You are on page 1of 1

PANEL : PB MAIN CIRCUIT BREAKER : 40AT, 50AF, 3-POLE

FED FROM: MAIN FEEDER : RYB

ENCLOSURE : NEMA 1 SYSTEM VOLTAGE : 400/230 VOLTS, 3Ø, 60Hz

CKT. DEVICES LOAD CURRENT (AMPERE) VOLT BRANCH CIRCUIT BREAKER BRANCH CIRCUIT WIRING
DESCRIPTION OF LOAD VOLT
NO. LO CO ØAN ØBN ØCN 3Ø AMP AMPERE POLE FRAME TRIP KAIC WIRE RACEWAY
1 9 LIGHTING 400/230 2.08 480 1 50 20 10 20mmØ CONDUIT
2 - 3.5mm² THHN/THWN + 1 - 3.5mm² THHN/THWN

2 10 LIGHTING 400/230 2.39 550 1 50 20 10 2 - 3.5mm² THHN/THWN + 1 - 3.5mm² THHN/THWN


20mmØ CONDUIT

3 9 LIGHTING 400/230 2.61 600 1 50 20 10 2 - 3.5mm² THHN/THWN + 1 - 3.5mm² THHN/THWN


20mmØ CONDUIT

4 2 CONVENIENCE OUTLET 400/230 1.57 360 1 50 20 10 2 - 3.5mm² THHN/THWN + 1 - 3.5mm² THHN/THWN 20mmØ CONDUIT

5 7 CONVENIENCE OUTLET 400/230 5.48 1260 1 50 20 10 2 - 3.5mm² THHN/THWN + 1 - 3.5mm² THHN/THWN 20mmØ CONDUIT

7 SPARE 400/230 4.35 1000 1 50 20 10


8 SPARE 400/230 4.35 1000 1 50 20 10
24 9 TOTAL CONNECTED LOAD 8.0 7.88 6.96 5,250

COMPUTATIONS: USE: 40AT/50AF, 3P, 400V, MCCB BOLT ON TYPE, NEMA 1 LOCATION : AS SHOWN
I = (8.0)(1.732) @ 85% D.F. = 11.77 amps.
WITH NEUTRAL BUS, 25KAIC WITH GROUND INSULATION BUS: MOUNTING : SURFACE MOUNTED
MINIMUM AMPACITY OF MAIN FEEDER CONDUCTOR:
I = 1.25 x 11.77 = 14.72 amps. USE: 4-8.0mm² THHN/THWN + 1 - 5.5mm² THHN/THWN in 1 1/4" RSC conduit APPLIED DEMAND FACTOR : 80%

SCHEDULE OF LOADS
SCALE : NTS

VOLTAGE DROP CALCULATION


SCALE : NTS

SHORT CIRCUIT ANALYSIS


SCALE : NTS

SEAL : SECTION 25/RA 545 PROJECT TITLE : PROJECT OWNER: SHEET CONTENTS DESIGNED : M.E.A.E, REE/RME REVISIONS: SHEET NO.
DRAWING AND SPECIFICATIONS DULY
SIGNED, SEALED OR STAMP, AS AN
NO. DATE REMARKS CAD
INSTRUMENTS OF SERVICE, ARE THE
PROPERTY AND DOCUMENTS OF DEUS'
CADD : M.E.A.E, REE/RME
PROFESSIONAL ELECTRICAL ENGINEER SCHEDULE OF LOADS
Project Management Corporation, WHETHER
THE OBJECT FOR WHICH THEY ARE MADE
IS EXECUTED OR NOT. IT SHALL BE
A PROPOSED INTERIOR RENOVATION DATE :
REG. NO. : DATE :
UNLAWFUL FOR ANY PERSON, WITHOUT
THE WRITTEN CONSENT OF THE
ARCHITECT OR AUTHOR OF SAID
DOCUMENTS, TO DUPLICATE OR TO MAKE
"DARA BEAUTY MARKET" RAISSA ALEXANDRA ONG OH AND DEOK HWAN KIM SHORT CIRCUIT ANALYSIS
CHECKED :
EE-2
PTR. NO. : DATE : COPIES OF SAID DOCUMENTS FOR USE IN
THE REPETITION OF AND FOR OTHER VOLTAGE DROP CALCULATION
T. I. N. : PROJECTS OR BUILDINGS, WHETHER
EXECUTED PARTLY OR IN WHOLE. LOCATION : BLOCK 10, 2F, SU 14, AYALA MALLS CENTRAL BLOCK IT PARK LAHUG, CEBU CITY UPDATED