Professional Documents
Culture Documents
Calculation
1. According to 2016 NYCECC (R402.4.1.2), the building or dwelling unit shall be tested and verified as
having an air leakage rate not exceeding three air changes per hour. Testing shall be conducted in
accordance with ASTM E 779 or ASTM E 1827 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
𝐶𝐹𝑀50×60
𝐴𝐶𝐻50 = 𝑉𝑜𝑙𝑢𝑚𝑒
≤3
2. According to 2016 NYCECC (R402.4.1.3), the optional testing procedure for buildings with two or
more dwelling units within the building thermal envelope.Each testing unit shall be tested and
verified as having an air leakage rate not exceeding 0.3 cubic feet per minute per square foot of
enclosure surface area within the testing area. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals), and shall be conducted in accordance with ASTM E779.
𝐶𝐹𝑀50
𝐴𝐿𝑅50 = ≤ 0.3
𝐸𝑆𝐴
ESA: Enclosure surface area, include sum of (i) each exterior wall in such testing unit, (ii) each
interior wall in such testing unit that abuts other testing unit(s), (iii) each ceiling in such testing unit
that abuts other testing unit(s) or abuts unconditioned space, and (iv) each floor in such testing unit
that abuts other testing unit(s) or abuts unconditioned space (sq ft)
During test