71-1 @ IEC:1993 -43— Table 2 ~ Standard insulation levels for range 1 (1 KV < U,, 245 KV) Highest vottage | Standard short-duration Standard for equipment power-frequency lighting impulse Un withstand voltage withstand voltage wv wv Ww (ems. valve) ems. value) (peak valve) 36 10 20 40 72 20 “0 60 12 28 60 7s 95 75 38 75 35 2a 50 5 125 145 36 70 148 170 32 35 250) 728 140 325 128 (185) 450 230 350 148 (185) (450) 230 550 275 650 170 (230) (650) 276 650 335 750 245 75) (650) (625) (750) 360 850 295 950 460 1050 NOTE ~ If values in brackets aro considered insutficient to prove that the required phase-to-phase withstand voltages are met, additional phaso-to phase withstand tests are nooded