General features
Modbus TCP/RTU Gateway
06/10/2015
General features
8 digital inputs
2 digital outputs
7-32Vdc supply
106(L)x90(H)x58(P)mm
06/10/2015
Communication
ETHERNET
RS232
INSULATED RS485
Remote FW update
06/10/2015
Communication
MODBUS RTU and TCP protocols
NTP support
06/10/2015
Operation
WEB monitoring
SI.MO.NE. extender/gateway
06/10/2015
Digital outputs Supply
Ethernet
Function/Host
RS485
selector
Analogue
USB function
inputs
06/10/2015
Gateway functionality
PC1 DANCE Device 1
Device 8
PCn
06/10/2015
Gateway functionality
This functionality allows to communicate towards
any MODBUS RTU devices from MODBUS TCP
applications and interfaces.
Using RS485, instead of RS232, up to 32 MODBUS
RTU devices can be connected on the same line.
06/10/2015
WEB monitoring
Generator
PC1 DANCE
Controller
PCn
06/10/2015
SI.MO.NE. extender/gateway
Router/Firewall
Generator
DANCE
Controller
SI.MO.NE.
06/10/2015
SI.MO.NE. extender/gateway
06/10/2015
Local Data Logger
Generator
DANCE
Controller
MODBUS RTU
Communication
USB STICK
06/10/2015
Local Data Logger
06/10/2015
Local Data Logger
React. Oil Coolant
Gen. Gen. Gen. Gen. L1 Gen. L2 Gen. L3 Gen. Active Pw. P.F.+Lo Battery Mains Mains Mains Pw Cnt Fuel Press. . Temp.
Date Time N.Prog. Valid EngRun L1-L2 V L2-L3 V L3-L1 V A A A Freq. Hz Pw. kW kVar ad Type V L1-L2 V L2-L3 V L3-L1 V Kwh Level % Bar °C Mode
16/09/2015 00:00:08 64842 1 1 313 313 313 3.3 3.3 3.3 50.2 -1.1 1.2 -0.05 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:18 64843 1 1 313 313 314 3.3 3.3 3.3 50.3 -0.4 -0.9 -0.59 i 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:28 64844 1 1 313 313 313 3.3 3.3 3.3 50.2 1.5 -0.0 0.77 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:38 64845 1 1 313 313 313 3.3 3.3 3.3 50.2 -1.5 1.1 -0.35 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:48 64846 1 1 313 313 314 3.3 3.3 3.3 50.2 0.4 -1.2 -0.29 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:58 64847 1 1 313 313 313 3.3 3.3 3.3 50.3 1.1 0.5 0.74 i 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:01:08 64848 1 1 313 313 313 3.3 3.3 3.3 50.3 -1.7 0.6 -0.61 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
06/10/2015
Operation
06/10/2015
06/10/2015
Network configuration
06/10/2015
SI.MO.NE. configuration
06/10/2015
MODBUS configuration
06/10/2015
Digital input configuration
06/10/2015
Digital output configuration
06/10/2015
GPS configuration
Dance has not GPS, but retains the possibility to set fixed
coordinates.
06/10/2015
Other configurations
06/10/2015
DataLog configuration
In order to use a USB stick for data logging, a digital input with
function 13-DataLog Enable has to be configured. Operation is the
following:
- Insert USB stick
- Ground the digital input with function 13
- Recording
- Disconnect digital input from ground
- Remove USB stick
06/10/2015