Professional Documents
Culture Documents
Earth Bar Calculation
Earth Bar Calculation
1
A=
where,
√[ T CAP . 10−4
t c α r ρr ][ln
( K o +T m )
( K o +T a ) ]
A = conductor cross section in sq. mm.
Ta = ambient temperature = 40 ºC
Tr = reference temperature = 20 ºC
Ko = 1 / α0 or (1 / αr) - Tr = 234 ºC
The area of cross section required for grounding conductor = 154 mm2
Proposed size for earthing conductor (50 x 5 Cu. Tape) = 250 mm2
Page