Optional extras
Panel Printer:
Fit to panel to allow up to 15 panels to be networked and to add Global Network Repeater Panels.
The Premier AL 1-4 loop panel can use the Standard Repeater (for a stand alone panel) or a Global Network
Repeater (for a networked system).
Technical Specification
Model PR-AL/1 PR-AL/2 PR-AL/3 PR-AL/4
Part No. 37-201 37-202 37-203 37-204
Detection Loops 1 2 3 4
Repeater Model Premier AL Repeater (REP-AL)
Repeater Part No. 37-220
Mains Voltage 230V AC + 10% / -6% @ 50/60 Hz
System Voltage 28V DC (nominal)
Loop Voltage 24V DC + 9V AC Signal (nominal)
Sounder Alarm Output 2 x 1 A Common @ 24V DC (nominal)
Fault Relay 1 x Relay SELV @ 1A maximum
Fire Relay 2 x Relay SELV @ 1A maximum
Zone Capacity 32 programmable zones
Sounder EOL 3K9 (Orange, White, Red, Gold)
Charge Voltage 27.1 Volt (with battery disconnected)
Charger Size 3 Amp
Aux Supply 500mA max
Batteries (Min. Size) 2 x 12V, 12AH SLA Batteries
Ingress Protection IP43
Enclosure 410 W x 480 H x 144 D (mm)
Weight 15kg (Excluding Batteries)