MFT button 1 action

(operating console)

MFT button 2 action


& MFT
(operating console)

ID Fan 1A Stop

ID Fan 1B Stop
&

PA Fan 1A Stop

PA Fan 1B Stop
&
SA Fan 1A Stop

SA Fan 1B Stop
&
2/3 Drum level HH
OR
2/3 Drum level LL OR Boiler trip
2/3 Pressure furnace HH

2/3 Pressure furnace LL


OR
3/6 Combustin bed temp.
>1050°C

3/6 Combustin bed temp.


OR
<680°C

Coal feeder 1A stop

Coal feeder 1B stop

Coal feeder 1C stop


&
Coal feeder 1D stop

ETS
ETS
Turbine over speed
trip(SOE

vacuum lower trip(SOE)

axial displacement
overstep trip(SOE))

shaft vibration
overstep trip(SOE)

lubrication oil press


lower trip(SOE)

fire resistant oil press


lower trip(SOE)

Generator Trip(SOE)
OR Turbine Trip
support bearing Temp. H
trip(SOE)

return oil temp of


support bearing H
trip(SOE)

Exhaust steam Temp. H


trip(SOE)

DEH interlock trip(SOE)

differential
expantion(SOE)

MFT

manual trip(SOE)

ETS buttom 1 action


& OR
ETS buttom 2 action

manual ETS (operation


station)