +5V
4 = do not use
3 = do not use
12 = SD(A)
11 = RD(B’)
10 = RD(A’)
RD(B’)
RD(A’) 10 12
5 = Logic GND
SD– 4 = do not use
12 = SD– (RS422)
11 = SD+ (RS422)
4
GND 7 5 3 = do not use 10 = RD– (RS422)
2 = do not use 9 = do not use
1 = do not use 1 CTS(B’)
CTS(A’)
8
15
2 = do not use 1
1 = Frame GND
9 = RD+ (RS422)
5
+5V 5
shield 1 6
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

GE VersaMax Micro: User Constructed 7


GE VersaMax Micro Port 1 To C-more Touch
To PLC
RJ45 Port 1 RS-232C
Panel PLC Port
8
RJ45 8-pin 15-pin
9
Phone Plug Wiring Diagram D-sub
1 = RTS (8P8C) (male)
2 = CTS
3 = RXD
4 = TXD
TXD
RXD
4
3
3
2
8 = do not use
RXD 7 = do not use
TXD 6 = donot use
15
15 = do not use
14 = do not use
13 = do not use
10
5 = DCD 8 5 5 = Logic GND 12 = do not use
6 = DTR
7 = +5V
8 = GND
GND
shield
1
4 = do not use
3 = RXD (232C)
2 = TXD (232C) 1
11 = do not use
10 = do not use
9 = do not use
11
1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable. 12
Mitsubishi: EA-MITSU-CBL
To PLC
25-Pin Port
Mitsubishi FX Series 25-pin D-sub port, To C-more Touch
13
RS-422A (p/n EA-MITSU-CBL) Panel PLC Port

14
13 = do not use
25-pin
D-sub
(male) 25 = do not use SD+ 3
Wiring Diagram 13 Term.
9 RD+
15-pin
D-sub
A
8 = do not use (male) 15 = do not use
12 = do not use 25 24 = do not use SD– 16 10 RD– 7 = do not use
11 = do not use
10 = do not use
9 = do not use
23 = do not use
22 = do not use RD+ 2 11 SD+ 6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
B
21 = do not use RD– 15 12 SD–
8 = do not use 4 = do not use 11 = SD+ (RS422)
20 = do not use
7 = Signal GND
6 = do not use
5 = do not use
19 = do not use GND
18 = do not use GND 4
7 5 3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) C
4 = Signal GND 17 = do not use 1
3 = SD+ (RS422) 16 = SD– (RS422) shield
2 = RD+ (RS422) 1
1 = do not use
15 = RD– (RS422)
14 = do not use
D
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–27


Chapter 6: PLC Communications

Mitsubishi(cont’d): EA-MITSU-CBL-1
1 To PLC
Mitsubishi FX Series 8-pin MINI-DIN,
RS-422A (p/n EA-MITSU-CBL-1)
To C-more Touch
Panel PLC Port
8-Pin Port

2 Wiring Diagram
Mini Din 13 Term. 15-pin
8-pin Male D-sub
3 1 = RD– (RS-422)
2 = RD+ (RS-422)
3 = Sig GND
SD+
SD–
7
4
9
10
RD+
RD–
8 = do not use
7 = do not use
(male) 15 = do not use
14 = do not use
6 7 8 6 = do not use 15 13 = Termination
4 = SD– (RS-422) RD+ 2 11 SD+
3 4 5
5 = Logic GND 12 = SD– (RS422)
4 5 = do not use
6 = do not use
7 = SD+ (RS-422)
1 2

RD– 1
3
12
5
SD– 4 = do not use
3 = do not use
11 = SD+ (RS422)
10 = RD– (RS422)
GND 2 = do not use 9 = RD+ (RS422)
8 = do not use 1 1
1 = Frame GND
5 shield
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

6 User Constructed
Mitsubishi Q02 / Q02H / Q06H / Q12H / Q25H Serial Driver
7 and QnA Serial Driver with Direct Connection to To C-more Touch
Panel PLC Port
To PLC the Serial Port on Q00 and Q01 CPU’s
6-Pin Port
8 RS-232C

9 1 = RXD (232C)
Mini Din
6-pin Male Wiring Diagram
15-pin
D-sub
(male)
2 = TXD (232C) 8 = do not use 15 = do not use
TXD 2 3 RXD 7 = do not use
3 = Logic GND 15 14 = do not use
10 4 = do not use
5 = do not use
5
3
6
4
RXD
GND
1
3
2
5
TXD 6 = donot use
5 = Logic GND
13 = do not use
12 = do not use
6 = do not use 4 = do not use 11 = do not use
1 2 1 3 = RXD (232C) 10 = do not use
11 shield
2 = TXD (232C) 1
1 = Frame GND
9 = do not use

Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
12 User Constructed
13 To PLC Mitsubishi Q / QnA Serial PLC To C-more Touch
9-Pin Port QJ71C24N Panel PLC Port
RS-232C
14
Wiring Diagram
A CD 1
9-pin 4 15-pin
D-sub DTR D-sub
B 1 = CD 1
(female)

6 = DSR RS
DSR 6
7
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
6 = do not use 15 13 = do not use
2 = RXD 7 = RS 8
CS 5 = Logic GND 12 = do not use
C 3 = TXD
4 = DTR
5 = Signal GND 9
8 = CS
9 = do not use TXD
3 3 RXD
4 = do not use
3 = RXD (232C)
11 = do not use
10 = do not use
RXD 2 2 TXD 2 = TXD (232C) 9 = do not use
1
5 5 1 = Frame GND
D GND
shield 1

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6–28 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

Omron: EA-OMRON-CBL
To PLC
25-Pin Port
Omron Host Link (C200 Adapter, C500),
RS-232C (p/n EA-OMRON-CBL)
To C-more Touch
Panel PLC Port
1
2
25-pin Wiring Diagram 15-pin
13 = do not use
D-sub
(male) 25 = do not use TXD 2 3 RXD 8 = do not use
D-sub
(male) 15 = do not use
3
12 = do not use 25 24 = do not use 3 2 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD TXD 15 13 = do not use
10 = do not use
9 = do not use
8 = do not use
22 = do not use GND 7
21 = do not use 4
5
6 = do not use
5 = Logic GND
4 = do not use
12 = do not use
11 = do not use
4
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
19 = do not use CTS 5
6 = do not use
5 = CTS
4 = RTS
18 = do not use
17 = do not use shield 1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
5
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
6
User Constructed
7
To PLC
9-Pin Port
Omron FINS (CQM1, CPM1, CPM2, C200, CJ1 & CS1)
RS-232C
To C-more Touch
Panel PLC Port 8
9
9-pin 15-pin
D-sub D-sub

1 = do not use
(male)
9
Wiring Diagram 8 = do not use (male)
7 = do not use
6 = do not use
15 = do not use
14 = do not use
10
6 = do not use TXD 2 3 RXD 15 13 = do not use
2 = TXD 7 = do not use 5 = Logic GND 12 = do not use
3 = RXD
4 = RTS
5 = CTS 1
8 = do not use RXD
9 = Signal GND SG
3
9
2
5
TXD 4 = do not use
3 = RXD (232C)
11 = do not use
10 = do not use
11
4 2 = TXD (232C) 9 = do not use
RTS 1 = Frame GND 1
CTS 5
shield 1
12
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
13
User Constructed
To Peripheral Omron Host Link CQM1 using CQM1-CIF02 Peripheral Port Connecting Cable To C-more Touch
14
Port Cable Panel PLC Port
RS-232C
A
9-pin
D-sub
(male) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
B
7 = do not use 14 = do not use
1 = do not use 9 3 3 6 = do not use 13 = do not use
2 = RXD
3 = TXD
6 = do not use TXD
7 = do not use
8 = do not use RXD
2 2
RXD
TXD
5 = Logic GND
4 = do not use
15
12 = do not use
11 = do not use
C
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 1
shield 1
2 = TXD (232C)
1 = Frame GND 1
9 = do not use
D
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–29


Chapter 6: PLC Communications

Modicon ModBus RS-232: User Constructed


1 To PLC
9-Pin Port
Modicon™ ModBus™, 984 CPU, Quanum 113 CPU
RS-232C
To C-more Touch
Panel PLC Port

2
9-pin 15-pin
3 D-sub
(male) Wiring Diagram
D-sub
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
1 = do not use 9 3 3
6 = DSR TXD RXD 6 = do not use 15 13 = do not use
4 2 = RXD
3 = TXD
4 = DTR
7 = RTS
8 = CTS RXD
9 = do not use GND
2
5
2
5
TXD
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
5 = Signal GND 1 2 = TXD (232C) 1
4 9 = do not use
5 DTR
DSR 6
1 = Frame GND

RTS 7

6 CTS 8
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
7 Modicon Micro Series:
User Constructed
8 To PLC
AEG Modicon™ Micro Series: To C-more Touch
9-Pin Port 110 CPU 311-xx, 110 CPU 411-xx, 110 CPU 512-xx, 110 CPU 612-xx Panel PLC Port
RS-232C
9
10 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
7 = do not use 14 = do not use
1 = do not use 1 2 3 6 = do not use 13 = do not use
11 2 = TXD
3 = RXD
6 = do not use TXD
7 = do not use
8 = do not use RXD
3 2
RXD
5 = Logic GND
TXD 4 = do not use
15
12 = do not use
11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9 2 = TXD (232C) 9 = do not use
12 shield 1 1 = Frame GND 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

13 Modicon ModBus with RJ45: User Constructed


14 To PLC
Modicon™ ModBus™ with RJ45
RS-232C
To C-more Touch
Panel PLC Port
RJ45 Port

A
RJ45 8-pin Wiring Diagram 15-pin
Phone Plug
B 1 = do not use
2 = do not use
3 = TXD
(8P8C) TXD
RXD
3
4
3
2
RXD
8 = do not use
TXD 7 = do not use
D-sub
(male) 15 = do not use
15 14 = do not use
4 = RXD GND 5 5 6 = donot use 13 = do not use
C 5 = Logic GND
6 = RTS RTS 6
7
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
7 = CTS CTS 10 = do not use
8 = do not use 2 = TXD (232C) 1 9 = do not use
D shield 1 1 = Frame GND

Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

6–30 ® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14


Chapter 6: PLC Communications

Siemens: User Constructed


To PLC
9-Pin Port
Siemens S7-200 CPU Port 0 or 1
RS-485A
To C-more Touch
Panel PLC Port
1
2
Wiring Diagram 13
9-pin Term. 15-pin
D-sub
(male)
RS-485
Signal B
3 9
11
RD+
D-sub
8 = do not use (male) 15 = do not use
3
1 = Logic Com 9 SD+ 7 = do not use 14 = do not use
6 = +5 VDC 15
8 10 6 = do not use 13 = Termination
2 = Logic Com
3 = RS485 Sig B
4 = do not use
7 = +24 VDC
8 = RS485 Sig A
RS-485
Signal A
12
RD–
SD–
5 = Logic GND
4 = do not use
12 = SD– (RS485)
11 = SD+ (RS485)
4
9 = do not use Logic 5 5 3 = do not use 10 = RD– (RS485)
5 = Logic Com 1 Common 2 = do not use 1
shield 1 1 = Frame GND
9 = RD+ (RS485)
5
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect L19954 shielded cable or equivalent.

6
7
8
9
10
11
12
13
14
A
B
C
D

® EA-USER-M Hardware User Manual, 2nd Ed. Rev. G, 08/14 6–31