You are on page 1of 27

DA.N.C.E.

(Data Network Communication


Equipment) is a device that allows controllers and
other devices to communicate over a Local Area
Network. It allows also to gather genset data.

06/10/2015
06/10/2015
General features
Modbus TCP/RTU Gateway

Direct support of SICES genset controllers

Direct support of most common genset controllers

SI.MO.NE. cloud system support

WEB monitoring server

RTC with rechargeable battery

06/10/2015
General features
8 digital inputs

2 digital outputs

2 analogue inputs (0..10V)

DIN rail mount system

7-32Vdc supply

106(L)x90(H)x58(P)mm

06/10/2015
Communication
ETHERNET

USB HOST / FUNCTION

RS232

INSULATED RS485

Remote FW update

06/10/2015
Communication
MODBUS RTU and TCP protocols

Direct SI.MO.NE connection (cloud)

NTP support

DHCP and DNS client

06/10/2015
Operation

Communication gateway and concentrator

WEB monitoring

SI.MO.NE. extender/gateway

Local Data logger (USB stick)

06/10/2015
Digital outputs Supply

Ethernet

Digital inputs USB host

RS232 Power LED

Function/Host
RS485
selector

Analogue
USB function
inputs

06/10/2015
Gateway functionality
PC1 DANCE Device 1

PC2 MODBUS TCP MODBUS RTU Device 2


Communication Communication

Device 8
PCn

Up to 8 Modbus RTU devices can be connected


on RS485 port (only one to RS232).
Up to 4 TCP sockets are available

06/10/2015
Gateway functionality
This functionality allows to communicate towards
any MODBUS RTU devices from MODBUS TCP
applications and interfaces.
Using RS485, instead of RS232, up to 32 MODBUS
RTU devices can be connected on the same line.

No special configuration is required to add any


MODBUS RTU devices.

06/10/2015
WEB monitoring
Generator
PC1 DANCE
Controller

PC2 HTML MODBUS RTU


communication Communication

PCn

All recent SICES controllers are supported.


Some third party controllers are supported too.

06/10/2015
SI.MO.NE. extender/gateway
Router/Firewall
Generator
DANCE
Controller

All recent SICES controllers are supported.


Some third party controllers are supported too.

SI.MO.NE.

06/10/2015
SI.MO.NE. extender/gateway

DANCE allows similar functionality of REWIND


modules but without GPRS connection.
If INTERNET connection is available and
installation is fixed, DANCE allows to save GPRS
connection costs.

06/10/2015
Local Data Logger
Generator
DANCE
Controller
MODBUS RTU
Communication

USB STICK

All recent SICES controllers are supported.


Some third party controllers are supported too.

06/10/2015
Local Data Logger

DANCE polls the attached controller with a


programmable rate and records the data on USB
stick.
Record rate can be selected down to 10s.

06/10/2015
Local Data Logger
React. Oil Coolant
Gen. Gen. Gen. Gen. L1 Gen. L2 Gen. L3 Gen. Active Pw. P.F.+Lo Battery Mains Mains Mains Pw Cnt Fuel Press. . Temp.
Date Time N.Prog. Valid EngRun L1-L2 V L2-L3 V L3-L1 V A A A Freq. Hz Pw. kW kVar ad Type V L1-L2 V L2-L3 V L3-L1 V Kwh Level % Bar °C Mode
16/09/2015 00:00:08 64842 1 1 313 313 313 3.3 3.3 3.3 50.2 -1.1 1.2 -0.05 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:18 64843 1 1 313 313 314 3.3 3.3 3.3 50.3 -0.4 -0.9 -0.59 i 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:28 64844 1 1 313 313 313 3.3 3.3 3.3 50.2 1.5 -0.0 0.77 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:38 64845 1 1 313 313 313 3.3 3.3 3.3 50.2 -1.5 1.1 -0.35 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:48 64846 1 1 313 313 314 3.3 3.3 3.3 50.2 0.4 -1.2 -0.29 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:00:58 64847 1 1 313 313 313 3.3 3.3 3.3 50.3 1.1 0.5 0.74 i 28.2 242 253 247 23114256.0 3.9 47.3 OFF
16/09/2015 00:01:08 64848 1 1 313 313 313 3.3 3.3 3.3 50.3 -1.7 0.6 -0.61 c 28.2 242 253 247 23114256.0 3.9 47.3 OFF

Validity and Engine and


Generator Grid
Date/Time engine Powers controller
current voltage
running info

Record Generator Generator Energy


Battery
Number voltage frequency counter

06/10/2015
Operation

All four operation can be used at the


same time.
(it is possible a performance reduction in case of
heavy tasks)

06/10/2015
06/10/2015
Network configuration

Setting P.0514 to 255.255.255.255 enable DHCP for automatic


network configuration (in this case set P.801 with a plant name)

06/10/2015
SI.MO.NE. configuration

06/10/2015
MODBUS configuration

Up to 8 managed devices (for WEB page) can be connected. The


first one is used for SI.MO.NE.
For MODBUS TCP/RTU operation no configuration is required.

06/10/2015
Digital input configuration

Up to 8 digital input can be used and configured

06/10/2015
Digital output configuration

Up to 2 digital output can be used and configured

06/10/2015
GPS configuration

Dance has not GPS, but retains the possibility to set fixed
coordinates.

06/10/2015
Other configurations

Plant name is used in different applications. In case of DHCP, it is the


name used to register on the network, and thus the one to be used to
access the device

06/10/2015
DataLog configuration

In order to use a USB stick for data logging, a digital input with
function 13-DataLog Enable has to be configured. Operation is the
following:
- Insert USB stick
- Ground the digital input with function 13
- Recording
- Disconnect digital input from ground
- Remove USB stick

06/10/2015