PLC COMMUNICATIONS
6
In This Chapter...
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2
DirectLOGIC PLCs Password Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .6–5
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .6–6
AutomationDirect PLCs RS-232C Serial: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–7
AutomationDirect PLCs RS-422A/RS-485A: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–10
Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON: . . . . . . . . . . .6–16
Direct LOGIC Universal Converter, p/n F2-UNICON: . . . . . . . . . . . . . . . . . . . . . . .6–17
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples . . . . . . . . . . . . . . . . . . . .6–18
Allen-Bradley: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–22
GE: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
GE VersaMax Micro: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
Mitsubishi: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–27
Omron: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–29
Modicon ModBus RS-232: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Modicon Micro Series: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Modicon ModBus with RJ45: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–30
Siemens: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–31
Chapter 6: PLC Communications
Introduction
1 The C-more family of touch panels is capable of communicating with a wide variety of
Programmable Logic Controllers. C-more is capable of communicating over RS232, RS422 and
2 RS485 serial networks as well as Ethernet networks. It communicates with all
AutomationDirect PLC's utilizing various protocols. C-more also communicates with other
brands of PLCs by their different protocols. The table on the next page lists all of the various
3 PLCs and protocols that can be configured. The page after the protocol table lists the various
serial communication cables that are available to purchase. The rest of this chapter is devoted to
4 show the pin to pin connections of all the available cables plus wiring diagrams that the user can
refer to in order to construct their own cables, along with wiring diagrams of cables that are not
available for purchase. To simplify RS422/RS485 wiring schemes, we have included wiring
5 diagrams showing connections for available terminal connectors such as our ZIPLink
Communication Adapter Module, p/n ZL-CMA15, used for example with our DL-06 and D2-
6 260 PLCs and C-more D-Sub 15-pin to Terminal Block Adapter p/n EA-COMCON-3.
If you have difficulty determining whether the particular PLC and/or protocol you are using
7 will work with the C-more series of touch panels, please contact our technical support group at
770-844-4200
11
C-more
Touch Panel
12
DL-06 PLC
13
14
C-more to
A Direct LOGIC
VGA 15-pin port
Port 2 serial cable
B p/n EA-2CBL-1
C
D
Model
Compatibility Table
Protocols
1
Productivity3000
P3000 Serial
P3000 Ethernet
2
CLICK Modbus (CLICK)
K-Sequence 3
all Direct NET
DL05/DL06
H0-ECOM/H0-ECOM100
Modbus (Koyo addressing)
Direct LOGIC Ethernet
4
DL105 all
D2-230
K-Sequence
K-Sequence
5
K-Sequence
D2-240
Direct NET 6
K-Sequence
DL205 D2-250/D2-250-1/D2-260 Direct NET
Modbus (Koyo addressing)
7
Direct NET
D2-240/D2-250-1/D2-260
Using DCM Modbus (Koyo addressing)
8
H2-ECOM/H2-ECOM100 Direct LOGIC Ethernet
D3-330/330P (Requires the use of a Data Communications Unit) Direct NET 9
D3-340 Direct NET
AutomationDirect
DL305 D3-350
K-Sequence
Direct NET
10
Modbus (Koyo addressing)
D3-350 DCM
Direct NET 11
Modbus (Koyo addressing)
D4-430
K-Sequence 12
Direct NET
D4-440
K-Sequence
Direct NET
13
K-Sequence
DL405
D4-450 Direct NET 14
Modbus (Koyo addressing)
GS Drives
GS Drives Serial C
GS Drives TCP/IP (GS-EDRV)
SOLO Temperature Controllers SOLO Temperature Controller D
PLC Compatibility Table continued on the next page.
8 Mitsubishi
Q02, Q02H, Q06H, Q12H, Q25H Q CPU
Q, QnA Serial QnA Serial
14
A
B
C
D
5
6
7
Part No. EA-MLOGIX-CBL Part No. EA-SLC-232-CBL
8
9
10
11 Part No. EA-PLC5-232-CBL Part No. EA-DH485-CBL
12
13
14
A Part No. EA-90-30-CBL Part No. EA-MITSU-CBL
B
C
D
Part No. EA-MITSU-CBL-1 Part No. EA-OMRON-CBL
A
B
C
D
6 Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
7
8
9
10
11
12
13
14
A
B
C
D
13 = do not use
25-pin
D-sub
(male) 25 = do not use TXD 2 3 RXD 8 = do not use
15-pin
D-sub
11
12 = do not use (male) 15 = do not use
25 24 = do not use 3 2 7 = do not use 14 = do not use
23 = do not use RXD TXD
11 = do not use
10 = do not use
9 = do not use
22 = do not use GND 7
21 = do not use 4
5
6 = do not use
5 = Logic GND
15 13 = do not use
12 = do not use
12
8 = do not use 4 = do not use 11 = do not use
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
5
6 = do not use
5 = CTS
19 = do not use
18 = do not use
17 = do not use
CTS
1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use 13
4 = RTS shield
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
14
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
A
B
C
D
11 User Constructed
12 25-pin
D-sub 25 = do not use
Wiring Diagram 13 Term. 15-pin
D-sub
13 = CTS– (male)24 = do not use TXD+ 14 9 RD+
8 = do not use (male) 15 = do not use
12 = CTS+ 23 = do not use
13 11 = RTS–
10 = RTS+
25 22 = do not use TXD–
21 = do not use RXD+ 17
15 10 RD– 7 = do not use
11 SD+ 6 = do not use
15
14 = do not use
13 = Termination
9 = do not use 20 = do not use 5 = Logic GND 12 = SD– (RS422)
8 = do not use 16 12 SD– 4 = do not use
19 = do not use RXD– 11 = SD+ (RS422)
14 7=0V
6 = do not use
5 = do not use
18 = do not use
17 = RXD+
0V
RTS–
7
11
5 3 = do not use
2 = do not use 1
10 = RD– (RS422)
9 = RD+ (RS422)
(RS422) 1 = Frame GND
4 = do not use 13
16 = RXD–
A 3 = do not use
2 = do not use
1 = do not use 1
(RS422)
15 = TXD–
CTS–
RTS+ 10 * Note: The DCM modules must be set for:
CTS+ 12 Direct NET Slave, HEX mode.
(RS422)
B 14 = TXD+
(RS422)
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
C
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
D than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.
8
User Constructed
To PLC
25-Pin Port
Direct LOGIC D4-450 Port 3 To C-more Touch
9
RS-422A Panel PLC Port
RTS and CTS are not present on this port.
10
13 = TXD–
25-pin
D-sub 25 = RXD–
12
Wiring Diagram 13
9
Term. 15-pin
D-sub
11
(male) (RS422) TXD+ RD+
(RS422) 8 = do not use (male) 15 = do not use
12 = TXD+ 24 = RXD+ 13 10
(RS422)
11 = do not use
25 (RS422)
23 = do not use
TXD–
RXD+ 24 11
RD– 7 = do not use
SD+
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
12
10 = do not use 22 = do not use 25 12
9 = do not use RXD– SD– 4 = do not use 11 = SD+ (RS422)
21 = do not use
8 = do not use
7=0V
6 = do not use
20 = do not use
19 = do not use
0V 7
shield
5
1
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) 13
5 = do not use 18 = do not use
17 = do not use
4 = do not use
3 = do not use
2 = do not use 1
16 = do not use
15 = do not use
14
1 = do not use 14 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. A
B
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.
C
D
8
NOTE: The RS-485 wiring diagram shown above is not for multi-drop networks involving connecting more
9 than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.
10
11
12
13
14
A
B
C
D
ZL-CMA15L
+5V
SIGNAL GND GND 3
RS-422/485 RX– RD–
RS422/485
RXD
TXD
232
RS-422/485 TX–
RS-422/485 RX+
SD–
SD+
4
TX+
RX+
TXD
RXD
+5V
TX-
RX-
shield
See ZL-CMA15L specifications on
TERM EA-COMCON-3 5
ZL-CMA15L termination resistor jumper.
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. 6
7
Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-422A – PLC D2-250 (-1), D2-260 or DL06 – Port 2 8
Terminal Block Adapter
plugs into C-more 15-pin
RS-232 RXD
RS-232 TXD Wiring Diagram
PLC Serial Comm. Port
9
TERMINATE +5V
ZL-CMA15L
SIGNAL GND
RS-422/485 RX–
GND
SD–
10
RXD
RS-422/485 RX+ SD+
RS422/485
TXD
232
RS-422/485 TX– RD– 11
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
Productivity3000
SD –
SD +
PS485 Port RD +
5 * 120 Ω resistor
shield TERM
EA-COMCON-3
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
6
7
8
AutomationDirect Productivity PAC
9 Removable Connector
included with RS-485
To C-more Touch
Panel Serial Port2
Productivity3000 CPU
10
Wiring Diagram 13 15-pin
11 TXD+ / RXD+ 3 9
Term.
RD+
D-sub
8 = do not use (male) 15 = do not use
TXD+ / RXD+ + Term. 11 SD+ 7 = do not use 14 = do not use
15
6 = do not use
12 TXD- / RXD-
Ground
-
G
TXD- / RXD- 8 10
12
RD–
SD–
5 = Logic GND
4 = do not use
13 = Termination
12 = SD– (RS485)
11 = SD+ (RS485)
Ground 5 5 3 = do not use 10 = RD– (RS485)
13 shield 1
2 = do not use 1
1 = Frame GND
9 = RD+ (RS485)
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
14
A
B
C
NOTE: The RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more
D than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC
will be connected to a panel.
4 TXD
TXD EN
TX–
TX+
RD–
RD+
B TXD shield TERM
5 C
RXD
CTS
C-A
+V
Ground the shield only at the equipment
end where the FA-ISOCON is located. EA-COMCON-3
C-A
D
6 TX+
TX–
RX–
RX+
See FA-ISOCON specificaitons to
properly configure the adapter. Note: When using multiple PLCs
C-B connected to one C-more touch
panel, only jumper the Term
7 FA-ISOCON
terminal to the RD+ terminal
when the panel is the last device
at one end of the network.
8 Port 2
9
10 Modular cable included
with the FA-ISOCON
PW
RU
CP
TX1
R
N
U
DL05 PLC
1
RX
TX2
11
2
RX
12 Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
13
14
A
B
C
D
D2-240 PLC
CPU TERM
CH 1
8
CH 2
CH 3
CH 4 9
PORT 1
10
PORT 2
2 DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave)
Cable Adapter
RXD
DL205 PLC
5
TXD
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)
Port 2
6
Shielded Cable
ZL-CMA15L
Cable Adapter
7
TXD
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
8
9
10 Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
To DL06 PLC port 2 To D2-250-1 PLC port 2
11 (example RS-422 connection) (example RS-422 connection)
RXD+
RXD+
RXD–
RXD–
TXD+
RTS+
CTS+
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
TXD–
RTS–
CTS–
GND
GND
12 7 10 9 6
*
13 11 14 12 15 7 10 9 6 13 11 14 12 15
13 15-pin
HD D-sub
8 = do not use (male)
7 = Sig GND
15 = CTS–
14 = CTS+
6 = RXD– 15 13 = RXD+
14 5 = do not use
4 = do not use
3 = do not use
2 = do not use 1
6
12 = RTS-
11 = RTS+
10 = TXD–
9 = TXD+
1 = do not use
HD = High Density
A RXD+ RXD+
RXD– RXD–
B TXD+
TXD–
TXD+
TXD–
Signal GND Signal GND
TERM
RIE
N-3
UST
IND
RD+
ON COICS
-COM
RD–
CTR
O ELE
EA
SD+
KOY
SD–
GND
ZL-CMA15L
RXD
Cable Adapter
7
TXD
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
10
To DL06 PLC port 2 To C-more Touch Panel
(example RS-422 connection) 11
* Term.
RXD+
RXD–
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
SHD
RD+
RD–
SD+
GND
SD–
GND
EA-COMCON-3
7 10 9 6 13 11 14 12 15 5 10 9 12 11 13 1
12
7 = Sig GND
15-pin
HD D-sub
8 = do not use (male) 15 = CTS–
14 = CTS+ 8 = do not use
15-pin
D-sub 15 = do not use
13
6 = RXD– 15 13 = RXD+ 7 = do not use (male) 14 = do not use
5 = do not use 12 = RTS-
4 = do not use
3 = do not use
2 = do not use 1
6
11 = RTS+
10 = TXD–
9 = TXD+
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
15 13 = Termination
12 = SD– (RS422)
11 = SD+ (RS422)
10 = RD– (RS422)
14
1 = do not use 2 = do not use 9 = RD+ (RS422)
HD = High Density 1 = Frame GND 1
RXD+ RXD+
A
RXD– RXD–
TXD+
TXD–
TXD+
TXD–
B
Signal GND Signal GND
shield
* Termination resistors required at both ends of the
shield
C
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-422 Multi-Drop Wiring Diagram (cont-d) 13 to 9 on the C-more Touch Panel 15-pin connector
to place the 120q internal resistor into the network. If D
the cable impedance is different, then use an external
using DirectLogic pin numbers to illustrate resistor matched to the cable impedance.
2 DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave) RXD
DL205 PLC
Cable Adapter
5
TXD
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)
Port 2
6
Shielded Cable
ZL-CMA15L
Cable Adapter
7
TXD
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
8
9
10 Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
12
RXD+
RXD+
RXD–
RXD–
TXD+
RTS+
CTS+
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
TXD–
RTS–
CTS–
GND
GND
7 6 10 13 9 11 14 12 15 7 6 10 13 9 11 14 12 15
13 *
15-pin
HD D-sub
A 3 = do not use
2 = do not use 1
1 = do not use 6
10 = TXD–
9 = TXD+
HD = High Density
B TXD– / RXD–
TXD+ / RXD+
TXD– / RXD–
TXD+ / RXD+
TERM
RIE
IND N-3
UST
CO
RD+
ICS
ON
-COM
CTR
RD–
O ELE
EA
SD+
KOY
SD–
GND
ZL-CMA15L
RXD
Cable Adapter
7
TXD
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
10
To DL06 PLC port 2 To C-more Touch Panel
11
(example RS-485 connection)
* Term.
12
RXD+
RXD–
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
SHD
RD+
RD–
SD+
GND
GND
SD–
EA-COMCON-3
7 6 10 13 9 11 14 12 15 5 10 12 9 11 13 1
15-pin
13
HD D-sub
15-pin
8 = do not use (male)
7 = Sig GND
6 = RXD–
5 = do not use
15
15 = CTS–
14 = CTS+
13 = RXD+
12 = RTS-
8 = do not use
6 = do not use
D-sub
7 = do not use (male)
15
15 = do not use
14 = do not use
13 = Termination
14
4 = do not use 11 = RTS+ 5 = Logic GND 12 = SD– (RS485)
3 = do not use 10 = TXD– 4 = do not use 11 = SD+ (RS485)
2 = do not use 1
1 = do not use 6
9 = TXD+
HD = High Density
3 = do not use
2 = do not use
1 = Frame GND 1
10 = RD– (RS485)
9 = RD+ (RS485) A
TXD– / RXD–
TXD+ / RXD+
TXD– / RXD–
TXD+ / RXD+
B
Signal GND Signal GND
shield shield
Allen-Bradley:
EA-MLOGIX-CBL
1 Allen-Bradley MicroLogix™ 1000/1100/1200/1400/1500 To C-more Touch
To AB MicroLogix RS-232
RS-232C (p/n EA-MLOGIX-CBL) Panel PLC Port
2 communication channel
3 1 = do not use
Mini Din
8-pin Male Wiring Diagram 8 = do not use
15-pin
D-sub
(male) 15 = do not use
2 = Sig GND 7 = do not use 14 = do not use
4 3 = do not use TXD 7 3 RXD 6 = do not use 15 13 = do not use
0.290”
4 = RXD 6 7 8
5 = Logic GND 12 = do not use
3 4 5
RXD 4 2
5 = do not use 1 2
TXD
4 = do not use 11 = do not use
6 = do not use GND 2 5 3 = RXD (232C) 10 = do not use
0.35”
5 7 = TXD
8 = do not use
DIA. Nonstandard
keying shield 1 2 = TXD (232C) 1
1 = Frame GND
9 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
6
EA-SLC-232-CBL
7 To PLC
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix, To C-more Touch
9-Pin Port FlexLogix, MicroLogix, DF1, RS-232C (p/n EA-SLC-232-CBL) Panel PLC Port
8
9 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
7 = do not use 14 = do not use
1 = do not use 1 6 = do not use TXD 3 3 RXD 6 = do not use 15
10 2 = RXD
3 = TXD
7 = do not use
8 = do not use RXD
2 2 TXD
5 = Logic GND
4 = do not use
13 = do not use
12 = do not use
11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9
11 shield 1 2 = TXD (232C) 1
1 = Frame GND
9 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
12
EA-PLC5-232-CBL
13 To PLC
25-Pin Port
Allen-Bradley PLC5 DF1 To C-more Touch
RS-232C (p/n EA-PLC5-232-CBL) Panel PLC Port
14
Wiring Diagram
A 25-pin
D-sub
13 = do not use (male) 25 = do not use TXD 2 3 RXD 8 = do not use
15-pin
D-sub
(male) 15 = do not use
12 = do not use 25 24 = do not use 3 2 TXD 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD
B 10 = do not use
9 = do not use
22 = do not use GND 7
21 = do not use
5
1
6
5
=
=
do not
Logic
use
GND
4 = do not use
15 13 = do not use
12 = do not use
8 = do not use shield 11 = do not use
7 = Signal GND 20 = do not use 3 = RXD (232C) 10 = do not use
C 6 = do not use
5 = do not use
4 = do not use
19 = do not use
18 = do not use
17 = do not use
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
Wiring Diagram
2
RJ45 8-pin
1 = TXD/RXD+
Phone Plug
(8P8C)
1
13
9
Term.
15-pin
D-sub
8 = do not use (male)
3
2 = TXD/RXD– TXD/RXD+ RD+ 15 = do not use
3 = do not use 2 10 7 = do not use 14 = do not use
4 = Signal GND
5 = LE
TXD/RXD–
11
RD–
SD+
6 = LE
5 = Logic GND
15 13 = Termination
12 = SD– (RS485)
4
6 = do not use 12 4 = do not use 11 = SD+ (RS485)
SD– 3 = do not use
7 = Signal GND 10 = RD– (RS485)
8 = do not use LE *
GND
5
4
6 LE * 2 = do not use 1
1 = Frame GND
9 = RD+ (RS485) 5
GND 7 5 * Note: The LE signal is wired in the cable
shield 1
as shown, but not required for
point-to-point communications. 6
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485/AIC to Multiple C-more Touch Panels
7
RS-485A (using C-more cable p/n EA-DH485-CBL)
8
Allen-Bradley DH-485 Link
SLC 500 Modular (See manufacturer’s litature for details.)
PLC Controller
DH-485 DH-485
9
10
Peripheral Peripheral
J2 J2
CPU CPU
J1 J1
AB 1747-AIC
DH485 Link Coupler
AB 1747-AIC
DH485 Link Coupler
11
AB 1747-C11 A
Cable
12
13
14
C-more
Touch Panel
C-more
Touch Panel
A
B
C-more
EA-DH485-CBL
C-more
EA-DH485-CBL
C
Cable Cable
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network
using the AB DH485 Link Coupler, p/n 1747-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
D
Allen-Bradley (cont’d):
1 Allen-Bradley SLC500™ 5/03 DH-485/AIC to Multiple C-more Touch Panels
(using C-more cables p/n EA-MLOGIX-CBL, EA-SLC-232-CBL)
3 PLC Controller
4
Channel 0 must be
set to DH485.
5 AB 1761-NET-AIC
AIC + Advanced
AB 1761-NET-AIC
AIC + Advanced
Interface Converter Interface Converter
6 C-more
EA-MLOGIX-CBL
Cable
7 AB 1747-CP3
RS-232 Cable
8 To additional
C-more
Touch Panel
9 C-more C-more
Touch Panel Touch Panel
10
C-more
11 EA-MLOGIX-CBL
Cable
C-more
EA-SLC-232-CBL
Cable
12 Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the
AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
13
14
A
B
C
D
Allen-Bradley (cont’d):
Multiple Allen-Bradley PLCs connected to multiple C-more Touch Panels 1
(using AB Ethernet Network Interface p/n 761-NET-ENI with EtherNet/IP protocol)
Allen-Bradley
SLC 5/03 Modular
Allen-Bradley
Allen-Bradley
MicroLogix 1500
2
MicroLogix 1000 PLC Controller
PLC Controller PLC Controller
3
4
AB mini DIN to D-shell
cable p/n 1761-CBL-AP00
AB mini DIN to mini DIN
cable p/n 1761-CBL-AM00 5
6
ETHERNET
RS232
FAULT
Ethernet
TX/RX ETHERNET
RS232
FAULT
Hub or Switch
IP
10/100 Base-T
TX/RX
PWR
ETHERNET
IP
FAULT
RS232
TX/RX
CABLE
EXTERNAL
IP
CABLE
EXTERNAL
PWR
7
AB 1761-NET-ENI
8
PWR
AB 1761-NET-ENI
CABLE
EXTERNAL
Ethernet/IP
Network
AB 1761-NET-ENI
9
C-more
Touch Panel 10
C-more
Touch Panel
11
12
13
14
A
B
C
D
2
25-pin Wiring Diagram 15-pin
3 13 = do not use
D-sub
(male) 25 = do not use TXD + 2 10 RD – 8 = do not use
D-sub
(male) 15 = do not use
12 = do not use 25 24 = do not use 3 12 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD + SD – 15 13 = do not use
4 10 = do not use
9 = do not use
8 = do not use
22 = do not use GND
21 = do not use
TXD – 14
7 5
6 = do not use
5 = Logic GND
9 RD + 4 = do not use
12 = SD –
11 = SD +
7 = Signal GND 20 = do not use 3 = do not use 10 = RD –
19 = do not use RXD – 16 11 SD +
5 6 = do not use
5 = do not use
4 = do not use
18 = do not use
17 = do not use shield 1
2 = do not use 1
1 = Frame GND
9 = RD +
3 = RXD + 16 = RXD –
2 = TXD + 15 = do not use
6 1 = do not use
Notes:
1
14 = TXD –
8
9
10
11
12
13
14
A
B
C
D
GE: EA-90-30-CBL
To PLC
15-Pin Port
GE 90/30 and 90/70 15-pin D-sub port,
RS-422A (p/n EA-90-30-CBL)
To C-more Touch
Panel PLC Port
1
2
Wiring Diagram 13
15-pin Term. 15-pin
8 = CTS(B’)
7 = Logic GND
D-sub
(male)
15 = CTS(A’)
14 = do not use
SD(B) 13
12
9
10
RD+
D-sub
8 = do not use (male) 15 = do not use
3
15 SD(A) RD– 7 = do not use 14 = do not use
6 = do not use 13 = SD(B) 15
11 11 SD+ 6 = do not use 13 = Termination
5 = +5V
4 = do not use
3 = do not use
12 = SD(A)
11 = RD(B’)
10 = RD(A’)
RD(B’)
RD(A’) 10 12
5 = Logic GND
SD– 4 = do not use
12 = SD– (RS422)
11 = SD+ (RS422)
4
GND 7 5 3 = do not use 10 = RD– (RS422)
2 = do not use 9 = do not use
1 = do not use 1 CTS(B’)
CTS(A’)
8
15
2 = do not use 1
1 = Frame GND
9 = RD+ (RS422)
5
+5V 5
shield 1 6
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
14
13 = do not use
25-pin
D-sub
(male) 25 = do not use SD+ 3
Wiring Diagram 13 Term.
9 RD+
15-pin
D-sub
A
8 = do not use (male) 15 = do not use
12 = do not use 25 24 = do not use SD– 16 10 RD– 7 = do not use
11 = do not use
10 = do not use
9 = do not use
23 = do not use
22 = do not use RD+ 2 11 SD+ 6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
B
21 = do not use RD– 15 12 SD–
8 = do not use 4 = do not use 11 = SD+ (RS422)
20 = do not use
7 = Signal GND
6 = do not use
5 = do not use
19 = do not use GND
18 = do not use GND 4
7 5 3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) C
4 = Signal GND 17 = do not use 1
3 = SD+ (RS422) 16 = SD– (RS422) shield
2 = RD+ (RS422) 1
1 = do not use
15 = RD– (RS422)
14 = do not use
D
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
Mitsubishi(cont’d): EA-MITSU-CBL-1
1 To PLC
Mitsubishi FX Series 8-pin MINI-DIN,
RS-422A (p/n EA-MITSU-CBL-1)
To C-more Touch
Panel PLC Port
8-Pin Port
2 Wiring Diagram
Mini Din 13 Term. 15-pin
8-pin Male D-sub
3 1 = RD– (RS-422)
2 = RD+ (RS-422)
3 = Sig GND
SD+
SD–
7
4
9
10
RD+
RD–
8 = do not use
7 = do not use
(male) 15 = do not use
14 = do not use
6 7 8 6 = do not use 15 13 = Termination
4 = SD– (RS-422) RD+ 2 11 SD+
3 4 5
5 = Logic GND 12 = SD– (RS422)
4 5 = do not use
6 = do not use
7 = SD+ (RS-422)
1 2
RD– 1
3
12
5
SD– 4 = do not use
3 = do not use
11 = SD+ (RS422)
10 = RD– (RS422)
GND 2 = do not use 9 = RD+ (RS422)
8 = do not use 1 1
1 = Frame GND
5 shield
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
6 User Constructed
Mitsubishi Q02 / Q02H / Q06H / Q12H / Q25H Serial Driver
7 and QnA Serial Driver with Direct Connection to To C-more Touch
Panel PLC Port
To PLC the Serial Port on Q00 and Q01 CPU’s
6-Pin Port
8 RS-232C
9 1 = RXD (232C)
Mini Din
6-pin Male Wiring Diagram
15-pin
D-sub
(male)
2 = TXD (232C) 8 = do not use 15 = do not use
TXD 2 3 RXD 7 = do not use
3 = Logic GND 15 14 = do not use
10 4 = do not use
5 = do not use
5
3
6
4
RXD
GND
1
3
2
5
TXD 6 = donot use
5 = Logic GND
13 = do not use
12 = do not use
6 = do not use 4 = do not use 11 = do not use
1 2 1 3 = RXD (232C) 10 = do not use
11 shield
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
12 User Constructed
13 To PLC Mitsubishi Q / QnA Serial PLC To C-more Touch
9-Pin Port QJ71C24N Panel PLC Port
RS-232C
14
Wiring Diagram
A CD 1
9-pin 4 15-pin
D-sub DTR D-sub
B 1 = CD 1
(female)
6 = DSR RS
DSR 6
7
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
6 = do not use 15 13 = do not use
2 = RXD 7 = RS 8
CS 5 = Logic GND 12 = do not use
C 3 = TXD
4 = DTR
5 = Signal GND 9
8 = CS
9 = do not use TXD
3 3 RXD
4 = do not use
3 = RXD (232C)
11 = do not use
10 = do not use
RXD 2 2 TXD 2 = TXD (232C) 9 = do not use
1
5 5 1 = Frame GND
D GND
shield 1
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
Omron: EA-OMRON-CBL
To PLC
25-Pin Port
Omron Host Link (C200 Adapter, C500),
RS-232C (p/n EA-OMRON-CBL)
To C-more Touch
Panel PLC Port
1
2
25-pin Wiring Diagram 15-pin
13 = do not use
D-sub
(male) 25 = do not use TXD 2 3 RXD 8 = do not use
D-sub
(male) 15 = do not use
3
12 = do not use 25 24 = do not use 3 2 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD TXD 15 13 = do not use
10 = do not use
9 = do not use
8 = do not use
22 = do not use GND 7
21 = do not use 4
5
6 = do not use
5 = Logic GND
4 = do not use
12 = do not use
11 = do not use
4
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
19 = do not use CTS 5
6 = do not use
5 = CTS
4 = RTS
18 = do not use
17 = do not use shield 1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
5
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
6
User Constructed
7
To PLC
9-Pin Port
Omron FINS (CQM1, CPM1, CPM2, C200, CJ1 & CS1)
RS-232C
To C-more Touch
Panel PLC Port 8
9
9-pin 15-pin
D-sub D-sub
1 = do not use
(male)
9
Wiring Diagram 8 = do not use (male)
7 = do not use
6 = do not use
15 = do not use
14 = do not use
10
6 = do not use TXD 2 3 RXD 15 13 = do not use
2 = TXD 7 = do not use 5 = Logic GND 12 = do not use
3 = RXD
4 = RTS
5 = CTS 1
8 = do not use RXD
9 = Signal GND SG
3
9
2
5
TXD 4 = do not use
3 = RXD (232C)
11 = do not use
10 = do not use
11
4 2 = TXD (232C) 9 = do not use
RTS 1 = Frame GND 1
CTS 5
shield 1
12
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
13
User Constructed
To Peripheral Omron Host Link CQM1 using CQM1-CIF02 Peripheral Port Connecting Cable To C-more Touch
14
Port Cable Panel PLC Port
RS-232C
A
9-pin
D-sub
(male) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
B
7 = do not use 14 = do not use
1 = do not use 9 3 3 6 = do not use 13 = do not use
2 = RXD
3 = TXD
6 = do not use TXD
7 = do not use
8 = do not use RXD
2 2
RXD
TXD
5 = Logic GND
4 = do not use
15
12 = do not use
11 = do not use
C
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 1
shield 1
2 = TXD (232C)
1 = Frame GND 1
9 = do not use
D
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
2
9-pin 15-pin
3 D-sub
(male) Wiring Diagram
D-sub
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
1 = do not use 9 3 3
6 = DSR TXD RXD 6 = do not use 15 13 = do not use
4 2 = RXD
3 = TXD
4 = DTR
7 = RTS
8 = CTS RXD
9 = do not use GND
2
5
2
5
TXD
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
5 = Signal GND 1 2 = TXD (232C) 1
4 9 = do not use
5 DTR
DSR 6
1 = Frame GND
RTS 7
6 CTS 8
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
7 Modicon Micro Series:
User Constructed
8 To PLC
AEG Modicon™ Micro Series: To C-more Touch
9-Pin Port 110 CPU 311-xx, 110 CPU 411-xx, 110 CPU 512-xx, 110 CPU 612-xx Panel PLC Port
RS-232C
9
10 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male) 15 = do not use
7 = do not use 14 = do not use
1 = do not use 1 2 3 6 = do not use 13 = do not use
11 2 = TXD
3 = RXD
6 = do not use TXD
7 = do not use
8 = do not use RXD
3 2
RXD
5 = Logic GND
TXD 4 = do not use
15
12 = do not use
11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9 2 = TXD (232C) 9 = do not use
12 shield 1 1 = Frame GND 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
A
RJ45 8-pin Wiring Diagram 15-pin
Phone Plug
B 1 = do not use
2 = do not use
3 = TXD
(8P8C) TXD
RXD
3
4
3
2
RXD
8 = do not use
TXD 7 = do not use
D-sub
(male) 15 = do not use
15 14 = do not use
4 = RXD GND 5 5 6 = donot use 13 = do not use
C 5 = Logic GND
6 = RTS RTS 6
7
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
7 = CTS CTS 10 = do not use
8 = do not use 2 = TXD (232C) 1 9 = do not use
D shield 1 1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.