PV Array Characteristics
PV module Si-mono Model LG375S2W-U5_R01
Original PVsyst database Manufacturer LG Electronics
Number of PV modules In series 18 modules In parallel 10 strings
Total number of PV modules Nb. modules 180 Unit Nom. Power 375 Wp
Array global power Nominal (STC) 67.5 kWp At operating cond. 61.4 kWp (50°C)
Array operating characteristics (50°C) U mpp 649 V I mpp 95 A
Total area Module area 353 m² Cell area 317 m²
Normalized productions (per installed kWp): Nominal power 67.5 kWp Performance Ratio PR
6 1.0
Lc : Collection Loss (PV-array losses) 0.74 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.839
0.9
Ls : System Loss (inverter, ...) 0.06 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 4.17 kWh/kWp/day
0.8
[kWh/kWp/day]
0.7
4
Performance Ratio PR
0.6
Energy
3 0.5
0.4
Normalized
2
0.3
0.2
1
0.1
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T_Amb T amb. E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio
500
Values from 01/01 to 31/12
400
[kWh/day]
grid
300
into
injected
200
Energy
100
0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]
2500
Values from 01/01 to 31/12
2000
Bin]
/
[kWh
1500
grid
into
injected
1000
Energy
500
0
0 10 20 30 40 50 60
Power injected into grid [kW]