1. GMB-3 at the left side of GMG-6 in grid line 7 Web bar not sufficiently tied with the stirrups. It should be tied at all intersections 2. GMG-12b Splice of continuous bottom bar not yet installed. 3. GMG-6 2 continuous top bar not met the minimum lap splice length. Web bar not installed. 4. GMB-3 at the left side of GMG-6 in grid line 6 Continuous top bar not met the minimum lap splice length. Web bar not installed. 5. GMG-11 No extra bar at midspan and at top left support No web bar installed. 6. GMG-7 No web bar installed. 7. GMG-12 No web bar installed. 8. GMG-8 in grid line 4/J-K Extra bar at top right support and web bars not yet installed 9. GMG-7a No extra bar at midspan 2 continuous bottom bar not splice through the column. 10. GMG-3a right of grid line 5 No extra bottom bar at midspan. 11. GMG-13 No extra bar at top left support 12. GMB-3a left of grid line 6 No web bar installed. 13. GMB-3a right of grid line 6 Web bar not sufficiently tied with the stirrups. It should be tied at all intersections 14. GMG-13a between grid line 6 and 7 No extra bar at right support. Continuous top bar not met the minimum lap splice length.
Beam and Girder completely installed and no corrections.
1. GMG-6 and GMG-6a in grid line 7 2. GMB-3 at right side of grid line 6 3. GMB-3 at right side of grid line 5 4. GMB-7 5. GMG-6a in grid line 6 6. GMB-22 7. GMB-29