PVSYST V6.84 Vu Phong Solar Jsc.

(Viet Nam) 17/02/20 Page 1/4

Grid-Connected System: Simulation parameters


Project : Lexus Central Saigon
Geographical Site Lexus Central Saigon Country Vietnam
Situation Latitude 10.76° N Longitude 106.69° E
Time defined as Legal Time Time zone UT+7 Altitude 0 m
Albedo 0.20
Meteo data: Lexus Central Saigon Meteonorm 7.2 (1991-2010), Sat=100% - Synthetic

Simulation variant : New simulation variant


Simulation date 17/02/20 10h33

Simulation parameters System type No 3D scene defined, no shadings


Collector Plane Orientation Tilt 15° Azimuth 40°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)

PV Array Characteristics
PV module Si-mono Model LG375S2W-U5_R01
Original PVsyst database Manufacturer LG Electronics
Number of PV modules In series 18 modules In parallel 10 strings
Total number of PV modules Nb. modules 180 Unit Nom. Power 375 Wp
Array global power Nominal (STC) 67.5 kWp At operating cond. 61.4 kWp (50°C)
Array operating characteristics (50°C) U mpp 649 V I mpp 95 A
Total area Module area 353 m² Cell area 317 m²

Inverter Model Trinergy Plus 60KW (60kw,3 phase with 1 MPPT)


Original PVsyst database Manufacturer AEC
Characteristics Operating Voltage 570-950 V Unit Nom. Power 60.0 kWac
Inverter pack Nb. of inverters 1 units Total Power 60 kWac
Pnom ratio 1.13

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 114 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction 1.0 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 20° 45° 55° 70° 75° 80° 85° 90°
1.000 1.000 0.997 0.993 0.940 0.872 0.772 0.472 0.000

PVsyst Licensed to Vu Phong Solar Jsc. (Viet Nam)


PVSYST V6.84 Vu Phong Solar Jsc. (Viet Nam) 17/02/20 Page 2/4

Grid-Connected System: Main results


Project : Lexus Central Saigon
Simulation variant : New simulation variant
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 40°
PV modules Model LG375S2W-U5_R01 Pnom 375 Wp
PV Array Nb. of modules 180 Pnom total 67.5 kWp
Inverter Trinergy Plus 60KW (60kw,3 phase with 1 MPPT) Pnom 60.0 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 102.6 MWh/year Specific prod. 1521 kWh/kWp/year
Performance Ratio PR 83.93 %

Normalized productions (per installed kWp): Nominal power 67.5 kWp Performance Ratio PR

6 1.0
Lc : Collection Loss (PV-array losses) 0.74 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.839
0.9
Ls : System Loss (inverter, ...) 0.06 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 4.17 kWh/kWp/day
0.8
[kWh/kWp/day]

0.7
4
Performance Ratio PR

0.6
Energy

3 0.5

0.4
Normalized

2
0.3

0.2
1

0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

New simulation variant


Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh
January 148.5 65.73 26.29 162.1 159.4 9.301 9.176 0.839
February 146.1 67.80 27.11 154.0 151.4 8.764 8.649 0.832
March 164.1 82.27 28.40 167.1 164.1 9.473 9.349 0.829
April 149.0 79.15 29.04 145.4 142.6 8.259 8.146 0.830
May 160.4 91.31 28.50 152.4 149.2 8.761 8.644 0.840
June 161.6 77.64 27.50 149.7 146.7 8.633 8.518 0.843
July 161.4 88.92 27.34 151.1 147.9 8.748 8.631 0.846
August 161.5 85.17 27.29 155.0 151.9 8.933 8.814 0.842
September 136.3 78.35 26.67 134.1 131.4 7.750 7.641 0.844
October 142.0 78.14 26.76 146.7 144.0 8.448 8.334 0.842
November 134.5 71.21 26.35 143.7 141.0 8.301 8.193 0.844
December 137.3 66.46 26.20 150.4 147.9 8.661 8.546 0.842
Year 1802.6 932.16 27.29 1811.9 1777.5 104.032 102.642 0.839

Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T_Amb T amb. E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Licensed to Vu Phong Solar Jsc. (Viet Nam)


PVSYST V6.84 Vu Phong Solar Jsc. (Viet Nam) 17/02/20 Page 3/4

Grid-Connected System: Special graphs


Project : Lexus Central Saigon
Simulation variant : New simulation variant
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 40°
PV modules Model LG375S2W-U5_R01 Pnom 375 Wp
PV Array Nb. of modules 180 Pnom total 67.5 kWp
Inverter Trinergy Plus 60KW (60kw,3 phase with 1 MPPT) Pnom 60.0 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

500
Values from 01/01 to 31/12

400
[kWh/day]
grid

300
into
injected

200
Energy

100

0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]

System Output Power Distribution

2500
Values from 01/01 to 31/12

2000
Bin]
/
[kWh

1500
grid
into
injected

1000
Energy

500

0
0 10 20 30 40 50 60
Power injected into grid [kW]

PVsyst Licensed to Vu Phong Solar Jsc. (Viet Nam)


PVSYST V6.84 Vu Phong Solar Jsc. (Viet Nam) 17/02/20 Page 4/4

Grid-Connected System: Loss diagram


Project : Lexus Central Saigon
Simulation variant : New simulation variant
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 40°
PV modules Model LG375S2W-U5_R01 Pnom 375 Wp
PV Array Nb. of modules 180 Pnom total 67.5 kWp
Inverter Trinergy Plus 60KW (60kw,3 phase with 1 MPPT) Pnom 60.0 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1803 kWh/m² Horizontal global irradiation


+0.5% Global incident in coll. plane

-1.90% IAM factor on global

1778 kWh/m² * 353 m² coll. Effective irradiation on collectors

efficiency at STC = 19.18% PV conversion

120.3 MWh Array nominal energy (at STC effic.)


-0.19% PV loss due to irradiance level

-10.57% PV loss due to temperature

-1.00% Module quality loss


-1.10% Mismatch loss, modules and strings
-1.02% Ohmic wiring loss
104.0 MWh Array virtual energy at MPP

-1.34% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
102.6 MWh Available Energy at Inverter Output
102.6 MWh Energy injected into grid

PVsyst Licensed to Vu Phong Solar Jsc. (Viet Nam)