Professional Documents
Culture Documents
REX521 Conf 751802 ENk PDF
REX521 Conf 751802 ENk PDF
REX 521
Contents
1. About this manual ...................................................................15
1.1. General .......................................................................................15
1.2. Use of symbols ............................................................................15
1.3. Related documents .....................................................................16
1.4. Document revisions .....................................................................16
2. Safety information ...................................................................17
3. Introduction .............................................................................19
4. Standard configurations .........................................................25
4.1. HW version: Basic .......................................................................25
4.1.1. Standard configuration B01 ................................25
4.1.1.1. Features .............................................................25
4.1.1.2. Application ..........................................................26
4.1.2. Standard configuration B02 ................................28
4.1.2.1. Features .............................................................28
4.1.2.2. Application ..........................................................29
4.2. HW version: Medium ...................................................................31
4.2.1. Standard configuration M01 ...............................31
4.2.1.1. Features .............................................................31
4.2.1.2. Application ..........................................................32
4.2.2. Standard configuration M02 ...............................34
4.2.2.1. Features .............................................................34
4.2.2.2. Application ..........................................................35
4.3. HW version: High/Sensor ............................................................37
4.3.1. Standard configuration H01 (Sensor) .................37
4.3.1.1. Features .............................................................37
4.3.1.2. Application ..........................................................38
4.3.2. Standard configuration H02 ...............................40
4.3.2.1. Features .............................................................40
4.3.2.2. Application ..........................................................41
4.3.3. Standard configuration H03 ...............................43
4.3.3.1. Features .............................................................43
4.3.3.2. Application ..........................................................44
4.3.4. Standard configuration H04 ...............................46
4.3.4.1. Features .............................................................46
4.3.4.2. Application ..........................................................47
4.3.5. Standard configuration H05 ...............................49
4.3.5.1. Features .............................................................49
4.3.5.2. Application ..........................................................50
3
REX 521 Protection Relay 1MRS751802-MUM
4
1MRS751802-MUM Protection Relay REX 521
5
REX 521 Protection Relay 1MRS751802-MUM
6
1MRS751802-MUM Protection Relay REX 521
7
REX 521 Protection Relay 1MRS751802-MUM
8
1MRS751802-MUM Protection Relay REX 521
9
REX 521 Protection Relay 1MRS751802-MUM
10
1MRS751802-MUM Protection Relay REX 521
11
REX 521 Protection Relay 1MRS751802-MUM
12
1MRS751802-MUM Protection Relay REX 521
Copyrights
The information in this document is subject to change without notice and should not
be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for
any errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or
consequential damages of any nature or kind arising from the use of this document,
nor shall ABB Oy be liable for incidental or consequential damages arising from use
of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third
party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under alicense and
may be used, copied, or disclosed only in accordance with the terms of such license.
Copyright © 2006 ABB Oy
All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
13
14
1MRS751802-MUM Protection Relay REX 521
1.1. General
This document provides detailed information about the separate functions of the
protection relay REX 521 Revision G.
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
15
REX 521 Protection Relay 1MRS751802-MUM
16
1MRS751802-MUM Protection Relay REX 521
2. Safety information
Dangerous voltages can occur on the connectors, even though
the auxiliary voltage has been disconnected.
Non-observance can result in death, personal injury or
substantial property damage.
Only a competent electrician is allowed to carry out the electrical
installation.
National and local electrical safety regulations must always be
followed.
The frame of the device has to be carefully earthed.
17
18
1MRS751802-MUM Protection Relay REX 521
3. Introduction
This document provides descriptions of the standard configurations for REX 521.
Chapter 4. Standard configurations describes the features of the different standard
configurations one by one while Chapters 5 to 7 describe the signal routings and
functionality. A short introduction of the function blocks available in different
standard configurations of REX 521 is given in Chapter 8. Function block
descriptions. Chapter 9. Example substations, Chapter 10. Application examples,
Basic, Chapter 11. Application examples, Medium, and Chapter 12. Application
examples, High present different application examples.
The standard configurations available are presented in Table 3.-1. Note that in the
function block descriptions in the CD-ROM Technical Descriptions of Functions
(see Related documents), the ABB standard FB names are used instead of the IEC
or ANSI names.
Hardware (HW) versions for REX 521 are basic, medium, high and sensor. The
sensor variant of the standard configuration is indicated with the letter ‘S’ in the
Config. name parameter, for example H02S.
19
REX 521 Protection Relay 1MRS751802-MUM
Standard configurations B01 B02 M01 M02 H01a H02 H03 H04 H05 H06 H07 H08bc H09bc H50b H51b
ANSI
IEC FB name
device
symbol (CD-ROM)
number
Protection
3I> 51-1 NOC3Low x x x x x x x x x x x x x x
3I>> 51-2 NOC3High x x x x x x x x x x x x x x
3I>>> 51-3 NOC3Inst x x x x x x x x x x x x x
Io> 51N-1 NEF1Low x x xd x x x x x x
Io>> 51N-2 NEF1High x x xd x x x x x x
Io>>> 51N-3 NEF1Inst x x xd x x x
Io>-->e 67N-1 DEF2Low x x x x x x x x x
Io>>--> e 67N-2 DEF2High x x x x x x x x x
Io>>>-->e 67N-3 DEF2Inst x x x x x x
3I>--> 67-1 DOC6Low xf xf xf xf
3I>>--> 67-2 DOC6High xf xf xf xf
3U> 59-1 OV3Low x x x x x x x
3U>> 59-2 OV3High x x x x x x
3U< 27-1 UV3Low x x x x x x x
3U<< 27-2 UV3High x x x x x x
3I2f> 68 Inrush3 x x x x x x x x x x x x
Iub> 46 CUB3Low x x x x x x x x
3Ith> 49F TOL3Cab x x x x x x x x
O-->I 79 AR5Func x x x x x x x x
Uo> 59N-1 ROV1Low x x x x x x
Uo>> 59N-2 ROV1High x x x x x
Uo>>> 59N-3 ROV1Inst x x x x
f1 81-1 Freq1St1 x x x x x x x
f2 81-2 Freq1St2 x x x x
SYNC1 25-1 SCVCSt1 x x
Is2t n< 48 MotStart x x
3I() 46R PREV3 x x
I2> 46-1 NPS3Low x x
I2>> 46-2 NPS3High x
3I< 37-1 NUC3St1 x
FUSEF 60 FuseFail x x
3Ithdev> 49M/G/T Tol3Dev x x x x
U1U2<>_1 47-1 PSV3St1 x x x
Control functions
I<->O CB1 COCB1 COCB1 x x x x x x x x x x x x x x x
I<->O IND1 COIND1 COIND1 x x x x x x x x x x x x x x x
I<->O IND2 COIND2 COIND2 x x x x x x x x x x x x x x x
I<->O IND3 COIND3 COIND3 xg xg
20
1MRS751802-MUM Protection Relay REX 521
Standard configurations B01 B02 M01 M02 H01a H02 H03 H04 H05 H06 H07 H08bc H09bc H50b H51b
ANSI
IEC FB name
device
symbol (CD-ROM)
number
I<->O POS COLOCAT COLOCAT x x x x x x x x x x x x x x x
ALARM1-8 ALARM1-8 MMIALAR1-8 x x x x x x x x x x x x x x x
Measurement
3I 3I MECU3A x x x x x x x x x x x x x x x
Io Io MECU1A x x x x x x x x x x x x x x x
Uo Uo MEVO1A x x x x x x x x x x x x x
DREC DREC MEDREC x x x x x x x x x x x x x x x
3U 3U MEVO3A x x x x x x x x x x x
3U_B 3U_B MEVO3B x x
f f MEFR1 x x x x x x x x x x x
PQE PQE MEPE7 x x x x x x x x x x x
AI1 AI1 MEAI1 x x
Condition monitoring
CB wear1 CB wear1 CMBWEAR1 x x x x x x x x x x x x x x x
TCS1 TCS1 CMTCS1 x x x x x x x x x x x x x x x
MCS 3I MCS 3I CMCU3 x x x x x x x x x x x x x x x
MCS 3U MCS 3U CMVO3 x x x x x x x x x x x
TIME1 TIME1 CMTIME1 x x
Power quality monitoring
PQ 3Inf PQ 3Inf PQCU3H x x x x x x x x x x x x x x x
PQ 3Unf PQ 3Unf PQVO3H x x x x x x x x x x x
Standard
SWGRP SWGRP SWGRP x x x x x x x x x x x x x x x
a. H01 available only as sensor version
b. Not available as sensor version
c. VTs are used to measure phase-to-earth voltages, calculated phase-to-phase voltages are shown by 3U_B
d. Configured fixedly to the Io (1/5 A) channel or Ios if selected
e. Can be used as Io>, Io>> and Io>>> or Uo>, Uo>> and Uo>>> function block with some limitations
f. 3I>--> and 3I>>--> cannot be set to operate as 3I>, 3I>> or 3I>>>
g. Motor status indication
21
REX 521 Protection Relay 1MRS751802-MUM
22
1MRS751802-MUM Protection Relay REX 521
23
24
1MRS751802-MUM Protection Relay REX 521
4. Standard configurations
4.1.1.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Non-directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cables
• Three-phase transformer inrush and motor start-up current detector
• Supervision function for the energizing current input circuit
• Current waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
For more information about the features, refer to Chapter 8. Function block
descriptions.
25
REX 521 Protection Relay 1MRS751802-MUM
CBCM 0 I
3I 2f > 68
3I~harm R
I> 46
3 49F
CBFP 62 3I I0
LO 86
4.1.1.2. Application
The B01 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective short-circuit, time overcurrent and
earth-fault protection of radial isolated neutral networks, solidly earthed networks,
resistant earthed networks and resonant earthed networks.
For more detailed information, refer to the application examples of B01 in Section
10.1. Outgoing feeder, Basic B01, Section 10.2. Incoming feeder, Basic B01 and
Section 10.3. Transformer feeder, Basic B01.
26
Digital Input signals Input SWGRP s Function blocks Output SWGRP s Output signals Output relays
inputs
3I>
3I>> Master Trip Open LOGIC *) HSPO1
3I>>> (X4.2.3/4/1/2)
SWGRP Io> Trip 1
>1 >1
Io>>
Selector Reset 1 O/C Io>>> Lockout
3I> I<->O CB1 S
E/F Iub> HSPO1
OOPEN Q
Iub> 3Ith> 3I>
O/C OCLOSE Lockout
Lockoutreset
reset R Lockout Working
3Ith> CBFP 3I>>
E/F BS1 OPEN AOPEN
PQ 3Inf 3I>>>
Iub> BS2 START CLOSE ACLOSE 1 Lockout
Reset 2 Io> Trip 2
Terminal 3Ith> GROUP TRIP CLOSEENA
Io>>
connection PQ 3Inf RESET CBFP BINOPEN
O/C Io>>>
1MRS751802-MUM
Fig. 4.1.1.2.-1 Block diagram of the standard configuration B01 for REX 521
Interlocking_D 3Ith> MCS 3I 3Ith>
Logic input 3 MEAS_HI Alarm LED6
Interlocking_E
Interlocking 3 ALARM MCS 3I Alarm 1
scheme DI2
J> TCS1 DI3
Cab PQ 3Inf har DI4
Lockout Working CBFP PQ 3Inf I<->0 CB1 open PQ 3Inf cum DI5
BLOCK I<->0 CB1 close CB wear1 DI6
TRIGG HAR_HIGH
DOUBLE 3I>> (BS) START 3Ith> DI7
3I2f START RESET CUM_HIGH Alarm 2 Interlocking
DOUBLE 3I>>> GROUP TRIP MCS 3I
RESET CBFP TCS1
CU_ALARM PQ 3Inf har MEAS LO ALARM Alarm LED7
BS1 3I> PQ 3Inf cum MEAS HI ALARM
3I2f START BS1 3I>> CB wear1 DI3
BS1 3I>>> DI4
BS1 Io> BS2 3I> DI5
BS1 Io>> 3I2f START DI6
BS2 3I>>
BS1 Io>>> BS2 3I>>> DI7
BS1 Iub> BS2 Io> Lockout
BS2 Io>>
CB wear1 Alarm LED8
3I2f START BS2 Io>>>
BS2 Iub> TCS1
MCS 3I
BS 3Ith>
DI4
*) This logic disables the Open signal to HSPO1 DI5
if Open is selected by any multiplexers for DI6
DI7
PO1, PO2, PO3, SO1, SO2. DI8
27
A051928
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.1.2.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Non-directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cables
• Supervision function for the energizing current input circuit
• Current waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1...5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
28
1MRS751802-MUM Protection Relay REX 521
3I 2f> CBCM 0 I
68
3I~harm R
I> 46
3 49F
0 I 79 I0
3I
CBFP 62
LO 86
4.1.2.2. Application
The B02 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective short-circuit protection, time-
overcurrent protection, earth-fault protection and automatic reclosing. The
configuration can be used in different types of networks such as radial isolated
neutral networks, solidly earthed networks, resistant earthed networks and resonant
earthed networks.
For more detailed information about the configuration, refer to the application
examples of the standard configuration B02 in Section 10.4. Outgoing feeder, Basic
B02.
29
Digital Input signals Input SWGRPs Function blocks Output SWGRP s Output signals Output relays
30
inputs
Open LOGIC **)
3I>
3I>> Master Trip Ropen HSPO1
SWGRP 3I>>> (X4.2.3/4/1/2)
3I> O-->I Io> Trip 1 >1
O/C AR1 ROPEN >1
Reset 1 Io>> Lockout
Selector E/F AR2 RCLOSE
CBFP Io>>> HSPO1
Iub> AR3 SHOT1 S
O/C BS1 Iub> Q
3Ith> AR4 SHOT2 3I>
E/F BS2 START 3Ith> Lockout reset R Lockout Working
PQ 3Inf ARINH SHOT3 3I>>
Iub> GROUP TRIP
O-->I CBOPEN SHOT4 3I>>>
RESET CBFP
REX 521
Fig. 4.1.2.2.-1 Block diagram of the standard configuration B02 for REX 521
BINOPEN SHOT1 DI5
BINOPEN CB wear1 DI6
DOUBLE 3I>> BINCLOSE SHOT2
3I2f START BINCLOSE DI7
DOUBLE 3I>>> SHOT3
O-->I Active Lockout
SHOT4
BS1 3I> SHOT5 Alarm LED8
CB wear1
3I2f START BS1 3I>> TRDUE
TCS1
BS1 3I>>> TDDUE MCS 3I
AR1TRIP
BS1 Io> ACTIVE DI4
BS2 3I> AR2TRIP
BS1 Io>> BS2 3I>> AR3TRIP DI5
BS1 Io>>> O-->I Alarm 1 DI6
BS2 3I>>> AR4TRIP
BS1 Iub> DI7
BS2 Io> CBFAIL
DI8
BS2 Io>> DEFTRIP
3I2f START BS2 Io>>> LOCKOUT AR1TRIP
BS2 Iub> SHOT_ALARM AR2TRIP
BS 3Ith> AR3TRIP O-->I Alarm 2
AR4TRIP
*) NOTE! The trip and start signals from the protection function blocks CBFAIL **) This logic disables the Open signal to HSPO1
are routed directly to the auto-recloser (O->I) via the input switchgroups DEFTRIP if Open is selected by any multiplexers for
of the auto-recloser and are not shown in the diagram. 3I2f START LOCKOUT PO1, PO2, PO3, SO1, SO2.
SHOT_ALARM
1MRS751802-MUM
A051930
1MRS751802-MUM Protection Relay REX 521
4.2.1.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cables
• Supervision function for the energizing current input circuit
• Current waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Residual voltage measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
31
REX 521 Protection Relay 1MRS751802-MUM
CBCM 0 I
3I 2f> 68
3I~harm R
I> 46
3 49F
CBFP 62 3I I0
LO 86
U0
4.2.1.2. Application
The M01 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective short-circuit, time overcurrent and
directional earth-fault protection of radial isolated neutral networks, solidly earthed
networks, resistant earthed networks and resonant earthed networks.
For more detailed information about the configuration, refer to the application
examples of the standard configuration M01 in Chapter 11. Application examples,
Medium and Section 11.2. Incoming feeder, Medium M01.
32
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs
SWGRP
3I>
Reset 1 O/C 3I> I<->O CB1 3I>> Master Trip Open LOGIC *)
Selector HSPO1
E/F OOPEN 3I>>> (X4.2.3/4/1/2)
OCLOSE Trip 1
Iub> O/C CBFP Io>-->
3Ith> BS1 OPEN AOPEN >1 >1
E/F Io>>-->
PQ 3Inf BS2 START CLOSE ACLOSE Lockout
Iub> Io>>>-->
GROUP TRIP CLOSEENA S HSPO1
Reset 2 3Ith> Iub> Q
Terminal RESET CBFP BINOPEN 3I>
PQ 3Inf 3Ith> Lockout reset R Lockout Working
connection BINCLOSE 3I>>
O/C 3I>>
1MRS751802-MUM
Fig. 4.2.1.2.-1 Block diagram of the standard configuration M01 for REX 521
3I>>>
Interlocking RESET CBFP DI7
MCS 3I
Logic input 3 scheme I<->0 CB1 open DI8
CLOSEENA 3Ith> ALARM
I<->O CB1 3 I<->0 CB1 close
Interlocking_A & 3Ith> MEAS HI ALARM Alarm LED6
J>
Interlocking_B Alarm 1 DI2
Cab PQ 3Inf MCS 3I
Interlocking_C DI3
Interlocking_D TCS1
TRIGG HAR_HIGH DI4
Interlocking_E BLOCK (BS) PQ 3Inf har
RESET CUM_HIGH DI5
GROUP START I<->0 CB1 open PQ 3Inf cum
DI6
RESET TRIP I<->0 CB1 close CB wear1
Lockout Working DI7
CBFP 3Ith> Interlocking
CU_ALARM MCS 3I Alarm 2
DOUBLE 3I>> TCS1
3I2f START MEAS LO ALARM Alarm LED7
DOUBLE 3I>>> PQ 3Inf har MEAS HI ALARM
PQ 3Inf cum DI3
BS1 3I> CB wear1 DI4
3I2f START BS1 3I>> DI5
BS1 3I>>> 3I2f START DI6
BS1 Io>--> BS2 3I>
DI7
BS1 Io>>--> BS2 3I>>
Lockout
BS1 Io>>>--> BS2 3I>>>
BS1 Iub> BS2 Io>-->
CB wear1 Alarm LED8
BS2 Io>>-->
BS2 Io>>>--> TCS1
BS2 Iub> *) This logic disables the Open signal to HSPO1 MCS 3I
3I2f START DI4
BS 3Ith> if Open is selected by any multiplexers for DI5
PO1, PO2, PO3, SO1, SO2. DI6
DI7
DI8
33
A051932
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.2.2.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cables
• Supervision function for the energizing current input circuit
• Current waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Residual voltage measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1...5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
34
1MRS751802-MUM Protection Relay REX 521
CBCM 0 I
3I 2f> 68
3I~harm R
I> 46
3 49F
0 I 79 I0
3I
CBFP 62
U0
LO 86
4.2.2.2. Application
The M02 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective short-circuit protection, time-
overcurrent protection, directional earth-fault protection and automatic reclosing.
The configuration can be used in different types of networks such as of radial
isolated neutral networks, solidly earthed networks, resistant earthed networks and
resonant earthed networks.
For more detailed information about the configuration, refer to the application
examples of the standard configuration M02 in Section 11.3. Outgoing feeder,
Medium M02.
35
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
36
inputs
Open LOGIC **)
3I>
3I>> Master Trip Ropen HSPO1
SWGRP 3I>>> (X4.2.3/4/1/2)
Io>--> Trip 1
O/C 3I> O-->I >1 >1
Reset 1 Io>>-->
Selector E/F AR1 ROPEN Lockout
Iub> AR2 RCLOSE
Io>>>-->
O/C CBFP S HSPO1
3Ith> AR3 SHOT1 Iub> Q
E/F BS1 3I>
PQ 3Inf BS2 AR4 SHOT2 3Ith> Lockout reset R Lockout Working
Iub> START 3I>>
O-->I ARINH SHOT3
REX 521
Fig. 4.2.2.2.-1 Block diagram of the standard configuration M02 for REX 521
START MCS 3I Alarm 2
GROUP OPEN ALARM
MEAS LO ALARM Alarm LED7
Lockout Working RESET TRIP BINOPEN TCS1
CBFP MEAS HI ALARM
BINCLOSE PQ 3Inf har
CU_ALARM DI3
PQ 3Inf cum DI4
TCS1 SHOT1 CB wear1
DOUBLE 3I>> SHOT2 DI5
3I2f START PQ 3Inf
DOUBLE 3I>>> TCSSTATE DI6
TRIGG HAR_HIGH SHOT3
BS ALARM O-->I Active DI7
RESET CUM_HIGH SHOT4 Lockout
BS1 3I> MCS 3I SHOT5
3I2f START BS1 3I>> ALARM TRDUE
CB wear1 Alarm LED8
BS1 3I>>> TDDUE TCS1
AR1TRIP
BS1 Io>--> BS2 3I> ACTIVE MCS 3I
AR2TRIP
BS1 Io>>--> BS2 3I>> DI4
AR3TRIP
BS1 Io>>>--> BS2 3I>>> O-->I Alarm 1 DI5
AR4TRIP
BS1 Iub> BS2 Io>--> DI6
CBFAIL
BS2 Io>>--> DI7
DEFTRIP DI8
3I2f START BS2 Io>>>--> LOCKOUT
BS2 Iub> AR1TRIP
SHOT_ALARM AR2TRIP
BS 3Ith>
AR3TRIP O-->I Alarm 2
AR4TRIP
*) NOTE! The trip and start signals from the protection function blocks CBFAIL **) This logic disables the Open signal to HSPO1
are routed directly to the auto-recloser (O->I) via the input switchgroups DEFTRIP if Open is selected by any multiplexers for
of the auto-recloser and are not shown in the diagram. 3I2f START LOCKOUT PO1, PO2, PO3, SO1, SO2.
SHOT_ALARM
1MRS751802-MUM
A051934
1MRS751802-MUM Protection Relay REX 521
4.3.1.1. Features
• Three-phase directional overcurrent protection with two stages
• Three-phase non-directional overcurrent protection with one stage
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cable
• Synchro-check/voltage-check function with one stage
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase-to-earth voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1…5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
37
REX 521 Protection Relay 1MRS751802-MUM
TCS1
3I> 50
CBCM 0 I
I 0> 67N
3I~harm R
3I 2f> 68
3U~harm
I> 46
3I I0 P
3 49F
SYNC 25
3U U Q
0
0 I 79
CBFP */62 f pf E
LO 86
4.3.1.2. Application
The H01 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective directional and non-directional short-
circuit protection, directional time-overcurrent protection, directional earth-fault
protection and automatic reclosing with synchro- and voltage-check functionality.
For more detailed information about the standard configuration, refer to the
application example of the standard configuration H01 in Section 12.1. Incoming
feeder, High H01.
38
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs Open LOGIC **)
SWGRP
REX 521 Master Trip Ropen HSPO1
O/C Io> I<->O CB1
Trip 1 (X4.2.3/4/1/2)
E/F OPEN OOPEN 3I>-->
Reset 1 >1 >1
Iub> O/C OPENENA OCLOSE 3I>>--> Lockout
3Ith> E/F CBFP CLOSE AOPEN 3I>>> HSPO1
Selector BACTRL 3I>--> S
PQ 3Inf Iub> CLOSEENAACLOSE Io>--> Q
O-->I BS1 START BINOPEN 3I>>--> Io>>-->
3Ith> Lockout reset R Lockout Working
PQ 3Unf BS2 TRIP BINCLOSE 3I>>> Io>>>-->
Reset 2 PQ 3Inf GROUP CBFP
O-->I I<->O IND1 Io>--> Iub> 1 Lockout
RESET 3I>-->
Terminal PQ 3Unf BINOPEN Io>>--> 3Ith>
O/C 3I>>-->
connection Io>> BINCLOSE Io>>>-->
Group E/F 3I>>>
X4.2.5/6 Iub> Trip 2
DI1 Iub> I<->O IND2 Io>-->
X4.2.6/7 BS1 3I>--> 3Ith> PO1 (X4.1.12/13)
3Ith>
1MRS751802-MUM
Fig. 4.3.1.2.-1 Block diagram of the standard configuration H01 for REX 521
PQ 3Unf har SHOT5 DI7
RESET CBFP MCS 3I PQ 3Unf cum TRDUE Interlocking
DOUBLE 3I>>--> CU_ALARM ALARM TDDUE O-->I Active
3I2f START ACTIVE MEAS LO ALARM Alarm LED7
DOUBLE 3I>>> O-->I MCS 3U
AR1 ROPEN MEAS HI ALARM
AR2 RCLOSE ALARM DI3
3I2f START BS1 3I>--> AR3 DEFTRIP AR1TRIP O-->I Alarm 1 DI4
BS1 3I>>--> AR4 PQ 3Inf AR2TRIP
LOCKOUT DI5
BS1 3I>>> ARINH TRIGG HAR_HIGH AR3TRIP DI6
BS1 Io>--> CBOPEN RESET CUM_HIGH AR4TRIP DI7
BS2 3I>--> CBCLOSE AR1TRIP Lockout
BS1 Io>>--> CBFAIL
BS2 3I>>--> ON PQ 3Unf AR2TRIP
BS1 Io>>>--> DEFTRIP
BS2 3I>>> RESET TRIGG HAR_HIGH AR3TRIP CB wear1 Alarm LED8
BS1 Iub> LOCKOUT
BS2 Io>--> RESET CUM_HIGH AR4TRIP TCS1
BS SYNC1 SHOT_ALARM
BS2 Io>>--> SYNC CBFAIL O-->I Alarm 2 MCS 3I
BS2 Io>>>--> COMMAND DEFTRIP MCS 3U
3I2f START DI5
BS2 Iub> GROUP LOCKOUT
BS 3Ith> BLOCK SC_OK SHOT_ALARM DI6
DI7
DI8
*) NOTE! The trip and start signals from the protection function blocks 3I2f START
are routed directly to the auto-recloser (O->I) via the input switchgroups
**) This logic disables the Open signal to HSPO1
of the auto-recloser and are not shown in the diagram.
if Open is selected by any multiplexers for
PO1, PO2, PO3, SO1, SO2.
39
A051936
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.3.2.1. Features
• Three-phase directional overcurrent protection with two stages
• Three-phase non-directional overcurrent protection with two stages
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Underfrequency or overfrequency protection with one stage
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cables
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1…5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
40
1MRS751802-MUM Protection Relay REX 521
TCS
3I > 50/51
CBCM 0 I
I0 > 67N
3I~harm R
f</f> 81U/81O
3U~harm
3I2f> 68
I> 46
3 49F 3I I0 P
0 I 79
3U U0 Q
CBFP */62
LO 86
f pf E
REX 521 H02
A051937
4.3.2.2. Application
The H02 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective directional and non-directional short-
circuit protection, directional and non-directional time-overcurrent protection,
directional earth-fault protection and automatic reclosing.
For more detailed information about the standard configuration, refer to the
application example of the standard configuration H02 in Section 12.2. Incoming
feeder, High H02.
41
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
42
inputs
REX 521 Open LOGIC **)
SWGRP 3I>-->
Io> I<->O CB1 3I>>-->
O/C OPEN OOPEN Master Trip Ropen HSPO1
3I>
E/F OPENENA OCLOSE 3I>>
Iub> O/C Trip 1 (X4.2.3/4/1/2)
CBFP CLOSE AOPEN Io>--> >1
Reset 1 3Ith> E/F BACTRL
>1
CLOSEENAACLOSE Io>>--> Lockout
Selector PQ 3Inf Iub> BS1 START BINOPEN HSPO1
O-->I 3Ith> BS2 TRIP Io>>>--> S
BINCLOSE 3I>--> Q
PQ 3Unf PQ 3Inf GROUP CBFP Iub>
3I>>--> Lockout reset R Lockout Working
f1 O-->I RESET I<->O IND1 3Ith>
3I>
REX 521
Fig. 4.3.2.2.-1 Block diagram of the standard configuration H02 for REX 521
Cab MCS 3I
DOUBLE 3I>>--> DI6
3I2f START CBFP MCS 3U TCS1 I<->0 CB1 open
DOUBLE 3I>> DI7
BLOCK START ALARM PQ 3Inf har I<->0 CB1 close Alarm 2
Interlocking
GROUP TRIP PQ 3Inf cum 3Ith>
RESET CBFP PQ 3Inf CB wear1 MCS 3I MEAS LO ALARM Alarm LED7
3I2f START BS1 3I>--> CU_ALARM MCS 3U TCS1
TRIGG HAR_HIGH MEAS HI ALARM
BS1 3I>>--> RESET CUM_HIGH
PQ 3Unf har PQ 3Inf har DI3
BS1 3I> BS2 3I>--> f1 PQ 3Unf cum PQ 3Inf cum DI4
BS1 3I>> BS2 3I>>--> f< PQ 3Unf CB wear1 SHOT1 DI5
BS1 Io>--> BS2 3I> f> MCS 3U SHOT2
TRIGG HAR_HIGH DI6
BS1 Io>>--> BS2 3I>> PQ 3Unf har SHOT3 DI7
RESET CUM_HIGH PQ 3Unf cum
BS1 Io>>>--> BS2 Io>--> df/dt< SHOT4 Lockout
BS1 Iub> BS2 Io>>--> df/dt> O-->I SHOT5
BS2 Io>>>--> AR1 ROPEN O-->I Active CB wear1 Alarm LED8
BS1 f1 AR2
TRDUE
BS2 Iub> RCLOSE TCS1
BS1 START1 AR3 TDDUE
DEFTRIP MCS 3I
3I2f START BS 3Ith> BS2 TRIP1 AR4 ACTIVE
LOCKOUT MCS 3U
BS2 f1 GROUP START2 ARINH AR1TRIP O-->I Alarm 1 DI5
RESET TRIP2 CBOPEN
*) NOTE! The trip and start signals from the protection function blocks AR2TRIP DI6
CBCLOSE DI7
are routed directly to the auto-recloser (O->I) via the input switchgroups ON AR3TRIP
AR4TRIP DI8
of the auto-recloser and are not shown in the diagram. RESET AR1TRIP
CBFAIL
DEFTRIP AR2TRIP
LOCKOUT AR3TRIP **) This logic disables the Open signal to HSPO1
SHOT_ALARM AR4TRIP
if Open is selected by any multiplexers for
CBFAIL
DEFTRIP PO1, PO2, PO3, SO1, SO2.
O-->I Alarm 2
LOCKOUT
SHOT_ALARM
3I2f START
1MRS751802-MUM
A051938
1MRS751802-MUM Protection Relay REX 521
4.3.3.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cable
• Synchro-check/voltage-check function with one stage
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements 1
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1…5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
43
REX 521 Protection Relay 1MRS751802-MUM
TCS
I0 > 67N
CBCM 0 I
3I 2f> 68
3I~harm R
I> 46
3U~harm
3 49F
25 3I I0 P
SYNC
0 I 79
3U U0 Q
CBFP */62
LO 86 f pf E
REX 521 H03
A051939
4.3.3.2. Application
The H03 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, directional earth-fault
protection and automatic reclosing with synchro- and voltage-check functionality.
For more detailed information about the standard configuration, refer to the
application example of the standard configuration H03 in Section 12.3. Bus
sectionalizer, High H03.
44
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs
Open LOGIC **)
SWGRP REX 521
O/C 3I> I<->O CB1 Master Trip Ropen HSPO1
E/F OPEN (X4.2.3/4/1/2)
Reset 1 OPENENA OOPEN 3I> Trip 1
Iub> O/C BS1 CBFP >1 >1
3Ith> E/F BS2 START CLOSE OCLOSE 3I>>
Selector
PQ 3Inf Iub> GROUP TRIP CLOSEENA AOPEN 3I>>> Lockout
BINOPEN ACLOSE S
PQ 3Unf 3Ith> RESET CBFP 3I> Io>--> Q HSPO1
O-->I PQ 3Inf BINCLOSE 3I>> Io>>--> R Lockout Working
3I>> Lockout reset
Reset 2 3I>>>
PQ 3Unf I<->O IND1 Io>>>-->
O-->I Io>--> Iub> 1 Lockout
Terminal O/C BS1 CBFP BINOPEN
BINCLOSE 3I> Io>>--> 3Ith>
connection Group E/F BS2 BSOUT 3I>> Io>>>-->
X4.2.5/6 Iub> GROUP START I<->O IND2
DI1 3I>>> Iub> Trip 2
3Ith> BS1 3I> DOUBLE TRIP BINOPEN
X4.2.6/7 DI2 Io>--> 3Ith>
1MRS751802-MUM
Fig. 4.3.3.2.-1 Block diagram of the standard configuration H03 for REX 521
Interlocking_C AR2 RCLOSE DI7
MCS 3U PQ 3Unf har SHOT5
Interlocking_D AR3 DEFTRIP Interlocking
AR4 ALARM PQ 3Unf cum TRDUE
Interlocking_E LOCKOUT
ARINH TDDUE O-->I Active MEAS LO ALARM Alarm LED7
CBOPEN PQ 3Inf ACTIVE MEAS HI ALARM
Lockout Working CBCLOSE TRIGG HAR_HIGH DI3
ON RESET CUM_HIGH DI4
AR1TRIP O-->I Alarm 1
DOUBLE 3I>> RESET DI5
3I2f START PQ 3Unf AR2TRIP
DOUBLE 3I>>> AR3TRIP DI6
SYNC TRIGG HAR_HIGH DI7
COMMAND RESET CUM_HIGH AR4TRIP
AR1TRIP Lockout
3I2f START BS1 3I> GROUP CBFAIL
DEFTRIP AR2TRIP
BS1 3I>> BLOCK SC_OK CB wear1 Alarm LED8
BS2 3I> LOCKOUT AR3TRIP
BS1 3I>>> TCS1
BS2 3I>> SHOT_ALARM AR4TRIP
BS1 Io>--> MCS 3I
BS1 Io>>--> BS2 3I>>> CBFAIL O-->I Alarm 2
MCS 3U
BS1 Io>>>--> BS2 Io>--> DEFTRIP DI5
BS1 Iub> BS2 Io>>--> LOCKOUT DI6
BS SYNC1 BS2 Io>>>--> SHOT_ALARM DI7
BS2 Iub>
DI8
3I2f START BS 3Ith>
3I2f START
*) NOTE! The trip and start signals from the protection function blocks **) This logic disables the Open signal to HSPO1
are routed directly to the auto-recloser (O->I) via the input switchgroups if Open is selected by any multiplexers for
of the auto-recloser and are not shown in the diagram. PO1, PO2, PO3, SO1, SO2.
45
A051940
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.3.4.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase directional overcurrent protection with one stage
• Underfrequency or overfrequency protection with one stage
• Three-phase transformer inrush and motor start-up current detector
• Directional earth-fault protection with three stages
• Non-directional earth-fault protection with three stages1
• Phase discontinuity protection for three phases
• Three-phase thermal protection for cable
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1…5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
1. The function blocks I0>, I0>>, I0>>> are fixedly configured to the I0 (1/5A)
channel.
46
1MRS751802-MUM Protection Relay REX 521
3I> 67 TCS1
CBCM 0 I
I0 > 67N
3I~harm R
I0 > 50N/51N
3U~harm
f</f> 81U/81O
3I2f> 68
I> 46
3 49F 3I I P
0
0 I 79
3U U0 Q
CBFP */62
LO 86 f pf E
REX 521 H04
A051941
4.3.4.2. Application
The H04 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, directional and non-
directional earth-fault protection and automatic reclosing.
For more detailed information about the standard configuration, refer to the
application example of the standard configuration H04 in Section 12.4. Outgoing
feeder, High H04.
47
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
48
inputs SWGRP Open LOGIC **)
Master Trip
O/C REX 521
Ropen
dir E/F 3I> 3I> HSPO1
3I>
Iub> O/C (X4.2.3/4/1/2)
3I>> Trip 1
3Ith> dir E/F >1 >1
Reset 1 BS1 CBFP 3I>>>
PQ 3Inf Iub> CBFP
BS2 START BACTRL START Io>--> Lockout
O-->I 3Ith> 3I>
Selector GROUP TRIP BS1 TRIP Io>>--> S
PQ 3Unf PQ 3Inf 3I>> Q HSPO1
RESET CBFP BS2 CBFP Io>>>-->
E/F O-->I 3I>>> Lockout reset R Lockout Working
GROUP Iub>
f1 PQ 3Unf 3I>> Io>--> 3Ith>
REX 521
Reset 2 RESET
E/F 3I> Io>>--> Io> 1 Lockout
Terminal O/C f1 BS1 CBFP I<->O CB1 3I>> Io>>>--> Io>>
connection E/F BS2 BSOUT OPEN 3I>>> Iub> Io>>>
Group GROUP START Io>--> 3Ith> 3I>-->
Iub> BS1 3I> OPENENA OOPEN
X4.2.5/6 DI1 DOUBLE TRIP Io>>--> Io> f1 Trip 1 PO1 (X4.1.12/13)
3Ith> BS1 3I>> CLOSE OCLOSE
X4.2.6/7 DI2 BS2 3I> RESET CBFP Io>>>--> Io>>
f1 BS1 3I>>> CLOSEENA AOPEN f1 Trip 2
X4.2.8/9 DI3 Blocking 1 BS2 3I>> Iub> Io>>>
BS1 Io>--> 3I>>> BINOPEN ACLOSE PO2 (X4.1.14/15)
X4.2.9/10 DI4 BS2 3I>>> 3Ith> 3I>--> Trip 2
BS1 Io>>--> BINCLOSE
X4.2.11/12 BS2 Io>--> Io> f1 Trip 1
DI5 BS1 Io>>>--> PO3 (X4.1.17/18)
X4.2.13/14 BS2 Io>>--> BS1 CBFP I<->O IND1 Io>> f1 Trip 2
DI6 BS1 Iub>
X4.2.15/16 BS2 Io>>>--> BS2 BSOUT BINOPEN Io>>>
DI7 BS1 Io> Trip 3 SO1 (X4.1.8/7/6)
X4.2.17/18 BS2 Iub> GROUP START BINCLOSE 3I>-->
DI8 BS1 Io>>
X3.1.1/2 BS 3Ith> DOUBLE TRIP f1 Trip 1
DI9 BS1 Io>>> I<->O IND2
BS2 Io> RESET CBFP f1 Trip 2 SO2 (X4.1.10/11/9)
BS1 3I>--> BINOPEN
BS2 Io>> External trip
BS1 f1 Io> BINCLOSE
Blocking 2 BS2 Io>>>
BS2 3I>--> I<->O POS 3I> Trip 4
BS2 f1 3I>>
BINLOCAL Alarm LED1
DREC trig CBFP 3I>>> 3I> Start
BINREMOTE
BACTR 3I> Trip
PQ 3Inf trig Io>--> 3I>
LBS1 START 3I Trip 5 3I>> Start
Io>>--> 3I>>
PQ 3Unf trig BS2 TRIP IL1 3I>> Trip
Io>>>--> 3I>>>
GROUP CBFP IL2 Iub> 3I>>> Start
O-->I INH Io>-->
RESET IL3 3Ith> 3I>>> Trip
O-->I ON Io>>-->
Io>> Io Io> Io>>>--> 3i>--> Start
O-->I Io Io>> Iub> 3I> 3I>--> Trip
O-->I Ext. start AR1 Io>>> 3Ith> 3I>>
Uo Alarm LED2
CBFP 3I>--> Io> 3I>>> Io>--> Start
O-->I Ext. trip AR2 Uo
BACTRL START f1 Trip 1 Io>> Io>--> Io>--> Trip
AR3 *)
BS1 TRIP f1 Trip 2 Io>>> Io>>--> Io>>--> Start
AR4 IL1
DREC
Io>--> BS2 CBFP 3I>--> Io>>>--> Io>>--> Trip
BACTRL IL2 Iub> Io>>>--> Start
Io>>--> GROUP f1 Trip 1
Master trip IL3 f1 Trip 2 3Ith> Io>>>--> Trip
Master trip Io>>>--> RESET
Io Io>
External trip Io>>> Iob CBFP
External trip Io>>
Lockout reset Uo Io>>>
Lockout reset U12 3I>--> Alarm LED3
Remote CBFP Io> Start
U23 RCLOSE
BACTRL START Close Io> Trip
Close enable U31 1
BS1 TRIP CLOSE Io>> Start
Open BI1 Start 3I>
I<->O CB1 BS2 CBFP Open Io>> Trip
Protection Relay
Fig. 4.3.4.2.-1 Block diagram of the standard configuration H04 for REX 521
Interlocking_C BS1 CBFP OPEN ALARM Alarm 2
BS2 START PQ 3Inf har I<->0 CB1 close Interlocking
Interlocking_D BINOPEN
GROUP TRIP PQ 3Inf cum 3Ith>
Interlocking_E BINCLOSE
RESET CBFP CB wear1 MCS 3I MEAS LO ALARM Alarm LED7
TCS1 MCS 3U TCS1 MEAS HI ALARM
Lockout Working Io>> TCSSTATE PQ 3Unf har PQ 3Inf har DI3
SHOT1
BS ALARM PQ 3Unf cum PQ 3Inf cum DI4
SHOT2
BS1 CBFP CB wear1 SHOT3 DI5
DOUBLE 3I>> MCS 3I
BS2 START MCS 3U DI6
3I2f START DOUBLE 3I>>> ALARM SHOT4
GROUP TRIP PQ 3Unf har DI7
DOUBLE 3I>-> SHOT5
RESET CBFP PQ 3Unf cum Lockout
MCS 3U TRDUE
3I2f START Io>>> ALARM TDDUE O-->I Active CB wear1 Alarm LED8
BS1 3I>
ACTIVE TCS1
BS1 3I>> BS2 3I> PQ 3Inf
BS1 3I>>> BS1 CBFP TRIGG HAR_HIGH MCS 3I
BS2 3I>>
BS1 Io>--> BS2 START RESET CUM_HIGH AR1TRIP O-->I Alarm 1 MCS 3U
BS2 3I>>>
BS1 Io>>--> GROUP TRIP AR2TRIP DI5
BS2 Io>-->
BS1 Io>>>--> RESET CBFP PQ 3Unf AR3TRIP DI6
BS2 Io>>-->
BS1 Iub> AR4TRIP DI7
BS2 Io>>>--> TRIGG HAR_HIGH
BS1 Io> f1 AR1TRIP DI8
BS2 Iub> RESET CUM_HIGH CBFAIL
BS1 Io>> f< AR2TRIP
BS 3Ith> DEFTRIP
BS1 Io>>> f> O-->I AR3TRIP
BS2 Io> LOCKOUT
BS1 3I>--> BS2 Io>> AR1 ROPEN AR4TRIP
AR2
SHOT_ALARM
BS1 f1 BS2 Io>>> df/dt< RCLOSE CBFAIL O-->I Alarm 2
BS2 3I>--> df/dt> AR3 DEFTRIP DEFTRIP
3I2f START
BS2 f1 AR4 LOCKOUT LOCKOUT
ARINH
BS1 START1 SHOT_ALARM
CBOPEN
*) NOTE! The trip and start signals from the protection function blocks BS2 TRIP1 **) This logic disables the Open signal to HSPO1
CBCLOSE
are routed directly to the auto-recloser (O->I) via the input switchgroups GROUP START2 if Open is selected by any multiplexers for
ON 3I2f START
RESET TRIP2
of the auto-recloser and are not shown in the diagram. RESET PO1, PO2, PO3, SO1, SO2.
1MRS751802-MUM
A051942
1MRS751802-MUM Protection Relay REX 521
4.3.5.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Non-directional earth-fault protection with three stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Residual overvoltage protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Three-phase thermal overload protection for devices
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
49
REX 521 Protection Relay 1MRS751802-MUM
TCS
I 0> 50N/51N
CBCM 0 I
3I2f 68
3I~harm R
U 0> 59N
3U~harm
3U> 59
3I I0 P
3U< 27
CBFP */62
3U U0 Q
LO 86
3 49 f pf E
A051943
4.3.5.2. Application
The H05 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, non-directional earth-fault
protection, overvoltage protection, undervoltage protection and residual overvoltage
protection.
For more detailed information about the configuration, refer to the application
example of the standard configuration H05 in Section 12.5. Incoming feeder, High
H05/H50.
50
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs
SWGRP Master Trip Open LOGIC *)
REX 521 HSPO1
O/C (X4.2.3/4/1/2)
3I> I<->O CB1 Trip 1
E/F 3I> >1 >1
O/V OPEN
3I>>
Reset 1 O/C OPENENA OOPEN 3I>
Lockout
U/V BS1 CBFP 3I>>> S
E/F CLOSE OCLOSE 3I>> HSPO1
PQ 3Inf BS2 START Io> Q
Selector O/V CLOSEENA AOPEN 3I>>> Lockout Working
RO/V GROUP TRIP Io>> Lockout reset R
U/V BINOPEN ACLOSE Io>
PQ 3Unf RESET CBFP Io>>>
PQ 3Inf BINCLOSE 3I> Io>>
3Ithdev> 3U> 1 Lockout
Reset 2 RO/V 3I>> 3I>> Io>>> 3U>>
PQ 3Unf I<->O IND1
3I>>> 3U> 3U<
3Ithdev> BINOPEN Io> 3U>> 3U<<
Terminal O/C CBFP
BS1 BINCLOSE Io>> 3U< Uo>
connection Group E/F PO1 (X4.1.12/13)
BS1 3I> BS2 BSOUT Io>>> 3U<< Uo>>
X4.2.5/6 DI1 O/V I<->O IND2
BS1 3I>> GROUP START 3U> Uo> Uo>>>
X4.2.6/7 DI2 U/V BS2 3I> DOUBLE TRIP BINOPEN
1MRS751802-MUM
Fig. 4.3.5.2.-1 Block diagram of the standard configuration H05 for REX 521
Interlocking_C MCS 3I CB wear1 MCS 3I MEAS LO ALARM Alarm LED7
Interlocking_D MCS 3U TCS1 MEAS HI ALARM
Uo> ALARM
Interlocking_E PQ 3Unf har PQ 3Inf har DI3
BS1 PQ 3Unf cum PQ 3Inf cum DI4
BS2 MCS 3U CB wear1
Lockout Working ALARM DI5
GROUP START MCS 3U DI6
RESET TRIP PQ 3Unf har DI7
PQ 3Inf PQ 3Unf cum
DOUBLE 3I>> Lockout
3I2f START Uo>> TRIGG HAR_HIGH
DOUBLE 3I>>>
RESET CUM_HIGH CB wear1 Alarm LED8
BS1
BS2 3I2f START TCS1
3I2f START BS1 3I> PQ 3Unf
START MCS 3I
BS1 3I>> GROUP TRIGG HAR_HIGH
BS2 3I> MCS 3U
BS1 3I>>> RESET TRIP RESET CUM_HIGH
BS2 3I>> DI5
BS1 Io>
DI6
BS1 Io>> BS2 3I>>> Uo>>>
3Ithdev> DI7
BS1 Io>>> BS2 Io>
BS1 DI8
BS1 3U> BS2 Io>> 3
BS1 3U>> BS2 Io>>> BS2 J>
BS1 3U< BS2 3U> GROUP START Dev
BS1 3U<< RESET TRIP CBFP *) This logic disables the Open signal to HSPO1
BS2 3U>> if Open is selected by any multiplexers for
BS1 Uo>
BS2 3U< BLOCK START
BS1 Uo>> PO1, PO2, PO3, SO1, SO2.
BS1 Uo>>> BS2 3U<< TRIP
BS2 Uo> RESET CBFP
3I2f START
BS2 Uo>>
BS2 Uo>>>
BS 3Ithdev>
51
A051944
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.3.6.1. Features
• Three-phase non-directional overcurrent protection with two stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Residual overvoltage protection with three stages
• Underfrequency or overfrequency protection with two stages
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
52
1MRS751802-MUM Protection Relay REX 521
TCS
U 0> 59N
CBCM 0 I
3U> 59
3I~harm R
3U< 27
3U~harm
f</f> 81U/81O
3I I0 P
CBFP 62
LO 86 U0
3U Q
f pf E
REX 521 H06
A051945
4.3.6.2. Application
The H06 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, overvoltage protection,
undervoltage protection, residual overvoltage protection, underfrequency protection
and overfrequency protection.
For more detailed information about the standard configuration, refer to the
application example of the standard configuration H06 in Section 12.6.
Measurement cubicle, High H06.
53
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
54
inputs REX 521
SWGRP 3I> I<->O CB1
O/C OPEN Master Trip Open LOGIC *) HSPO1
O/V OPENENA OOPEN (X4.2.3/4/1/2)
BS1 CBFP Trip 1
Reset 1 U/V CLOSE OCLOSE
BS2 START 3I> >1 >1
RO/V O/C CLOSEENA AOPEN
Selector GROUP TRIP 3I>> Lockout
Freq O/V BINOPEN ACLOSE
RESET CBFP 3U> HSPO1
PQ 3Inf U/V BINCLOSE S
3I> 3U>> Q
PQ 3Unf RO/V 3I>>
I<->O IND1 3I>> 3U< Lockout reset R Lockout Working
Freq
REX 521
df/dt< DI2
f2 Start1
df/dt> DI3
f2 Start2
Logic input 1 DI4
CB wear1
OPEN ALARM DI5
BS1 START1 BSOUT DI6
Logic input 2 Interlock- BS2 TRIP1 BINOPEN 3I>>
BINCLOSE DI7
ing GROUP START2 DI8
Logic input 3 scheme CLOSEENA RESET TRIP2
TCS1 I<->0 CB1 open
I<->O CB1 I<->0 CB1 close Alarm 1 MEAS HI ALARM Alarm LED6
Interlocking_A f2 TCSSTATE
& MCS 3I DI2
Interlocking_B f< BS ALARM
f> TCS1 DI3
Interlocking_C
Fig. 4.3.6.2.-1 Block diagram of the standard configuration H06 for REX 521
PQ 3Inf har I<->0 CB1 open DI4
Interlocking_D MCS 3I Alarm 2
PQ 3Inf cum I<->0 CB1 close DI5
Interlocking_E df/dt< ALARM CB wear1 MCS 3I DI6
df/dt> DI7
MCS 3U TCS1
Lockout Working MCS 3U PQ 3Unf har Interlocking
PQ 3Inf har
BS1 START1 ALARM PQ 3Unf cum PQ 3Inf cum
BS2 TRIP1 MEAS LO ALARM Alarm LED7
CB wear1
GROUP START2 PQ 3Inf MEAS HI ALARM
MCS 3U
RESET TRIP2 TRIGG HAR_HIGH DI3
PQ 3Unf har
RESET CUM_HIGH DI4
PQ 3Unf cum
DI5
DI6
PQ 3Unf
DI7
TRIGG HAR_HIGH
Lockout
RESET CUM_HIGH
CB wear1 Alarm LED8
TCS1
*) This logic disables the Open signal to HSPO1 MCS 3I
MCS 3U
if Open is selected by any multiplexers for DI5
PO1, PO2, PO3, SO1, SO2. DI6
DI7
DI8
1MRS751802-MUM
A051946
1MRS751802-MUM Protection Relay REX 521
4.3.7.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Non-directional earth-fault protection with two stages
• Directional earth-fault protection with two stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Underfrequency or overfrequency protection with one stage
• Negative phase sequence (NPS) protection with two stages
• Three-phase motor start-up supervision
• Three-phase thermal overload protection for devices
• Phase reversal protection
• Phase sequence voltage protection
• Fuse failure protection
• Three-phase non-directional undercurrent protection with one stage
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three-phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Operation time counter
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
55
REX 521 Protection Relay 1MRS751802-MUM
TCS
I0> 67N
CBCM 0 I
I0> 50N/51N
3I~harm R
3U> 59
3U~harm
3U< 27
3I I0 P
f</f> 81U/81O
Is2t,n< 48,14,66
3U U0 Q
3I
3I 46R
I2> 46 f pf E
3I< 37
F
60
3 49
U1<
U2> 27,47,59
U1>
CBFP */62
LO 86
A051947
4.3.7.2. Application
The H07 standard configuration for REX 521 is designed for protection of large or
medium-size three-phase AC motors in circuit breaker controlled motor drives. Due
to large number of protective functions integrated, the relay provides a complete
protection against motor damage caused by electrical faults.
The H07 configuration can also be applied to other objects needing thermal overload
protection (such as power transformers) and it can also be used in applications
requiring overcurrent protection, under/overvoltage protection and/or directional or
non-directional earth-fault protection.
For more information about the H07 standard configuration, refer to application
example in Section 12.7. Motor protection, High H07/H51.
56
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs REX 521
3I> I<->O CB1 3I>
OPEN 3I>>
BS1 CBFP OPENENA OOPEN 3I>>>
BS2 CLOSE OCLOSE Io>--> Master Trip Open LOGIC *)
START
GROUP CLOSEENA AOPEN Io>>-->
SWGRP TRIP HSPO1
RESET BINOPEN ACLOSE 3Ithdev>
O/C CBFP (X4.2.3/4/1/2)
BINCLOSE Io> Trip 1
dE/F Io>> >1 >1
3I>> I<->O IND1
3Ithdev> O/C 3I<
BINOPEN 3I> Lockout
PQ 3Inf dE/F 3U> S
3Ithdev> BS1 CBFP BINCLOSE 3I>> Q HSPO1
PQ 3Unf 3U>>
Reset 1 PQ 3Inf BS2 BSOUT 3I>>> Lockout reset R
E/F I<->O IND2 3U< Lockout Working
PQ 3Unf GROUP START BINOPEN Io>-->
Selector Voltage 3U<<
E/F DOUBLE TRIP BINCLOSE 3I> Io>>-->
f1 I2> 1 Lockout
Voltage RESET CBFP 3I>> 3Ithdev>
U/C I<->O IND3 I2>>
f1 3I>>> Io>
Current BINOPEN Is2t n<
U/C 3I>>> Io>--> Io>>
Is2t n<>
1MRS751802-MUM
Remote BS1 CBFP BI13Start 3U</3U<< f1 Trip2 3I() 3Ithdev> Alarm LED3
U1U2<>_1 3U> Start
Close enable BS2 START BI14 Start1/2 f1 Io>
f1 Trip1 3U> Trip
GROUP TRIP BI15 Trip1 Io>>
Open f1 Trip2 3U>> Start
I<->O CB1 RESET CBFP BI16 Trip2 3I<
CBFP 3U>> Trip
EXT_TRG I2>
Close SWGRP 3U< Start
3U> 3U I2>>
3U< Trip
CBO CBO TCS BS UL1_U12 Close 3U<< Start
CB pos. open
BS1 UL2_U23 3U<< Trip
BS2 UL3_U31 Open
CB pos. close DC1 Alarm LED4
I<->O IND1 GROUP START Open I2> Start
RESET TRIP f I2>> Start
DC1 3I> 3Ithdev> Start
DC pos. open DC2 3U>> PQE 3I>> Is2t n< Start
Start 1
3I>>> 3I< Start
DC2 BS1 Io>--> 3I() Start
ES1 I<->O IND2 CB wear1 Io>>--> 3I> f1 Start1/2
DC pos. close BS2 OPEN ALARM
GROUP START 3Ithdev> 3I>> FUSEF
BINOPEN
RESET TRIP Io> 3I>>>
ES1 BINCLOSE Alarm LED5
ES pos. open ES2 Io>> Io>--> Lockout I2> Trip
Technical Reference Manual, Standard
Fig. 4.3.7.2.-1 Block diagram of the standard configuration H07 for REX 521
Interlocking_A RESET TRIP f1 Start2 Is2t n< DI1
& PQ 3Inf
Interlocking_B 3I() DI2
TRIGG HAR_HIGH U1U2<>_1 DI3
Interlocking_C 3Ithdev> RESET CUM_HIGH
Start 2
3 f1 Start1 DI4
Interlocking_D
f1 Start2 Interlocking
Interlocking_E J> PQ 3Unf
3I>> BSOUT
Dev TRIGG HAR_HIGH MEAS LO ALARM Alarm LED7
Lockout Working CBFP RESET CUM_HIGH 3I>>>
MEAS HI ALARM
BLOCK START I<->0 CB1 open Alarm 1 DI3
Restart inhibit Restart enable TRIP FUSEF I<->0 CB1 close DI4
RESET CBFP MCB BSOUT MCS 3I DI5
STALL (speed switch) TCS1
EN_RESTART I2> I<->0 CB1 open DI6
MCB State PQ 3Inf har I<->0 CB1 close DI7
f1 Alarm 2
PQ 3Inf cum MCS 3I Lockout
f< BLOCK START CB wear1
DOUBLE 3I>> TCS1
Is2t, n< START f> GROUP TRIP MCS 3U
DOUBLE 3I>>> PQ 3Inf har CB wear1 Alarm LED8
RESET CBFP PQ 3Unf har PQ 3Inf cum TCS1
df/dt< BLOCK_OU PQ 3Unf cum CB wear1 MCS 3I
BS1 3I> T
df/dt> TIME1 MCS 3U MCS 3U
Is2t, n< START BS1 3I>> I2>>
FUSEF PQ 3Unf har TIME1
BS1 3I>>>
BS1 Io>--> BS1 START1 PQ 3Unf cum Motor Runs
BS2 3I> BLOCK START
FUSEF BSOUT BS1 Io>>--> BS2 TRIP1 TIME1 DI7
BS2 3I>> GROUP TRIP
BS1 Io> GROUP START2 FUSEF DI8
BS2 3I>>> RESET CBFP 3Ithdev>
BS1 Io>> BS2 Io>--> RESET TRIP2 BLOCK_OU I2> Block Restart enable
BS1 3U> BS2 Io>>--> T
3I< I2>> Block
BS1 3U>> BS2 Io> Is2t n<
Restart Inhibit
BS1 3U< BS2 Io>> Restart enable
GROUP START Is2t n<
BS1 3U<< BS2 3U> TRIP
STALL_I BLOCK START U1U2<>_1 Start
BS1 f1 BS2 3U>> STALL *) This logic disables the Open signal to HSPO1
ND GROUP TRIP
BS I2> BS2 3U< RESTAR
BS I2>> RESET CBFP if Open is selected by any multiplexers for
BS2 3U<< T
BS2 f1 U1U2<>_1 3I() FUSEF BSOUT PO1, PO2, PO3, SO1, SO2.
Is2t, n< START BS 3Ithdev>
BS 3I< Is2t n< START
BS 3I() BLOCK BLOCK START
FUSEF BSOUT
BS U1U2<>_1 GROUP START GROUP TRIP
RESET TRIP RESET CBFP
57
A051948
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.3.8.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Non-directional earth-fault protection with three stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Residual overvoltage protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Three-phase thermal overload protection for devices
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
58
1MRS751802-MUM Protection Relay REX 521
TCS
I 0> 50N/51N
CBCM 0 I
3I2f 68
3I~harm R
U 0> 59N
3U~harm
3U> 59
3I I0 P
3U< 27
CBFP */62
3U U0 3U_B
LO 86
Q f pf
3 49
A051949
4.3.8.2. Application
The H08 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, non-directional earth-fault
protection, overvoltage protection, undervoltage protection and residual overvoltage
protection.
For more detailed information about the configuration, refer to the application
example of the standard configuration H08 in Section 12.8. Incoming feeder, High
H08/H09.
59
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
60
inputs
SWGRP
REX 521
O/C
3I> I<->O CB1
E/F
O/V OPEN
Reset 1 O/C OPENENA OOPEN Master Trip Open LOGIC *)
U/V BS1 CBFP HSPO1
E/F CLOSE OCLOSE
PQ 3Inf BS2 START (X4.2.3/4/1/2)
Selector O/V CLOSEENA AOPEN Trip 1
RO/V GROUP TRIP 3I> >1
U/V BINOPEN ACLOSE >1
PQ 3Unf RESET CBFP 3I>>
PQ 3Inf BINCLOSE Lockout
3Ithdev> 3I>>>
Reset 2 RO/V 3I>> 3I> S HSPO1
Io>
REX 521
BS1 DI4
3U< Io>>
BS2 DI5
3U<< Io>>>
Logic input 1 GROUP START CB wear1 DI6
Uo> 3U> Lockout
RESET TRIP OPEN ALARM DI7
Uo>> 3U>>
BINOPEN DI8
Logic input 2 Uo>>> 3U<
Interlock- 3U<< BINCLOSE
3Ithdev> 3U<<
ing MEAS HI ALARM Alarm LED6
Logic input 3 CLOSEENA BS1 Uo>
scheme TCS1 DI2
BS2 TCSSTATE Uo>> Start 2
Interlocking_A I<->O CB1 DI3
& GROUP START BS ALARM Uo>>>
Interlocking_B DI4
RESET TRIP 3Ithdev>
DI5
Fig. 4.3.8.2.-1 Block diagram of the standard configuration H08 for REX 521
Interlocking_C MCS 3I DI6
Interlocking_D Uo> ALARM 3I>> BSOUT
DI7
Interlocking_E 3I>>> Interlocking
BS1
BS2 MCS 3U
Lockout Working ALARM I<->0 CB1 open MEAS LO ALARM Alarm LED7
GROUP START
I<->0 CB1 close MEAS HI ALARM
RESET TRIP
PQ 3Inf MCS 3I DI3
DOUBLE 3I>> Alarm 1 DI4
3I2f START Uo>> TRIGG HAR_HIGH TCS1
DOUBLE 3I>>> DI5
RESET CUM_HIGH PQ 3Inf har
BS1 DI6
BS2 PQ 3Inf cum DI7
3I2f START BS1 3I> PQ 3Unf
BS1 3I>> GROUP START CB wear1 I<->0 CB1 open Lockout
TRIGG HAR_HIGH MCS 3U
BS1 3I>>> BS2 3I> RESET TRIP I<->0 CB1 close
RESET CUM_HIGH Alarm LED8
BS1 Io> BS2 3I>> PQ 3Unf har MCS 3I CB wear1
BS1 Io>> BS2 3I>>> Uo>>> PQ 3Unf cum TCS1 TCS1
BS1 Io>>> BS2 Io> 3U_B PQ 3Inf har MCS 3I
BS1 Alarm 2 MCS 3U
BS1 3U> BS2 Io>> UL1_U12 PQ 3Inf cum
BS1 3U>> BS2 DI5
BS2 Io>>> UL2_U23 CB wear1
BS1 3U< GROUP START DI6
BS2 3U> UL3_U31 MCS 3U
BS1 3U<< RESET TRIP DI7
BS2 3U>> PQ 3Unf har DI8
BS1 Uo>
BS2 3U< 3Ithdev> PQ 3Unf cum
BS1 Uo>>
BS1 Uo>>> BS2 3U<< 3
BS2 Uo> J> *) This logic disables the Open signal to HSPO1
3I2f START
BS2 Uo>> Dev 3I2f START
BS2 Uo>>>
if Open is selected by any multiplexers for
CBFP PO1, PO2, PO3, SO1, SO2.
BS 3Ithdev>
BLOCK START
TRIP
RESET CBFP
1MRS751802-MUM
A051950
1MRS751802-MUM Protection Relay REX 521
4.3.9.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Non-directional earth-fault protection with three stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Residual overvoltage protection with three stages
• Three-phase transformer inrush and motor start-up current detector
• Underfrequency or overfrequency protection with two stages
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Automatic reclosing 1...5 shots
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
61
REX 521 Protection Relay 1MRS751802-MUM
TCS
I 0> 50N/51N
CBCM 0 I
3I2f 68
3I~harm R
U 0> 59N
3U~harm
3U> 59
3I I0 P
3U< 27
CBFP */62
3U U0 3U_B
LO 86
f</f> 81U/81O Q f pf
0 I 79
E
A051951
4.3.9.2. Application
The H09 standard configuration for REX 521 is designed to be used in single busbar
systems using one circuit breaker for selective non-directional short-circuit
protection, non-directional time-overcurrent protection, non-directional earth-fault
protection, overvoltage protection, undervoltage protection, residual overvoltage
protection, underfrequency protection, overfrequency protection and automatic
reclosing.
For more detailed information about the configuration, refer to the application
example of the standard configuration H09 in Section 12.8. Incoming feeder, High
H08/H09.
62
Digital Input signals Input SWGRPs Function blocks Output SWGRPs Output signals Output relays
inputs SWGRP Open LOGIC **)
O/C REX 521
E/F I<->O CB1 Master Trip Ropen HSPO1
3I>
O/V O/C OPEN (X4.2.3/4/1/2)
E/F Trip 1
U/V OPENENA OOPEN 3I> >1 >1
Reset 1 O/V BS1 CBFP 3I>>
RO/V CLOSE OCLOSE
U/V BS2 START Lockout
Selector PQ 3Inf CLOSEENA AOPEN 3I>>> S
GROUP TRIP 3I> HSPO1
PQ 3Unf RO/V BINOPEN ACLOSE Io> Q
RESET CBFP 3I>> Lockout Working
I-->O PQ 3Inf BINCLOSE Io>> Lockout reset R
3I>>>
Reset 2 FREQ PQ 3Unf 3I>> Io>>>
I<->O IND1 3I> Io>
I-->O 3U> 1 Lockout
O/C 3I>> Io>>
Terminal FREQ CBFP
BINOPEN 3U>>
E/F BS1 3I>>> Io>>>
connection BINCLOSE 3U<
Group O/V BS2 BSOUT Io> 3U>
BS1 3I> I<->O IND2 3U<<
X4.2.5/6 DI1 U/V GROUP START Io>> 3U>>
BS1 3I>> BS2 3I> Uo> PO1 (X4.1.12/13)
X4.2.6/7 DI2 RO/V DOUBLE TRIP BINOPEN Io>>> 3U<
BS1 3I>>> BINCLOSE
Uo>>
X4.2.8/9 DI3 FREQ BS2 3I>> RESET CBFP 3U> 3U<<
Blocking 1 BS1 Io> Uo>>> PO2 (X4.1.14/15)
X4.2.9/10 DI4 BS2 3I>>> 3U>> Uo>
1MRS751802-MUM
Fig. 4.3.9.2.-1 Block diagram of the standard configuration H09 for REX 521
RESET CUM_HIGH Lockout
BS1 I<->0 CB1 close
BS1 3I> BS2 MCS 3I CB wear1 Alarm LED8
3I2f START PQ 3Unf
BS1 3I>> GROUP START TRIGG HAR_HIGH TCS1 TCS1
TRIP Alarm 1 MCS 3I
BS1 3I>>> RESET RESET CUM_HIGH PQ 3Inf har
BS1 Io> PQ 3Inf cum MCS 3U
Uo>>> O->I OPEN
BS1 Io>> CB wear1
3U_B I<->0 CB1 open O->I ACTIVE
BS1 Io>>> BS1 MCS 3U O->I ALARM1
BS2 3I> UL1_U12 I<->0 CB1 close
BS1 3U> BS2 PQ 3Unf har O->I ALARM2
BS2 3I>> UL2_U23 MCS 3I
BS1 3U>> GROUP START PQ 3Unf cum
BS2 3I>>> UL3_U31 TCS1
BS1 3U< RESET TRIP
BS2 Io> PQ 3Inf har
BS1 3U<< Alarm 2
BS2 Io>> f1 O-->I PQ 3Inf cum
BS1 Uo>
BS2 Io>>> f< AR1 ROPEN CB wear1
BS1 Uo>>
BS2 3U> f> AR2 RCLOSE MCS 3U
BS1 Uo>>> SHOT1
BS2 3U>> AR3 DEFTRIP PQ 3Unf har
BS1 f1 AR4 LOCKOUT
SHOT2
BS2 3U< df/dt< PQ 3Unf cum
BS1 f2 ARINH SHOT3
BS2 3U<< df/dt> O-->I Active
CBOPEN SHOT4
BS2 Uo> CBCLOSE SHOT5
3I2f START
BS2 Uo>> BS1 START1 ON TRDUE
BS2 Uo>>> BS2 TRIP1 RESET AR1TRIP TDDUE
BS2 f1 GROUP START2 AR2TRIP ACTIVE
BS2 f2 RESET TRIP2 AR3TRIP O-->I Alarm 1
AR4TRIP
f2
f< CBFAIL
*) NOTE! The trip and start signals from the protection function blocks **) This logic disables the Open signal to HSPO1
f> DEFTRIP AR1TRIP
are routed directly to the auto-recloser (O->I) via the input switchgroups LOCKOUT if Open is selected by any multiplexers for
AR2TRIP
of the auto-recloser and are not shown in the diagram. SHOT_ALARM AR3TRIP
PO1, PO2, PO3, SO1, SO2.
df/dt<
df/dt> AR4TRIP
CBFAIL O-->I Alarm 2
BS1 START1 DEFTRIP
BS2 TRIP1 LOCKOUT
GROUP START2 SHOT_ALARM
RESET TRIP2
3I2f START
63
A051952
REX 521
REX 521 Protection Relay 1MRS751802-MUM
4.3.10.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase directional overcurrent protection with two stages
• Directional earth-fault protection with two stages
• Non-directional earth-fault protection with two stages
• Three-phase overvoltage protection with two stages
• Three-phase undervoltage protection with two stages
• Residual overvoltage protection with two stages
• Three-phase transformer inrush and motor start-up current detector
• Underfrequency or overfrequency protection with two stages
• Phase-sequence voltage protection
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Automatic reclosing 1...5 shots
• Circuit breaker control with indication
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
64
1MRS751802-MUM Protection Relay REX 521
CBCM 0 I
3I2f 68
3I~harm R
U0> 59N
3U~harm
3U> 59
3U< 27 3I I P
0
CBFP */62
3U U Q
0
LO 86
3I> 67 f pf E
U1<
U2> 27,47,59
U1>
I0 > 67N
f</f> 81U/81O
O I 79
A060006
4.3.10.2. Application
The H50 standard configuration for REX 521 is designed to be used in single busbar
systems by using one circuit breaker for selective non-directional short-circuit
protection, directional and non-directional time-overcurrent protection, directional
and/or non-directional earth-fault protection, overvoltage protection, undervoltage
protection, residual overvoltage protection, underfrequency protection,
overfrequency protection and automatic reclosing.
For more detailed information about the configuration, refer to the application
example of the standard configuration H50 in Section 12.5. Incoming feeder, High
H05/H50.
65
Digital inputs Input signals Input SWGRPs Function blocks Ouput SWGRPs Output signals
Output relays
66
REX 521 3I>
3I>>
3I> I<->O CB1 3I>>> Ropen
SWGRP 3I>
OPEN Io>
O/C OPENA 3I>>
CBFP Io>> Master Trip Open LOGIC***)
E/F BS1 CLOSE OPEN 3I>>> HSPO1
BS2 Io>-->
O/V START CLOSENA OCLOSE Io> Trip 1 (X4.2.3/4/1/2)
O/C GROUP TRIP BINOPEN AOPEN 3I> Io>>-->
U/V E/F RESET 3I>> Io>> >1
Reset 1 CBFP BINCLOSE ACLOSE 3I>--> >1
PQ 3Inf O/V 3I>>> Io>-->
Selector 3I>>-->
RO/V U/V 3I>> I<->O IND1 Io> Io>>--> Lockout
3U> S
PQ 3Unf PQ 3Inf BINOPEN Io>> 3I>--> HSPO1
3U>> Q
O-->I RO/V BINCLOSE Io>--> 3I>>-->
CBFP 3U< Lockout reset R Lockout Working
REX 521
Fig. 4.3.10.2.-1 Block diagram of the standard configuration H50 for REX 521
BS2 TRIP1 AR4 LOCKOUT DI5
f1 Start2 f1 Trip1 f prot GROUP START2 ARINH TCS1 I<->O CB1 open Alarm 2
& DI6
No delay RESET TRIP2 CBOPEN PQ 3Inf har I<->O CB1 close DI7
>1 50 ms CBCLOSE PQ 3Inf cum MCS 3I
f2 ON DI8
f2 Start2 100 ms CB wear1 TCS1
DOUBLE 3I>> f< RESET Lockout
150 ms f> MCS 3U PQ 3Inf har
DOUBLE 3I>>> SHOT1
200 ms 3I2f START PQ 3Unf har PQ 3Inf cum
DOUBLE 3I>--> 3I>--> SHOT2
250 ms df/dt< PQ 3Unf cum CB wear1 CB wear1 Alarm LED8
DOUBLE 3I>>--> SHOT3
300 ms df/dt> MCS 3U TCS1
SHOT4
350 ms PQ 3Unf har MCS 3I
BS1 3I> SHOT5 MCS 3U
400 ms 3I2f START PQ 3Unf cum
BS1 3I>> BS1 START1 CBFP TRDUE O-->I OPEN
500 ms BS2 3I> BS2 TRIP1 O-->I Active
BS1 3I>>> BACTRL START TDDUE O-->I ACTIVE
600 ms BS2 3I>> GROUP START2
BS1 3I>--> RESET TRIP2 BS1 TRIP ACTIVE O-->I ALAR1
700 ms BS2 3I>>> BS2 CBFP
BS1 3I>>--> O-->I Alarm1 O-->I ALAR2
800 ms BS2 3I>--> GROUP
BS1 Io>--> Io>--> AR1TRIP
900 ms BS2 3I>>--> RESET
BS1 Io>>--> AR2TRIP
1000 ms BS2 Io>-->
BS1 Io> 3I>>--> AR3TRIP O-->I Alarm2
1500 ms BS2 Io>>--> AR1TRIP
BS1 Io>> AR4TRIP
BS2 Io> AR2TRIP
BS1 3U> CBFP CBFAIL
BS2 Io>> AR3TRIP
U1U2<>_1 BS1 3I> BS1 3U>> DEFTRIP
BS2 3U> BACTRL START AR4TRIP
BS1 3I>> BS1 3U< BS1 TRIP CBFP LOCKOUT
BS1 3I>>> BS2 3U>> CBFAIL
>1 3I2f STA RT BS1 3U<< BS2 CBFP BACTRL BSOUT SHOT_ALARM
BS1 3I>- - > BS2 3U< GROUP DEFTRIP
3U< Start2 BS1 Uo> BS1 START
BS1 3I>>- -> BS2 3U<< LOCKOUT
BS1 Uo>> BS2 TRIP
BS2 Uo> Io>>--> GROUP CBFP SHOT_ALARM *) The trip and start signals from the protection function blocks are
BS1 f1
BS1 f2 BS2 Uo>> DOUBLE routed directly to the AR1-4 conf selector via the input switchgroups
BS2 3I> BS2 f1 RESET of the auto-recloser and are not shown in the diagram.
BS2 3I>> BS U1U2<>_1 U1U2<>_1
BS2 3I>>> BS2 f2
U1U2<>_1
BS2 3I>- - > CBFP 3U< Start **) The starting of auto reclose sequence is:
BS2 3I>>- -> BACTRL START - Standard - Trip and Start signals start auto-recloser.
BS1 TRIP BLOCK - Fast final trip - After first close AR5func goes to final Trip.
BS2 CBFP GROUP START
TRDUE - CB Position act. - The binary input from CB starts auto recloser sequence.
GROUP RESET TRIP
RESET
3I2f START ***) This logic disables the Open signal to HSPO1 if Open is selected
by any multiplexers for PO1, PO2, PO3, SO1, SO2.
f1 Trip1
f2 Start2
f1 Start2
1MRS751802-MUM
A060007
1MRS751802-MUM Protection Relay REX 521
4.3.11.1. Features
• Three-phase non-directional overcurrent protection with three stages
• Three-phase directional overcurrent protection with one stage
• Non-directional earth-fault protection with two stages
• Directional earth-fault protection with two stages
• Three-phase overvoltage protection with one stage
• Three-phase undervoltage protection with one stage
• Underfrequency or overfrequency protection with two stages
• Negative phase-sequence (NPS) protection with one stage
• Three-phase motor start-up supervision
• Three-phase thermal overload protection for devices
• Residual overvoltage protection with one stage
• Phase-sequence voltage protection
• Fuse-failure protection
• Three-phase non-directional undercurrent protection with one stage
• Supervision function for energizing current input circuit
• Supervision function for energizing voltage input circuit
• Current waveform distortion measurement
• Voltage waveform distortion measurement
• Three-phase current measurement
• Neutral current measurement
• Three-phase voltage measurements
• Residual voltage measurement
• System frequency measurement
• Three-phase power and energy measurement
• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
• Trip-circuit supervision
• Delayed trip output for the circuit breaker failure protection (CBFP) function
• Circuit breaker control with indication
• Operation time counter
• Lockout function
• Object indication
• Logic control position selector
• User-configurable I/Os
• Interlocking
• User-configurable alarm LEDs
67
REX 521 Protection Relay 1MRS751802-MUM
CBCM 0 I
I0> 50N/51N
3I~harm R
3U> 59
3U~harm
3U< 27
f</f> 81U/81O 3I I P
0
Is2t,n< 48,14,66
3U U Q
0
3I
3I 46R
I2> 46 f pf E
U0> 59N
F
60
3 49
U1<
U2> 27,47,59
U1>
CBFP */62
LO 86
3I> 67
A060005
4.3.11.2. Application
The H51 standard configuration for REX 521 is designed for protection of large or
medium-size three-phase AC motors in circuit breaker controlled motor drives. Due
to the large number of protective functions integrated, the relay provides a complete
protection against motor damage caused by electrical faults.
The H51 configuration can be applied to other objects that need thermal overload
protection (such as power transformers). It can also be used in applications requiring
overcurrent protection, directional overcurrent protection, under/overvoltage
protection, directional or non-directional earth-fault protection, underfrequency
protection and/or overfrequency protection.
For more information about the H51 standard configuration, refer to the application
example in Section 12.7. Motor protection, High H07/H51.
68
Digital inputs Input signals Input SWGRPs Funtion blocks Ouput SWGRPs Output signals Output relays
SWGRP 3I>
REX 521
O/C 3I>> Master Trip
3I> I<->O CB1 O p en LOGIC *)
DE/F OPEN 3I>>> HSPO1
3Ithdev> O/C OPENENA OOPEN Io> (X4.2.3/4/1/2)
PQ 3Inf DE/F BS1 CBFP 3I> Io>> Trip 1
BS2 CLOSE OCLOSE >1 >1
PQ 3Unf 3Ithdev> START 3I>> Io>-->
Reset 1 CLOSEENA AOPEN
E/F PQ 3Inf GROUP TRIP 3I>>> Io>>--> Lockout
RESET BINOPEN ACLOSE S
Vo PQ 3Unf CBFP 3I> Io> 3I>>-->
BINCLOSE Q HSPO1
FREQ E/F 3I>> Io>> 3U<
3I>> Lockout reset R Lockout Working
Curr Vo I<->O IND1 3I>>> Io>--> 3U>
Motstart FREQ BINOPEN Io> Io>>--> Uo>
Curr BS1 CBFP BINCLOSE Io>> 3I>>--> Is2t n< 1 Lockout
Reset 2 Motstart BS2 3U< 3I()
BSOUT I<->O IND2 Io>-->
GROUP START Io>>--> 3U> I2>
O/C BINOPEN
Group DOUBLE TRIP 3I>>--> Uo> 3Ithdev>
BINCLOSE
E/F RESET CBFP 3U< Is2t n< U1U2<>_1
X4.2.5/6 DI1 BS1 3I> PO1 (X4.1.12/13)
Volt I<->O IND3 3U> 3I() f prot.
X4.2.6/7 DI2 Freq BS1 3I>> BINOPEN
3I>>> Uo> I2> f1 Trip1
X4.2.8/9 DI3 BS1 3I>>> BINCLOSE PO2 (X4.1.14/15)
Is2t n< 3Ithdev> f1 Trip2
1MRS751802-MUM
X4.2.9/10 DI4 BS1 3I>>-> BS2 3I> I<->O POS 3I() U1U2<>_1 f2 Trip1
X4.2.11/12 BS1 Io>--> BS2 3I>> BS1 CBFP
DI5 BINLOCAL I2> f prot. f2 Trip2 PO3 (X4.1.17/18)
X4.2.13/14 BS1 Io>>--> BS2 3I>>> BS2 BSOUT
DI6 BINREMOTE 3Ithdev> f1 Trip1 Trip 2
X4.2.15/16 BS1 Io> BS2 3I>>-> GROUP START
DI7 Blocking 1 U1U2<>_1 f1 Trip2 SO1 (X4.1.8/7/6)
X4.2.17/18 BS1 Io>> BS2 Io>--> DOUBLE TRIP 3I
DI8 f prot. f2 Trip1
X3.1.1/2 BS1 3U> BS2 Io>>--> RESET CBFP IL1
DI9 IL2 f1 Trip1 f2 Trip2
BS1 3U< BS2 Io> Trip 3 SO2 (X4.1.10/11/9)
Io> IL3 f1 Trip2
BS1 Uo> BS2 Io>> f2 Trip1
BS1 f1 BS2 3U> Io
Io f2 Trip2
BS1 f2 BS2 3U<
BS I2> BS2 Uo> CBFP Uo
BS2 f1 BACTR Uo Trip 4
3I>
Blocking 2 BS2 f2 LBS1 START AI1 3I>>
BS 3I() BS2 TRIP LOW ALARM 3I>>>
BS 3Ithdev> GROUP CBFP HIGH ALARM 3I> Trip 5
Io> Alarm LED1
BS U1U2<>_1 3I>> 3I> Start
DREC Io>>
DREC trig Io>> IL1 3I>>> 3I> Trip
Io>-->
IL2 Io> 3I>> Start
PQ 3Inf trig Io>>-->
IL3 Io>> 3I>> Trip
3I>>-->
PQ 3Unf trig CBFP Io Io>--> 3I>>> Start
3U<
Iob Io>>--> 3I>>> Trip
BACTRL START 3U>
Uo Uo> 3I>>-->
BS1 TRIP 3U<
U12 Is2t n< External trip
BS2 CBFP 3U>
U23 3I()
BACTRL Io>--> GROUP Uo> Alarm LED2
U31 I2> Io>-> Start
Io>>--> RESET BI1 Start 3I> 3Ithdev> Is2t n< Io>-> Trip
Master trip BI2 Start 3I>> U1U2<>_1 3I()
Io> Io>>-> Start
Master trip BI3 Start 3I>>> I2> 3I>
External trip f prot. Io>>-> Trip
External trip BI4 Start Io>--> f1 Trip1 3Ithdev> 3I>> Io> Start
Lockout reset BI5 Start Io>>--> f1 Trip2 U1U2<>_1 3I>>>
Lockout reset BS1 CBFP Io> Trip
BI6 Start Io>/Io>> f2 Trip1 f prot. Io>-->
Remote BS2 START Io>> Start
BI7 Start 3U</3U> f2 Trip2 f1 Trip1 Io>>-->
GROUP TRIP Io>> Trip
Close enable BI8 Start 3Ithdev> f1 Trip2 3Ithdev>
RESET CBFP
Open BI9 Start I2> f2 Trip1 Io> Alarm LED3
I<->O CB1 f2 Trip2 3U> Start
BI10 Start Is2t, n< Io>>
Io>> Start 1/2 f1 CBFP 3U> Trip
Close SWGRP BI11 I2>
Start 1/2 f2 3U< Start
BI12 3I>>-->
CBO CBO TCS BS BS1 CBFP Start 3I>>--> 3U< Trip
BI13
CB pos. open BS2 Start Uo> 3I>>--> Start
START BI14 Close
GROUP TRIP f prot. 3I>>--> Trip
BI15
Protection Relay
Fig. 4.3.11.2.-1 Block diagram of the standard configuration H51 for REX 521
U1U2<>_1 Start PQ 3Unf 3I>>>
BS2 3I>> DI5
>1 BS2 3I>>> BS1 START1 TRIGG HAR_HIGH 3I>>-->
BS2 3I>>- -> RESET CUM_HIGH DI6
3U< Start2 BS2 TRIP1 DI7
Alarm 1
GROUP START2 I<->0 CB1 open DI8
RESET TRIP2 FUSEF
MCB State I<->0 CB1 close Lockout
MCB BSOUT
MCS 3I
Restart inhibit Is2t n< I<->0 CB1 open Alarm 2
I2> TCS1 CB wear 1 Alarm LED8
GROUP START PQ 3Inf har I<->0 CB1 close TCS1
STALL (speed switch) MCS 3I
STALL_I TRIP BLOCK START PQ 3Inf cum MCS 3I
ND STALL GROUP TRIP CB wear 1 TCS1 MCS 3U
RESTART RESET CBFP MCS 3U PQ 3Inf har TIME1
f prot. delay BLOCK_OU PQ 3Unf har PQ 3Inf cum Motor Runs
f prot U1U2<>_1 PQ 3Unf cum CB wear 1 DI7
f1 Start2 f1 Trip1
No delay & f2 TIME1 MCS 3U DI8
50 ms f< PQ 3Unf har
>1 f> FUSEF
100 ms BLOCK PQ 3Unf cum
f2 Start2 GROUP START
150 ms TIME1
DOUBLE 3I>> RESET TRIP df/dt<
200 ms DOUBLE 3I>>> df/dt> FUSEF
Is2t, n< START
250 ms
DOUBLE 3I>>--> 3I()
300 ms START1
BS1 FUSEF BSOUT
350 ms BS1 3I> BS2 TRIP1
400 ms BS1 3I>> GROUP START2
Is2t, n< START BLOCK START RESET TRIP2 Is2t n< START 3Ithdev>
500 ms BS1 3I>>>
BS1 3I>>-> GROUP TRIP I2> Block
600 ms BS2 3I> 3I>> ->
RESET CBFP Restart Inhibit
700 ms FUSEF BSOUT BS1 Io>--> BS2 3I>>
800 ms BS1 Io>>--> Is2t n< Restart enable
BS2 3I>>> Uo> U1U2<>_1 Start
900 ms BS1 Io> BS2 3I>>->
1000 ms BS1 Io>> CBFP *) This logic disables the Open signal to HSPO1
BS2 Io>--> if Open is selected by any multiplexers for PO1,
1500 ms BS1 3U> BS1 START BACTRL BSOUT
BS2 Io>>--> BS2 TRIP BS1 START U1U2<>_1 Start PO2, PO3, SO1, SO2.
BS1 3U< BS2 Io> GROUP BS2 TRIP
BS1 Uo> RESET GROUP CBFP
BS2 Io>> DOUBLE 3U< Start
BS1 f1 BS2 3U> RESET
BS1 f2 BS2 3U<
BS I2> BS2 Uo>
BS2 f1
Is2t, n< START BS2 f2
BS2 3I()
BS 3Ithdev>
FUSEF BSOUT BS U1U2<>_1
69
A060008
REX 521
70
1MRS751802-MUM Protection Relay REX 521
Selectors
Digital PREDELAY Input Output
inputs Signals relays
HSPO 1
Master trip
A051953
Fig. 5.-1 Main principle of the overview diagrams of the signal routings
71
REX 521 Protection Relay 1MRS751802-MUM
The routings between the digital inputs and different functionalities are set with
selectors and switchgroups (SWGRP) for each functionality respectively. Settings
are done with the Human-Machine Interface (HMI) or with the Relay Setting Tool.
I>
DI1 Selector I>>
I>>>
SWGRP
Reset OC
Reset EF Io>
Selector Io>>
Io>>>
Reset Iub
SWGRP
Selector Iub
etc.
Selector Open
etc.
A051954
Fig. 5.1.-1 Digital input signals are routed via selectors and switchgroups to the
function blocks (DI1 in the figure) or to the different functions (DI2 in
the figure)
72
1MRS751802-MUM Protection Relay REX 521
Selector DI1
.
. Selector Reset 1
.
DI9
Reset 2
Selector
Blocking 1
Selector
Selector Blocking 2
etc.
A051955
SWGRP
RESET OC
RESET EF
Reset 1
RESET Iub
etc.
A051956
Fig. 5.1.2.-1 The input signal is routed with the switchgroup to one or several
function block input(s)
Note that the symbol O/C (overcurrent) includes overcurrent function blocks I>, I>>
and I>>>. The E/F (earth fault) symbol includes all three earth-fault function blocks
Io>, Io>> and Io>>>, for example the Reset 1 signal resets all the three stages.
The symbols O/C and E/F are used in the overview diagrams of the signal routings
and in the HMI menus.
73
REX 521 Protection Relay 1MRS751802-MUM
Input signals
SWGRP
Selector Reset 1 O/C
E/F
Iub> O/C
3Ith> E/F
PQ 3Inf Iub>
Reset 2 3Ith>
PQ 3Inf
O/C
DI1 Group E/F
DI2 Iub> Input switchgroups
DI3 3Ith>
DI4 Blocking 1
Digital BS1 3I>
inputs DI5 BS2 3I> BS1 3I>>
DI6 BS2 3I>> BS1 3I>>>
DI7 BS2 3I>>> BS1 Io>-->
DI8 Blocking 2 BS2 Io>--> BS1 Io>>-->
DI9 BS2 Io>>--> BS1 Io>>>-->
BS2 Io>>>--> BS1 Iub>
BS2 Iub>
BS 3lth>
DREC trig - Disturbance recorder trigger
PQ 3Inf trig - Power quality trigger
Io>-->
BACTRL Io>>--> Input switchgroup
Io>>>-->
Master trip
Master trip
External trip - Master trip
External trip - External trip
Lockout reset - Lockout reset
Lockout reset
Close enable
Open
I<->O CB1
Close
Control operations
to the circuit breaker SWGRP
CB pos. open CBO
CBO TCS BS Trip circuit supervision
CB pos. close
ES2 ES2
ES pos. close
Logic input 1
Logic input 2
Logic input 3
Interlocking
scheme
Lockout working
A051957
74
1MRS751802-MUM Protection Relay REX 521
Iub> CB wear
OPEN ALARM
3∆I> BINOPEN
BINCLOSE
CBFP
BS1
TCS1
BS2 START
GROUP
RESET
TRIP
CBFP
TCSSTATE Condition
BS ALARM
3Ith> MCS 3I
monitoring
3 ALARM
J>
Cab
CBFP PQ 3Inf
BLOCK (BS)
GROUP START TRIGG HAR_HIGH
RESET TRIP RESET CUM_HIGH
CBFP
CU_ALARM
A051958
Fig. 5.2.-1 Function blocks in the overview diagrams of the signal routings
75
REX 521 Protection Relay 1MRS751802-MUM
3I>>>
CBFP
BS1
BS2 BSOUT
Inputs GROUP START Outputs
DOUBLE TRIP
RESET CBFP
Io> SWGRP
Trip Selector PO1
Start
I> PO2
Selector
Trip Trip 2
Start
etc.
Selector SO2
SWGRP
Start 1
etc.
A051960
76
1MRS751802-MUM Protection Relay REX 521
3I>
3I>> Master Trip HSPO1
3I>>> (X4.2.3/4/1/2)
Io>--> Trip 1
1 1
Io>>-->
Io>>>--> Lockout
Iub> S HSPO1
Q
3Ith> Lockout reset R Lockout Working
1 Lockout
A051961
Trip HSPO1
>1
signal (trip relay)
Lockout
S HSPO1
Q
Lockout reset R Lockout Working Connected to COCB
(Close enable)
to prevent
Selector close operation
A051962
77
REX 521 Protection Relay 1MRS751802-MUM
+
Trip signal S
Q 1 Lockout
Lockout reset R
Lockout
(Normally closed)
Close command
A051963
1. Change-over contact
78
1MRS751802-MUM Protection Relay REX 521
High speed
tripping contact
HSP01 Open logic
3I> HSPO1
3I>> Master trip Open Logic (X4.2.3/4/1/2)
3I>>>
Io>--> Trip 1
>1 >1
Io>>-->
Io>>>-->
Iub> S Lockout
3Ith> HSPO1
Lockout reset R Q Lockout working
3I> 1 Lockout
3I>>
3I>>>
Io>--> Trip 2
Io>>-->
Io>>>-->
Iub>
3Ith>
Lockout function
3I>
3I>>
3I>>> Trip 3
Io>-->
Io>>-->
Io>>>-->
Iub>
3Ith>
3I>
3I>>
3I>>> Trip 4
Io>-->
Io>>-->
Io>>>-->
Iub> PO1 (X4.1.12/13)
3Ith>
PO2 (X4.1.14/15)
3I>
3I>> PO3 (X4.1.17/18)
3I>>> Trip 5
Io>-->
Output Io>>-->
SO1 (X4.1.8/7/6)
switchgroups Io>>>-->
Iub> SO2 (X4.1.10/11/9)
3Ith>
External trip
3I>
3I>>
3I>>>
Io>--> CBFP
Io>>-->
Io>>>-->
Iub> Output relays
3Ith>
Close
Open
Open
3I>
3I>>
3I>>> Start 1
Io>-->
Io>>-->
Io>>>-->
Iub>
3Ith>
3I>
3I>>
3I>>> Output signals
Io>--> Start 2
Io>>-->
Io>>>-->
Iub>
3Ith>
Lockout
3I>> BSOUT
3I>>>
A051964
79
REX 521 Protection Relay 1MRS751802-MUM
PO1 (X4.1.12/13)
PO2 (X4.1.14/15)
PO3 (X4.1.17/18)
Close
SO1 (X4.1.8/7/6)
Open
SO2 (X4.1.10/11/9)
Open
Output relays
A060004
Fig. 5.4.2.-1 Open signal connected to output relays in the block diagrams of the
standard configurations
High speed
tripping contact
HSP01 Open logic
HSPO1
Open Logic (X4.2.3/4/1/2)
>1 >1
S Lockout
HSPO1
Lockout reset R Q Lockout working
1 Lockout
A060003
Fig. 5.4.2.-2 HSPO1 Open logic in the block diagrams of the standard
configurations
80
1MRS751802-MUM Protection Relay REX 521
The df/dt function detects the oscillation. Basically, the frequency protection signal
is activated when the frequency is stable and the set frequency limit has been
exceeded. Here stable means that df/dt has not detected any oscillation during a
certain period of time. The period of time is set in Configuration/Special
settings/f prot. delay.
f prot. delay
f1 Start2 f1 Trip1 f prot
No delay &
>1 50 ms
f2 Start2 100 ms
150 ms
200 ms
250 ms
300 ms
350 ms
400 ms
500 ms
600 ms
700 ms
800 ms
900 ms
1000 ms
1500 ms
A060137
f1 Trip1
underfrequency
protection
f1 Start2
df/dt>
f2 Start2
df/dt<
f prot.
f prot. delay
A060138
Fig. 5.4.3.1.-2 Example signal diagram for frequency protection signal explaining
the df/dt blocking function
81
REX 521 Protection Relay 1MRS751802-MUM
f1 Trip1
underfrequency
protection
f1 Start2
df/dt>
f2 Start2
df/dt<
f prot.
f prot. delay
A060139
Fig. 5.4.3.1.-3 Example signal diagram for frequency protection signal explaining
the activated frequency protection function
The f. prot signal is not routed to any output relay by default. To enable this signal
it must be routed to any of the outputs.
82
1MRS751802-MUM Protection Relay REX 521
BS1 3I>
BS1 3I>>
BS1 3I>>>
BS1 3I>>-->
Voltage
Enabled
Overcurrent
protection Blocked
A060140
83
84
1MRS751802-MUM Protection Relay REX 521
Selectors
Input Output
Signals relays
Reset 1 HSPO 1
Reset 2 PO1
Group PO2
Digital PREDELAY
Blocking 1 .
inputs Blocking 2 .
DREC trig .
DI1 PQ 3Inf trig etc.
. BACTRL
. Master trip
. External trip
DI9 INVERSION Lockout reset
Remote Input
Close enable SWGRP
Open
Close Reset 1
CB pos. open O/C
CB pos. close E/F
DC pos. open Iub>
DC pos. close 3Ith>
PQ 3Inf
ES pos. open
O-->I
ES pos. close
Logic input 1 Reset 2
Logic input 2
Logic input 3
etc.
A051965
6.1. Selectors
6.1.1. Reset
Selectors Reset 1 and Reset 2 can be programmed to connect any of the inputs
DI1...DI9 to reset the latched trip signal and the recorded data of the functions (for
example O/C, E/F, Iub>, 3Ith>, PQ 3Inf 1).
6.1.2. Group
Group is used for switching between the setting groups 1 and 2 of the protection
functions.
6.1.3. Blocking
Selectors BS1 and BS2 can be programmed to block the operation of the functions
(for example 3I>, 3I>>, 3I>>> etc.1).
85
REX 521 Protection Relay 1MRS751802-MUM
6.1.9. Local/Remote
Any of the digital inputs can be used for activating the local mode of the relay if the
Local/Remote selection is set to “external input”. In local position, the circuit
breaker can be controlled via the binary inputs and the HMI but not through a
communication port. In remote position, the circuit breaker can be controlled only
through a communication port.
When using digital inputs to control the circuit breaker, the inputs
must be activated with a pulse. Otherwise, if the input remains
activated, a position change from remote to local can cause an
immediate opening or closing of the circuit breaker
86
1MRS751802-MUM Protection Relay REX 521
6.2. Interlocking
Closing the circuit breaker (CB) is permitted by the CLOSEENA input of the
I<->O CB1 function block. Different kinds of logics for permitting close operations
can be built by using the interlocking logic described in Fig. 6.2.-1 and
Fig. 6.2.1.-4.
The logic states of an earth switch (ES), a disconnector (DC), and general digital
inputs (DI1...DI9) can be used together with the interlocking logic in Fig. 6.2.-1.
CB pos. open
CB pos. close
Close enable
DI
1<-->0 CB
Selector
CB
DI1
DI2 CLOSEENA
Selector ES pos. open
ES pos. close
Interlocking_A
Interlocking_B
&
... DC pos. open Interlocking_C Lockout working
A051966
87
REX 521 Protection Relay 1MRS751802-MUM
ES pos. open
ES pos. close
& Interlocking_A
A051967
DC pos. open
DC pos. close
& Interlocking_A
A051968
88
1MRS751802-MUM Protection Relay REX 521
DC pos. open
DC pos. close
& 1 Interlocking_A
ES pos. open
ES pos. close
& & Interlocking_B
A051969
DC pos. open
DC pos. close
& 1 Interlocking_A
ES pos. open
ES pos. close
& & Interlocking_B
& Interlocking_D
Interlocking_E
A051970
89
REX 521 Protection Relay 1MRS751802-MUM
& Interlocking_D
= Close enable
Logic input 1 = SF6 gas alarm
Logic input 2 = Spring not charged
Logic input 3 = Manual stop &
A051971
90
1MRS751802-MUM Protection Relay REX 521
7. Default settings
These settings can be found in Main menu\Configuration\.
91
REX 521 Protection Relay 1MRS751802-MUM
92
1MRS751802-MUM Protection Relay REX 521
93
REX 521 Protection Relay 1MRS751802-MUM
94
1MRS751802-MUM Protection Relay REX 521
95
REX 521 Protection Relay 1MRS751802-MUM
96
1MRS751802-MUM Protection Relay REX 521
Start 1b - - - - - - 3I()
U1U2<>_1
f1 Start1
f1 Start2
Start 2 NC NC NC NC NC NC -
Start 2a - - - - - - NC
Start 2b - - - - - - NC
BSOUT 3I>>--> 3I>>--> 3I>> 3I>> 3I>> 3I>> 3I>>
3I>> 3I>>> 3I>>> 3I>>> 3I>>> 3I>>>
Alarm 1 I<->O CB1 open I<->O CB1 open I<->O CB1 open I<->O CB1 open I<->O CB1 open I<->O CB1 open I<->O CB1 open
I<->O CB1 close I<->O CB1 close I<->O CB1 close I<->O CB1 close I<->O CB1 close I<->O CB1 close I<->O CB1 close
3Ith> 3Ith> 3Ith> 3Ith> MCS 3I MCS 3I MCS 3I
MCS 3I MCS 3I MCS 3I MCS 3I TCS1 TCS1 TCS1
TCS1 TCS1 TCS1 TCS1 PQ 3Inf har PQ 3Inf har PQ 3Inf har
PQ 3Inf har PQ 3Inf har PQ 3Inf har PQ 3Inf har PQ 3Inf cum PQ 3Inf cum PQ 3Inf cum
PQ 3Inf cum PQ 3Inf cum PQ 3Inf cum PQ 3Inf cum CB wear1 CB wear1 CB wear1
CB wear1 CB wear1 CB wear1 CB wear1 MCS 3U MCS 3U MCS 3U
MCS 3U MCS 3U MCS 3U MCS 3U PQ 3Unf har PQ 3Unf har PQ 3Unf har
PQ 3Unf har PQ 3Unf har PQ 3Unf har PQ 3Unf har PQ 3Unf cum PQ 3Unf cum PQ3Unf cum
PQ 3Unf cum PQ 3Unf cum PQ 3Unf cum PQ 3Unf cum TIME1
FUSEF
Alarm 2 NC See Alarm 1 See Alarm 1 See Alarm 1 NC NC See Alarm 1
O-->I Active NC NC NC NC - - -
O-->I Alarm1 NC NC NC NC - - -
O-->I Alarm2 NC NC NC NC - - -
HSPO1 NC NC NC NC NC NC NC
Lockout
Restart - - - - - - NC
Enable
97
REX 521 Protection Relay 1MRS751802-MUM
98
1MRS751802-MUM Protection Relay REX 521
99
REX 521 Protection Relay 1MRS751802-MUM
100
1MRS751802-MUM Protection Relay REX 521
8.1. Protection
101
REX 521 Protection Relay 1MRS751802-MUM
102
1MRS751802-MUM Protection Relay REX 521
103
REX 521 Protection Relay 1MRS751802-MUM
104
1MRS751802-MUM Protection Relay REX 521
105
REX 521 Protection Relay 1MRS751802-MUM
3I> 3I>>
CBFP CBFP
BACTRL START BACTRL START
BS1 TRIP BS1 TRIP
BS2 CBFP BS2 CBFP
GROUP GROUP
RESET DOUBLE
RESET
A051975
106
1MRS751802-MUM Protection Relay REX 521
3U> 3U>>
107
REX 521 Protection Relay 1MRS751802-MUM
108
1MRS751802-MUM Protection Relay REX 521
3U< 3U<<
109
REX 521 Protection Relay 1MRS751802-MUM
8.1.7. 3I2f>
The function block 3I2f> can be used for doubling the set start current of overcurrent
protection in a transformer magnetizing inrush situation, or at motor start-up, or for
blocking (stabilizing) overcurrent protection in a transformer magnetizing inrush
situation.
3I2f>
3I2f/I1f>
3dI/dt>
GROUP RESET
A051978
Three-phase transformer inrush and motor start-up current detector 3I2f> (68)
Ratio I 2f/I 1f 5...50%
Start current 0.10...5.00 x ln
Operation mode Not in use
Inrush mode
Start-up mode
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy Current meas.: ±2.5% of set value or ±0.01 x ln
Ratio I2f/I1f measurement: ±5.0% of set value
Start time Internal time <32 ms
Total time <40 ms
8.1.8. Iub>
The phase discontinuity protection function block Iub> is designed to be used for
protection against broken phase conductors in distribution networks. Definite-time
(DT) characteristic is always used.
110
1MRS751802-MUM Protection Relay REX 521
Iub>
3∆I>
CBFP
BS1 START
BS2 TRIP
GROUP CBFP
RESET
A051979
8.1.9. 3Ith>
The three-phase thermal overload protection function block 3Ith> is designed for the
thermal protection of three-phase power cables and overhead lines.
3Ith>
3
J>
Dev
CBFP
BLOCK START
RESET TRIP
CBFP
EN_RESTART
A051980
111
REX 521 Protection Relay 1MRS751802-MUM
8.1.10. O-->I
The majority (about 80...85%) of MV overhead line faults are transient and are
automatically cleared by momentarily de-energizing the line, whereas the rest of the
faults (15...20%) can be cleared by longer interruptions. The de-energization of the
fault place for a desired period of time is implemented by autoreclose (AR) relays
or functions. The autoreclosers are capable of clearing most of the faults. At a
permanent fault, the autoreclosing is followed by final tripping. A permanent fault
has to be located and cleared before the fault location can be re-energized.
The autoreclose function O-->I can be used for autoreclosing together with any
circuit breaker that has the characteristics required for autoreclosing. The function
block provides five programmable AR shots which can perform one to five
successive autoreclosures of desired type and duration, such as one high-speed and
one delayed autoreclosure. When the reclosing is initiated by the start of a protection
function, the AR function is capable of executing the final trip of the circuit breaker
in a short operate time in case the fault still persists when the last reclosure selected
has been carried out.
O I
AR1 ROPEN
AR2 RCLOSE
AR3 SHOT1
AR4 SHOT2
ARINH SHOT3
CBOPEN SHOT4
CBCLOSE SHOT5
ON AR1TRIP
RESET AR2TRIP
AR3TRIP
AR4TRIP
CB FAIL
DEFTRIP
LOCKOUT
TRDUE
TDDUE
ACTIVE
SHOT_ALARM
A051981
112
1MRS751802-MUM Protection Relay REX 521
The re-open (ROPEN) signal is connected directly to the HSPO1. The reclose signal
is routed to the close signal which can be connected to the output relays. The reclose
signal is depended on the interlocking scheme chosen for the control (COCB)
function. (See Fig. 8.1.10.-2.) Note that the open and the trip signal always overrides
the reclose and the close signal.
Sometimes it can be useful to get indications on the display cleared after a successful
autoreclosing. This can be done by selecting O-->I in input SWGRP Reset
indication. By default this option is disabled.
CB open and CB close via the AR function are disabled in REX 521.
O-->1 Active
SHOT1
O-->I 3I> Start SHOT2
O-->I 3I>> Start SHOT3
O-->I 3I>>> Start SHOT4
. SHOT5
. TRDUE
.
Initiation signals TDDUE
DI1...DI9 O-->I
Ext. start AR1 ACTIVE
AR2 ROPEN
AR3 RCLOSE
AR4 SHOT1 O-->1 Alarm 1
DI1...DI9 ARINH SHOT2
DI1...DI9 ARON SHOT3
AR1TRIP
SHOT4
CB pos. open AR2TRIP
CBOPEN SHOT5 AR3TRIP
CB pos. close CBCLOSE AR1TRIP AR4TRIP
AR2TRIP CBFAIL
Reset AR3TRIP
RESET DEFTRIP
AR4TRIP LOCKOUT
CB FAIL SHOT_ALARM
O-->I Trip 3I> DEFTRIP
O-->I Trip 3I>> LOCKOUT
O-->I Trip 3I>>> TRDUE
. TDDUE O-->1 Alarm 2
. ACTIVE
. SHOT_ALARM
DI1...DI9 Ext. trip
AR1TRIP
AR2TRIP
AR3TRIP
AR4TRIP
CBFAIL
DEFTRIP
LOCKOUT
SHOT_ALARM
A051982
Fig. 8.1.10.-2 Input and output signal overview for the autoreclose function
113
REX 521 Protection Relay 1MRS751802-MUM
Output SWGRP
A060141
Fig. 8.1.10.-3 Input and output signal overview for the AR function in H50
CB position act.
Opening a CB manually does not start the O-->I sequence. The selected signals in
the Input SWGRP are used to block the initiation of the O-->I sequence.
In order to allow the Master trip input signal to initiate the O-->I sequence,
O-->I INH must have a different DI selected than the Master trip input
signal. Both signals are found in Configuration/Input signals/. Both the
Master trip and the O-->I INH signals are by default configured to DI8.
114
1MRS751802-MUM Protection Relay REX 521
Standard
The input SWGRP determines the initiate signals that activates the O-->I sequence.
AR works like in other configurations where it is used.
Residual overvoltage protection, low-set stage, Uo> (59N-1), high-set stage, Uo>>
(59N-2) and instantaneous stage, Uo>>> (59N-3)
Start voltage 2.0...100.0% Un
Operate time 0.05...300.00 s
Operation mode Not in use
Definite time
Measuring mode Peak-to-peak
Fundamental frequency
Note! The values below apply when f/fn = 0.95...1.05
Operation accurcy ±2.5% of set value or ±0.01 x Un
Start time Injected voltages > 2.0 x start voltage:
internal time < 32 ms
total time < 40 ms
Reset time 40...1000 ms (Depends on the minimum pulse width set
for the trip output)
Reset ratio, typically 0.95
Retardation time Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms
Operate time accuracy in DT mode ±2% of set value or ±20 ms
115
REX 521 Protection Relay 1MRS751802-MUM
8.1.12. f1 and f2
The frequency function blocks operate as either underfrequency or overfrequency
protection depending on whether the set operate value is above or below the rated
frequency of the relay. The operation is insensitive to harmonics and the DC
component.
f1 f2
f< f<
f> f>
df/dt< df/dt<
df/dt> df/dt>
8.1.13. SYNC1
The function block is designed to be used for checking the conditions for circuit-
breaker closing. The function can be used for closing ring mains, interconnecting
busbars and connecting generators to the network. The harmonics are suppressed.
116
1MRS751802-MUM Protection Relay REX 521
SYNC
Command SC OK
A051985
Ist2t n<
GROUP START
STALL_IND TRIP
STALL
RESTART
A051986
117
REX 521 Protection Relay 1MRS751802-MUM
8.1.15. 3I()
The function block 3I() is designed for phase-reversal protection of motors
3I()
BLOCK START
GROUP TRIP
RESET CBFP
A051987
118
1MRS751802-MUM Protection Relay REX 521
I2> I2>>
Negative phase sequence (NPS) protection, low-set stage I2> (46-1) and high-set
stage I2>> (46-2)
Operation mode Not in use
Definite time
Inverse time
Start value 0.01...0.50 x In
Operate time 0.1...120.0 s
K 5.0...100.0 s
Start delay 0.1...60.0 s
Minimum time 0.1....120.0 s
Maximum time 500...10000 s
Cooling time 5...10000 s
Number of phases 2...3
Note! The values below apply when f/fn = 0.95...1.05:
Operation accuracies ±2.5% of set value or ±0.01 x In
Start time Injected negative-sequence current = 2.00 x start value:
internal time <32 ms
total time <40 ms 1
Reset time 40...1000 ms (depending on the minimum pulse width set
for TRIP output)
Reset ratio Typical 0.96 (range 0.96...0.98) in definite-time mode
Retardation time Total retardation time when negative-sequence current
drops below the start value <45 ms 2
Operate time accuracy in definite-time mode Depends on the frequency of the current measured:
±2% of set value or ±20 ms 2
Accuracy class index E in inverse-time mode Depends on the frequency of the current measured:
±2% of the calculated ideal operate time or ±20 ms 2
1
Includes the delay of the signal relay.
2
Includes the delay of the heavy-duty output relay.
8.1.17. 3I<
The undercurrent function block is designed to be used for non-directional three-
phase undercurrent protection. Usually the undercurrent function block indicates
loss of load for pumps, fans and conveyors. Protection is important if the pump is
cooled by the liquid it pumps, or if a broken conveyor belt may cause damage for
the process. Also a broken main circuit, problems with measuring devices, and loss
of supply can be indicated.
119
REX 521 Protection Relay 1MRS751802-MUM
3I<
BLOCK START
GROUP TRIP
RESET CBFP
A051989
8.1.18. FUSEF
Some voltage-based protection functions may mal-operate if a voltage measurement
circuitry is damaged or if the miniature circuit breaker (MCB) of the measurement
circuitry has opened for example due to an operation of the short-circuit protection.
A failure in the voltage measurement circuitry should, however, be repaired as soon
as possible to restore the blocked protection functions into use.
FUSEF
BSOUT
A051990
120
1MRS751802-MUM Protection Relay REX 521
Reset time (when task interval is 10 ms) 2 20 ms (within the same task)
Reset ratio 0.8...0.96 (for Ratio U2/U1>)
1.04...1.2 (for Ratio I2/I1<)
1
When BSOUT output is used for blocking function blocks that are executed in a slower task interval
than FuseFail, an additional delay has to be included in the block activation time
2
When BSOUT output is used for blocking function blocks that are executed in a slower task interval
than FuseFail, an additional delay has to be included in the reset time
8.1.19. 3Ithdev>
The function block protects a motor both from short- and long-duration overloads.
The start situation is a good example of short-duration overload since particularly at
start-up the rotor is in danger to be overloaded by the starting current. The starting
current can be in the range of five to seven times the rated current of the motor.
The motor start-ups also load stator windings. Especially when a warm motor is
restarted, the stator may constitute a limitation regarding thermal protection.
Because the function block calculates the temperature rise both for the stator and the
rotor individually, the motor can be fully protected by proper settings. Furthermore,
the thermal model of two-time constants enables detecting both short-time and long-
time overloadings.
3Ithdev>
3
J>
Dev
CBFP
BLOCK START
GROUP TRIP
RESET CBFP
EN_RESTART
A051991
121
REX 521 Protection Relay 1MRS751802-MUM
8.1.20. U1U2<>_1
The positive-sequence undervoltage function U1< is designed to be used to protect
small generating plant from asynchronous reclosure with the rest of the network, and
to protect the plant from loss of synchronism.
The function block is also used to protect against unwanted isolation of small
generating plant during one- or two-phase network unbalance. The level of positive
sequence voltage is found to be a good criteria when determining the criticality of
the network fault from the generating plant’s point of view.
Additionally, the function block can be used in unsuccessful reclosure protection in
cases where a small generating plant with a faulted feeder supplies fault current
which is too small to be detected by the current relays, but high enough to maintain
the arc.
The negative-sequence overvoltage function U2> is designed to be used to protect
motors against failure on one or more phases (single phasing), to protect against
excessive imbalance between phases, and to protect machines against reversal of
phase sequence both in forward and reverse rotation direction.
122
1MRS751802-MUM Protection Relay REX 521
U1U2<>_1
BLOCK START
GROUP TRIP
RESET
A051992
123
REX 521 Protection Relay 1MRS751802-MUM
8.2. Control
I<->O CB1
OPEN OOPEN
CLOSE OCLOSE
CLOSENA AOPEN
BINOPEN ACLOSE
BINCLOSE
A051993
I<->O POS
BINREMOTE
A051994
124
1MRS751802-MUM Protection Relay REX 521
8.2.5. ALARM1-8
The alarm indicating functions are used for controlling alarm LEDs. The following
configuration-specific signals can be connected to the alarm indicating functions :
Table 8.2.5-1 Basic B01
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8
3I> Start Io> Start Iub> Start DI1 DI1 MEAS HI ALARM MEAS LO ALARM CB wear1
3I> Trip Io> Trip Iub> Trip DI2 DI2 DI2 MEAS HI ALARM TCS1
3I>> Start Io>> Start 3Ith> Start DI3 DI3 DI3 DI3 MCS 3I
3I>> Trip Io>> Trip 3Ith> Trip DI4 DI4 DI4 DI4 DI4
3I>>> Start Io>>> Start DI5 DI5 DI5 DI5 DI5
3I>>> Trip Io>>> Trip DI6 DI6 DI6 DI6 DI6
DI7 DI7 DI7 DI7 DI7
DI8 DI8 Interlocking Lockout DI8
125
REX 521 Protection Relay 1MRS751802-MUM
126
1MRS751802-MUM Protection Relay REX 521
127
REX 521 Protection Relay 1MRS751802-MUM
8.3. Measurement
8.3.1. 3I
The measurement function block 3I measures the true RMS phase currents, that is,
harmonics are not suppressed. The current values are updated once a fundamental
frequency cycle, that is, the integration time for the true RMS calculation is one
fundamental cycle.
3I
IL1
IL2
IL3
A051995
8.3.2. Io
The neutral current measurement function block Io measures the true RMS neutral
current, that is, harmonics are not suppressed. The current values are updated once
a fundamental frequency cycle, that is, the integration time for the true RMS
calculation is one fundamental cycle
Io
Io
A051996
8.3.3. Uo
The function block Uo measures either the true RMS residual voltage, that is,
harmonics are not suppressed, or the numerically calculated fundamental
component amplitude of the residual voltage. A HMI parameter or a serial
communication parameter can be used for selecting the measuring mode. The
voltage value is updated once a fundamental frequency cycle, that is, the integration
time for the true RMS calculation, is one fundamental cycle.
128
1MRS751802-MUM Protection Relay REX 521
Uo
Uo
A051997
8.3.4. DREC
The transient disturbance recorder DREC is used for recording current waveforms
and, when available, voltage waveforms. Furthermore, start and trip signals from the
protection functions are recorded. The amount of recorded signals is standard
configuration specific; refer to the block diagram of the standard configuration.
The default setting for the analogue channels recorded in DREC does not include I0b
measurement. When I0b is in use and it is wanted to record data, the used analogue
channel setting has to be changed in Main menu\Measurement\DREC\
General info\AI chs used.
Recording can be triggered on the rising or falling edge of any or several of the
digital inputs, on an adjustable level of overcurrent, overvoltage or undervoltage, or
the recording can be triggered manually via the HMI, via serial communication or a
parameter, or using a periodic triggering.
Notice that the recordings will be cleared if setting some of the parameters which
cause the device to reset.
Refer to Technical Reference Manual, General, chapter "Relay Setting Tool view"
(see Section 1.3. Related documents).
DREC
IL1 Start 3I>
IL2 Start 3I>>
IL3 Start 3I>>>
Io Start Io>
Iob Start Io>>
BI1 Start Io>>>
BI2 Start 3Iub>
BI3 Start 3Ith>
BI4 Trip 3I>
BI5 Trip 3I>>
BI6 Trip 3I>>>
BI7 Trip Io>
BI8 Trip Io>>
BI9 Trip Io>>>
BI10 Trip 3Iub>
BI11 Trip 3Ith>
BI12
BI13
BI14
BI15
BI16
EXT_TRG
A051998
129
REX 521 Protection Relay 1MRS751802-MUM
The recording can be triggered by any (or several) of the alternatives listed below:
• triggering on the rising or falling edge of any (or several) of the digital inputs
• triggering on undercurrent, undervoltage
• triggering via serial communication or a parameter
• periodic triggering
The recording length depends on the number of recordings and inputs used. For example, the following
combination of recording length, number of recordings and number of inputs is available at 50 Hz
(in parentheses the total recording time at 60 Hz):
# recordings \ # inputs 1 2 3 4a 5 6 7b
1066 cyc. 581 cyc. 399 cyc. 304 cyc. 246 cyc. 206 177 cyc.
1 21.3 s 11.6 s 8.0 s 6.1 s 4.9 s ( 4.1 s 3.5 s
(17.8 s) (9.7 s) (6.7 s) (5.1 s) 4.1 s) (3.4 s) (3.0 s)
212 cyc. 116 cyc. 79 cyc. 60 cyc. 49 cyc. 41 35 cyc.
5 4.2 s 2.3 s 1.6 s 1.2 s 1.0 s 0.8 s 0.7 s
(3.5 s) (1.9 s) (1.3 s) (1.0 s) (0.8 s) (0.7 s) (0.6 s)
106 cyc. 57 39 cyc. 30 cyc. 24 cyc. 20 cyc. 17 cyc.
10 2.1 s 1.1 s ( 0.8 s 0.6 s 0.5 s 0.4 s 0.34 s
(1.8 s) 1.0 s) (0.7 s) (0.5 s) (0.4 s) (0.3 s) (0.28 s)
a. Used in Basic and Medium configurations
b. Used in High and Sensor configurations
130
1MRS751802-MUM Protection Relay REX 521
Table 8.3.4-1 DREC digital inputs (Trip 1...5 are Output SWGRP signals.)
Input B01/B02 M01/M02 H01 a H02 H03 H04
BI1 Start 3I> Start 3I> Start 3I>--> Start 3I>--> Start 3I> Start 3I>
BI2 Start 3I>> Start 3I>> Start 3I>>--> Start 3I>>--> Start 3I>> Start 3I>>
BI3 Start 3I>>> Start 3I>>> Start 3I>>> Start 3I> Start 3I>>> Start 3I>>>
BI4 Start Io> Start Io>--> Start Io>--> Start 3I>> Start Io>--> Start Io>-->
BI5 Start Io>> Start Io>>--> Start Io>>--> Start Io>--> Start Io>>--> Start Io>>-->
BI6 Start Io>>> Start Io>>>--> Start Io>>>--> Start Io>>--> Start Io>>>--> Start Io>>>-->
BI7 Start Iub> Start Iub> Start Iub> Start Io>>>--> Start Iub> Start Io>
BI8 Start 3Ith> Start 3Ith> Start 3Ith> Start Iub> Start 3Ith> Start Io>>
BI9 Trip 3I> Trip 3I> Trip 3I>--> Start 3Ith> Trip 3I> Start Io>>>
BI10 Trip 3I>> Trip 3I>> Trip 3I>>--> Start1 f1 Trip 3I>> Start Iub>
BI11 Trip 3I>>> Trip 3I>>> Trip 3I>>> Start2 f1 Trip 3I>>> Start 3Ith>
BI12 Trip Io> Trip Io>--> Trip Io>--> Trip1 Trip Io>--> Start 3I>-->
BI13 Trip Io>> Trip Io>>--> Trip Io>>--> Trip2 Trip Io>>--> Start1 f1
BI14 Trip Io>>> Trip Io>>>--> Trip Io>>>--> Trip3 Trip Io>>>--> Start2 f1
BI15 Trip Iub> Trip Iub> Trip Iub> Trip4 Trip Iub> Trip1
BI16 Trip 3Ith> Trip 3Ith> Trip 3Ith> Trip5 Trip 3Ith> Trip2
BI2 Start 3I>> Start 3I>> Start 3I>> Start 3I>> Start 3I>> Start 3I>>
BI3 Start 3I>>> Start 3U> Start 3I>>> Start 3I>>> Start 3I>>> Start 3I>>>
BI4 Start Io> Start 3U>> Start Io>--> Start Io> Start Io> Start Io>-->
BI5 Start Io>> Start 3U< Start Io>>--> Start Io>> Start Io>> Start Io>>-->
BI6 Start Io>>> Start 3U<< Start Io> Start Io>>> Start Io>-->/Io>>--> Start Io>/Io>>
BI7 Start 3U> Start Uo> Start Io>> Start 3U> Start 3I>-->/3I>>--> Start 3U</3U>
BI8 Start 3U>> Start Uo>> Start 3Ithdev> Start 3U>> Start 3U>/3U>> Start 3Ithdev>
BI9 Start 3U< Start Uo>>> Start I2>/I2>> Start 3U< Start 3U</3U<< Start I2>
BI10 Start 3U<< Start 1 f1 Start Is2t n< Start 3U<< Start 1/Start 2 f1 Start Is2t, n<
BI11 Start Uo> Start 2 f1 Start 3I< Start Uo> Start 1/Start 2 f2 Start 1/Start 2 f1
BI12 Start Uo>> Start 1 f2 Start 3U>/3U>> Start Uo>> Start Uo> Start 1/Start 2 f2
BI13 Start Uo>>> Start 2 f2 Start 3U</3U<< Start Uo>>> Start Uo>> Start 3I>>-->
131
REX 521 Protection Relay 1MRS751802-MUM
8.3.5. 3U
The measurement function block 3U measures true RMS phase-to-earth or phase-to-
phase voltages. If voltage dividers are used, as in configurations H01S-H07S, only
phase-to-earth voltages can be measured. If voltage transformers are used, as in
configurations H02-H07, H50 and H51 only phase-to-phase voltages can be
measured. As an exception from these, in configurations H08 and H09, voltage
transformers are used and phase-to-earth voltage is measured. The voltage values
are updated once per fundamental frequency cycle, that is, the integration time for
true RMS calculation is one fundamental cycle.
3U
UL1_U12
UL2_U23
UL3_U31
A051999
8.3.6. 3U_B
The measurement function block 3U_B measures true RMS phase-to-earth or phase-
to-phase voltages. In configurations H08 and H09, 3U_B measures the calculated
phase-to-phase voltage. The voltage values are updated once per fundamental
frequency cycle, that is, the integration time for true RMS calculation is one
fundamental cycle.
3U_B
UL1_U12
UL2_U23
UL3_U31
A052000
132
1MRS751802-MUM Protection Relay REX 521
8.3.7. f
The measurement function block f measures the frequency of the network.
A052001
8.3.8. PQE
The measurement function block PQE measures fundamental frequency three-phase
power and energy.
PQE
A052002
8.3.9. AI1
The analog measuring block is used for supervising current limits and for
determining the state of the motor (running/stopped) in H07 and H51.
AI1
LOW ALARM
HIGH ALARM
A052003
133
REX 521 Protection Relay 1MRS751802-MUM
8.4.1. CB wear1
In the circuit-breaker wear function block CB wear1, calculating the electrical wear
of the circuit breaker is based on the current in each phase before opening. The
breaker wear is calculated for each phase separately and when the accumulated
breaker wear has reached the setting value, the function block will issue an alarm
signal.
The function block uses a 16-point setting table
(Main menu\Cond.Monit.\CB wear1\ Control settings) for the
current and the corresponding breaker wear value. The calculation is based on linear
interpolation using the table. Typically, the breaker wear increases in proportion to
the square of the current. However, the interpolation table solution provides a close
match and facilitates the configuration.
CB wear
OPEN ALARM
BINOPEN
BINCLOSE
A052004
8.4.2. TCS1
The trip-circuit supervision function block TCS1 does not perform the supervision
itself but it is used as an aid for configuration. The functional part belongs mainly to
the self-supervision tasks of the PS_ card.
TCS1
TCSSTATE
BS ALARM
A052005
8.4.3. MCS 3I
The supervision function block MCS 3I detects interruptions in energizing current
circuits. The function block supervises the energizing circuits by comparing the
measured phase currents. If one or two phase currents exceed the setting “High
limit”, while the measured phase current in the remaining one or two phases is below
the setting “Low limit”, the output ALARM is activated after the adjustable alarm
delay.
The function block is disabled if all input currents are below the setting “Low limit”.
The ALARM output will reset automatically when the fault disappears.
The phase current supervision function block operates on the numerically calculated
fundamental frequency component of the phase currents.
MCS 3I
ALARM
A052006
134
1MRS751802-MUM Protection Relay REX 521
8.4.4. MCS 3U
The supervision function block MCS 3U detects interruptions in energizing voltage
circuits. The user can select three-phase or two-phase operation. The function block
can also be set out of use by means of the parameter.
The function block supervises the energizing circuits by comparing the measured
voltages. If one or two voltages exceed the setting “High limit”, while the measured
values of the remaining one or two voltages are below the “Low limit”, the output
ALARM is activated after the set alarm delay.
The function block is disabled if all input voltages are below the setting “Low limit”.
The ALARM output resets automatically when the fault disappears.
MCS 3U
ALARM
A052007
8.4.5. TIME1
The time measuring block TIME1 is used for measuring the motor running time in
H07 and H51.
TIME1
ALARM
A052008
135
REX 521 Protection Relay 1MRS751802-MUM
8.5.1. PQ 3Inf
The current waveform distortion measurement function block PQ 3Inf is used for
measuring the harmonics and monitoring the power quality in distribution networks.
Although the European Standard EN 50160 concerns voltage distortion, the same
standard is applied to current distortion measurements in PQ 3Inf. Measuring
principles for individual harmonics and THD are adapted from the International
standard IEC 61000-4-7. The American standard IEEE Std 1159 is also partly
supported.
The function block measures quasi-stationary (slowly varying) harmonics up to
13th. Distortion measurement does not include rapidly changing harmonics,
interharmonics or other spurious components.
PQ 3Inf
TRIGG HAR_HIGH
RESET CUM_HIGH
A052009
136
1MRS751802-MUM Protection Relay REX 521
8.5.2. PQ 3Unf
The function block PQ 3Unf is used for measuring the harmonics and monitoring
the power quality in distribution networks. Power quality measurements carried out
by the function block PQ 3Unf follow the European Standard EN 50160. Data
collection and analysis is done according to EN 50160. Measuring principles for
individual harmonics and THD are adapted from the International standard IEC
61000-4-7. The American standard IEEE Std 1159 is also partly supported.
The function block measures quasi-stationary (slowly varying) harmonics up to
13th.
Distortion measurement does not include rapidly changing harmonics,
interharmonics or other spurious components.
PQ 3Unf
TRIGG HAR_HIGH
RESET CUM_HIGH
A052010
137
REX 521 Protection Relay 1MRS751802-MUM
8.6.2. Selectors
The selectors are used for routing signals and connecting inputs. Every digital input
can be connected to an input signal (for example Blocking 1, Master trip) via a
selector. Likewise, an output signal can be connected to an output relay (Trip1,
Alarm 1) via a selector.
138
1MRS751802-MUM Protection Relay REX 521
9. Example substations
All the application examples are designed for typical HV/MV substations like
below.
3I 2f > 68 TC S
CBCM 0 I
C B FP 62
3 I~ harm R
3I I0
REX 5 2 1 B 0 1
I 0> TC S
50N/51N
CBCM 0 I
C B FP 62
3 I~ harm R
3I I0
REX 5 2 1 B 0 1
I 0> TC S
TC S 50N/51N
I 0> 50N/51N
CBCM 0 I
CBCM 0 I I> 46
I> 46
3 I~ harm R
3 I~ harm R 3 49F
3 49F
C B FP 62
C B FP 62
0 I 79 3I I0
3I I0
REX 5 2 1 B 0 1
REX 5 2 1 B 0 2
A052011
139
REX 521 Protection Relay 1MRS751802-MUM
CBCM 0 I
CBFP 62
3I~harm R
3I
U0
CBFP 62 CBFP 62
0 I 79 I0
3I 3I I0
U0 U0
140
1MRS751802-MUM Protection Relay REX 521
3I> 67 3I> 67
U 0> 59N 3I > 50/51 3I> 50/51 3I > 50/51 U 0> 59N
A052013
141
142
1MRS751802-MUM Protection Relay REX 521
10.1.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Overcurrent protection
• Non-directional earth-fault protection
• Phase discontinuity protection
• Thermal overload protection for cable/line
The network is either resistance or solidly earthed. The three-phase current
measurement is established with a set of current transformers. The neutral current is
measured in a residual connection.
I 0> TC S
50N/51N
CBCM 0 I
I> 46
3 I~ harm R
3 49F
C B FP 62
3I I0
143
REX 521 Protection Relay 1MRS751802-MUM
Circuit-breaker failure
protection
REX 521
ES
CB
A052015
144
1MRS751802-MUM Protection Relay REX 521
REX 521
A052016
Fig. 10.1.2.-1 Connection diagram of the standard configuration B01 with three
CTs in a residual connection
The technical data of the current transformers are set via the Relay Setting Tool or
the local HMI. The settings can be found in
Main menu\Configuration\Meas. devices\. Refer to
Technical Reference Manual, General (see Section 1.3. Related documents) for
further information about how to set the rated currents.
10.1.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
145
REX 521 Protection Relay 1MRS751802-MUM
For more information about the phase overcurrent blocking signals between the first
and the third application example, refer to the overview diagram on Fig. 10.3.5.-1.
The operation of the low-set overcurrent stage 3I> of the relay can be based on a
definite- or on an inverse-time characteristic. The operation characteristic is selected
within the settings of the low-set overcurrent function block. When the definite time
characteristic has been selected, the operate time of the relay is current independent.
On the contrary, when the inverse-time characteristic is in use, the operate time is a
function of the fault current level: the greater the fault current, the shorter the operate
time. Therefore, the operate time is short at close faults. The definite-time
characteristic can be used for obtaining the time grading steps over a wide current
range and it offers faster tripping times than the inverse time protection at low
multiples of the current settings.
The settings for the over current protections can be found in:
Main menu\Protection\3I>\ … \3I>>>\Setting group 1\. The
parameters Operation mode, Start current, Operate time and Time
multiplier for the function can be set in this setting group.
For example, in Main menu\Protection\3I>\ … \3I>>>\Control
setting\ the Drop-off time and the length of the trip signal, Trip pulse,
can be set.
The data of the three last operations, start or trip, are recorded and the values of the
most recent operation can be found in: Main menu\Protection\3I>\ …
\3I>>>\Recorded data1\…3\.
146
1MRS751802-MUM Protection Relay REX 521
While using the sensitive non-directional earth fault it is recommended to secure the
earth-fault functionality by using the start signal from a residual voltage relay to
release blocking of the earth-fault protection. By doing this, unnecessary trips are
avoided due to disturbances in the measured earth-fault current.
The settings for the earth-fault current protections can be found in
Main menu\Protection\Io>\ … \Io>>>\.
IL max – IL min
∆I = 100% × --------------------------------
IL max
Full unbalance (100%) occurs when a phase conductor is broken before the first load
on the phase. Due to asymmetrical load in the network, the normal unbalance has to
be considered when defining the start value. Since this type of protection cannot be
graded with other systems, it is confined to a supplementary role by the use of a long
time delay, adjustable from 1s up to 300 s.
The settings for the phase discontinuity protection can be found in
Main menu\Protection\Iub>\Setting group 1\, where the
parameters Operation mode, Start unbalance and Operate time for
the protection function can be set.
For example, the pulse length for the trip and the start signal can be set in
Main menu\Protection\Iub>\Control setting\.
147
REX 521 Protection Relay 1MRS751802-MUM
highest phase current value. The 3Ith> applies the thermal model of one time-
constant for temperature measurement, which means that both the temperature rise
and the cooling follow an exponential curve.
The following set values have to be defined for the 3Ith>: the time constant for the
rise and cooling of the cable, the maximum rated load current for the cable, the
maximum temperature allowed for the cable and the reference temperature in which
the rated current has been defined.
The Start output becomes active when the calculated conductor temperature exceeds
the setting of the Prior alarm parameter that can be given a value in the range
40% to 100%. The trip output is activated if the conductor temperature-rise
measured in per cents exceeds the value of the Trip temperature parameter
that can be set in the range 80% to 120%. The delayed trip is set into use by giving
the Trip temperature parameter a value higher than 100% and the Trip
delay parameter one higher than 0. For example, the trip temperature can be set to
120% and the trip delay to 60 min, in which case the function block trips when the
cable load remains above 100% for 60 minutes but does not exceed 120%.
The CU_ALARM output alarms when the measured current has exceeded the level
where, if it remains the same, the cable temperature will reach the maximum
temperature set for the cable.
After the thermal overload protection has tripped, reclosing is not possible until the
calculated conductor temperature falls below the value set for the Reclosure
temp parameter, because the function block holds the trip output active. If the re-
closing inhibit is chosen not to be used, the parameter is set to 100%.
In the initializing stage, that is, when the auxiliary voltage is connected to the relay,
the function block assumes that the cable temperature has risen to 50% of the
difference between the parameter values Maximum temp and Ambient temp.
For example, if the maximum temperature has been set to +90°C (cable with PEX
insulation) and the ambient temperature is set to +20°C, the relay assumes a
temperature of +55°C for the cable.
The necessary settings for the thermal overload protection can be found in:
Main menu\Protection\3Ith>\Setting group 1\.
The calculated temperatures of the conductor can be viewed in:
Main menu\Protection\3Ith>\Output data\.
148
1MRS751802-MUM Protection Relay REX 521
As the HSPO1 is always routed to the “Trip 1” output signal, the settings are made
directly in Main menu\Configuration\Output SWGRP\Trip 1 where
the checksum for the settings is displayed (255 by default).
Using HMI:
To change the settings for the Trip 1, go to Configuration\Output
SWGRP\Trip 1 and press the [E]-button. The different protection functions are
displayed one at a time. By pressing the [→ ] or [← ] navigation push button, it is
possible to scroll between the different protections. By pressing the [↑ ] or [↓ ]
navigation push button, the specific protection function trip signal can be connected
or disconnected. When the two-stage overcurrent (3I> and 3I>>>), two-stage earth
fault (Io> and Io>>), the unbalance and thermal overload protection are selected, the
checksum for the Trip 1 is 221.
Using Relay Setting Tool:
To change the settings for the Trip 1, go to the Configuration in config view
and Output SWGRP and select the “New value” on Trip 1. Press backspace to
change the value. In the “New value” window the protection functions that are used
can be marked or unmarked. The checksum can also be changed directly. Finally,
the new setting has to be sent to the relay with the Download button. For more
information about the tool, refer to Tools for Relays and Terminals, User’s Guide
(see Section 1.3. Related documents).
A052018
Fig. 10.1.4.1.-1 Changing the checksum value for the Trip 1 in the
Relay Setting Tool
149
REX 521 Protection Relay 1MRS751802-MUM
A052019
Fig. 10.1.4.1.-2 Setting Trip 1 signal in the Graphical I/O Setting Tool
150
1MRS751802-MUM Protection Relay REX 521
The status-indication signals are also routed from the digital inputs to the circuit
breaker function (I<->O CB1) via the input signal selectors. These settings can be
found in: Main menu\Configuration\Input Signals\, where the
different input signal names are displayed and the specific inputs selected. The
status-indication signals are named as “CB pos. open” and “CB pos. close”.
Using the HMI:
To change the settings for “CB pos. open” go to the Configuration\Input
Signals\ and scroll with the [↑ ] or [↓ ] navigation push button to “CB pos. open”
and press the [E]-button. The different digital inputs are displayed one at a time by
selecting with the [↑ ] or [↓ ] navigation push button. Select DI1 and press the [E]-
button to confirm. Scroll to the “CB pos. close” and select the DI2 input.
Using Relay Setting Tool:
To change the settings for the CB pos. open go to the Configuration/Input Signals
and find CB pos. open. Select DI1 in the pull-down menu. For more information,
refer to Tools for Relays and Terminals, User’s Guide (see Section 1.3. Related
documents).
A052020
Fig. 10.1.4.2.-1 Selecting the digital input for the status indication of the breaker in
the Relay Setting Tool
In this application example the open and close push buttons are connected to the
digital inputs DI7 and DI8. Normally these buttons are connected directly to the
open or close circuits of the breaker. By including these to the relay, it is possible to
monitor the whole opening and closing time of the breaker and it is also possible to
151
REX 521 Protection Relay 1MRS751802-MUM
define the pulse width for the open and close pulse. The manual opening and closing
via push buttons are also disabled when the relay is set to remote mode, and vice
versa when the relay is in local mode, the remote control is disabled. If the breaker
is interlocked and the interlocking scheme is used with one or more digital inputs
configured to the “CLOSEENA” input signal, no close pulse will be sent from the
relay. The open and close input signals have to be selected via the
Configuration\Input Signals\ menu in the same way as for the breaker
status indication signals.
CB 0
REX521
A052021
Fig. 10.1.4.2.-2 Connection diagram for the standard configuration B01 with the breaker status indication and
the control signals for opening and closing of the circuit breaker
152
1MRS751802-MUM Protection Relay REX 521
10.1.5. Implementations
In the sections below a few implementation examples for the standard configuration
B01 are presented.
153
REX 521 Protection Relay 1MRS751802-MUM
The settings for the breaker failure are set separately for each protection function.
For example, to set the CBFP time for the 3I>> go to
Main menu\Protection\3I>>\Control settings, where it is possible
to set the CBFP time from 100 ms to 1000 ms. The control parameter Trip
pulse sets the width of the trip output signal, but also of the CBFP output signal.
The CBFP signals from the protection functions are routed to the output signals via
the output switchgroups. These settings can be found in
Main menu\Configuration\Output SWGRP\CBFP. When the three-stage
overcurrent, the two-stage earth fault, the unbalance and thermal overload protection
are selected the checksum for the CBFP is 223.
The CBFP signal is then connected to any of the output relays, via
Main menu\Configuration\Output Signals\. In this example, the
circuit-breaker failure signal is connected to the power output 1, PO1.
154
1MRS751802-MUM Protection Relay REX 521
The alarm signal from the breaker wear function is routed via
Main menu\Configuration\Output SWGRP\Alarm 1\ or \Alarm 2\
to the output signal together with the other available alarm signals from the relay. If
the CB wear1 alarm alone is selected in Alarm 1, the checksum is 128.
The Alarm 1 signal is then connected to an output relay via
Main menu\Configuration\Output Signals\, and in this example, the
breaker wear alarm signal is connected to the signal output 1, SO1.
155
REX 521 Protection Relay 1MRS751802-MUM
DC
CB 0
ES
0
Breaker wear alarm
1
Circuit-breaker failure
protection
Blocking signal from
the residual voltage relay
to Io> Blocking signal to the incoming feeder
(START 3I>>)
REX521
A052022
Fig. 10.1.5.-1 Connection diagram for the standard configuration B01 with the breaker status indication, the
control and alarm signals.
156
1MRS751802-MUM Protection Relay REX 521
10.2.1. Features
This application example describes an incoming feeder to a single busbar including:
• Overcurrent protection
• Non-directional earth-fault protection
The network is resistance or solidly earthed. The three-phase current measurement
is established with current transformers. The neutral current is measured via a
current transformer located in the neutral earthing circuit on the LV side of the
power transformer.
CBCM 0 I
CBFP 62
3I~harm R
3I I0
CBCM 0 I
I> 46
3I~harm R
3 49F
CBFP 62
3I I0
Fig. 10.2.1.-1 B01 is used for protection, measuring and supervision on both an
incoming and an outgoing feeder in a single busbar system. The
supplying network is either solidly or resistance earthed
157
REX 521 Protection Relay 1MRS751802-MUM
1
TRIP circuit breaker
Circuit-breaker failure
protection
OC blocking signal to
the HV relay (3I>> START)
OC blocking signal
from the outgoing feeders
to the 3I>>> stage
0
REX521
*) Power flow direction
DC
CB
A052024
158
1MRS751802-MUM Protection Relay REX 521
REX 521
IncProt
10.2.3. Protection
All the necessary settings for the protection functions can be set by means of the
Relay Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
159
REX 521 Protection Relay 1MRS751802-MUM
If a fault occurs in the feeder, the overcurrent protection relay of the outgoing feeder
provides a blocking signal to the overcurrent protection relay of the incoming feeder.
If the fault should occur in the busbar system, no blocking signal is issued and the
3I>>> stage of the overcurrent protection of the in-feeder provides a trip signal to
the in-feeder circuit breaker. Therefore, when no auxiliary relay is used, it is possible
to use a minimum operate time of 100 ms when a fault in the busbar system occurs.
The needed time for blocking includes:
Start time of the relay + Input delay on the relay + Retardation time + Margin
(40 ms) to be blocked (30 ms) (20 ms)
(10 ms)
160
1MRS751802-MUM Protection Relay REX 521
instantaneous trip of the busbar system. On the other hand, it is difficult to find the
right setting value since a close-up fault in a feeder can cause the circuit breaker of
the in-feeder to trip instead of the feeder protection relay.
In a double busbar system where the busbar circuit breaker is closed and two main
transformers are connected in parallel, the breaking capacity of the circuit breakers
of the outgoing feeders may not be sufficient and so tripping should be carried out
by the circuit breaker of the in-feeder. Then the current setting of the outgoing
instantaneous stage 3I>>> is set to the same level as the breaking capacity of the
feeders. This means that if the fault current exceeds the breaking capacity of the
outgoing feeders, the tripping is performed by the protection of the in-feeder. An
external control signal can be used for shifting to the second settings when the
transformers are used in parallel operation. Then the stage 3I>>> is active in parallel
operation and inhibited or has other settings when the parallel operation is not used.
The settings for the overcurrent protections can be found in:
Main menu\Protection\3I>\ … \3I>>>\Setting group 1\ where
the parameters Operation mode, Start current and Operate time for
the function can be set. In Main menu\Protection\3I>\Control
setting\ can for example the Drop-off time and the length of the trip signal
Trip pulse be set. The data of the three last operations, start or trip, are recorded
and the values of the most recent operation can be found in
Main menu\Protection\3I>\Recorded data1\…3\.
161
REX 521 Protection Relay 1MRS751802-MUM
10.2.4. Implementations
In the sections below a few implementation examples for the standard configuration
B01 are presented.
162
1MRS751802-MUM Protection Relay REX 521
As mentioned above the start signal from the high-set overcurrent stage 3I>> can be
routed to the high-set stage 3I>> of the HV relay. To use the start signal of a
protection function, the signal has to be routed via
Main menu\Configuration\Output SWGRP\Start 1 or \Start 2.
When the start signal has been routed, the output relay has to be selected in
Main menu\Configuration\Output Signals. In this example, the
overcurrent start signal from the 3I>> stage is routed via Start 1 and then connected
to the signal output 2, SO2. The checksum in this application example for Start 1
is 2.
10.2.4.3. Earth-fault stage Io>>> used to trip the breaker on the HV side of
the transformer
The trip signal from the earth-fault instantaneous stage can be routed to an output
relay to trip the breaker on the HV side of the transformer. To use the trip signal from
the earth-fault function, the signal has to be routed via
Main menu\Configuration\Output SWGRP\Trip 2 or \Trip 3.
When the trip signal has been routed, the output relay has to be selected in
Main menu\Configuration\Output Signals.
In this example, the trip signal of the earth-fault stage Io>>> is routed via
Trip 2 and then connected to the power output 2, PO2. The checksum in this
application example for Trip 2 is 32.
163
REX 521 Protection Relay 1MRS751802-MUM
164
1MRS751802-MUM Protection Relay REX 521
0
CB
DC 1
1
OC-blocking signal to
HV-relay (3I>> START)
REX 521
A052026
Fig. 10.2.4.6.-1 Connection diagram for the standard configuration B01 with the
breaker-status indication, blocking-, control- and breaker failure
signals.
165
REX 521 Protection Relay 1MRS751802-MUM
10.3.1. Features
This application example describes a transformer feeder including:
• Overcurrent protection
• Inrush protection
The application described in this example can serve as a backup protection for a
differential protection of the transformer or as main protection for smaller
transformers.
3I 2f> 68 TCS
CBCM 0 I
CBFP 62
3I~harm R
3I I0
CBCM 0 I
CBFP 62
3I~harm R
3I I0
CBCM 0 I
I> 46
3I~harm R
3 49F
CBFP 62
3I I0
A052027
166
1MRS751802-MUM Protection Relay REX 521
Circuit-breaker failure
protection
REX 521
*)Power flow direction
DC
CB
A052028
167
REX 521 Protection Relay 1MRS751802-MUM
HV
REX 521
Fig. 10.3.2.-1 Connection diagram for the standard configuration B01 with three
current transformers
The technical data of the current transformers are set via the Relay Setting Tool or
the local HMI. The settings can be found in
Main menu\Configuration\Meas. devices\. Refer to Technical
Reference Manual, General (see Section 1.3. Related documents) for further
information about how to set the rated currents.
10.3.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
168
1MRS751802-MUM Protection Relay REX 521
169
REX 521 Protection Relay 1MRS751802-MUM
The signal from the inrush function is configured as an input signal to the standard
configuration and has to be routed to the overcurrent functions when taken into use.
The settings, for which overcurrent stage to double, are made in
Main menu\Input SWGRP\Double\.
10.3.4. Implementations
In the section below a few implementation examples for the standard configuration
B01 are presented.
10.3.4.1. Blocking signal from the MV relay on the secondary side of the
transformer
The start signal from the high-set overcurrent stage 3I>> of the MV relay (incoming
feeder) can be routed to the high-set stage 3I>> of the HV relay to block the
overcurrent protection stage. There are two input blocking signals, Blocking 1 and
Blocking 2, which can have different functions depending on the different
protections.
170
1MRS751802-MUM Protection Relay REX 521
On the overcurrent stages 3I>, 3I>> and 3I>>>, the Blocking 1 input signal is
connected to the BS1 input and the Blocking 2 input signal is connected to the BS2
input of the function. The BS1 in this application example will stop the DT or IDTM
timer and the BS2 will block the trip signal. Refer to the CD-ROM Technical
Descriptions of Functions (see Section 1.3. Related documents) for more
information about the different protection function blocks.
In this application example the digital input DI9 is connected to the input signal
Blocking 1 and then routed to the BS1 input of the overcurrent stage 3I>>. The
Blocking 1 signal can be found in Main menu\Configuration\Input
Signals\Blocking 1\ where DI9 is selected. The checksum for the
switchgroup in Main menu\Configuration\Input SWGRP\
Blocking 1\ should be 2 to block the 3I>>.
171
REX 521 Protection Relay 1MRS751802-MUM
0
CB
DC 1
REX 521
A052030
Fig. 10.3.4.2.-1 Connection diagram for the standard configuration B01 with
breaker status indication, blocking, control and breaker failure
signals.
172
1MRS751802-MUM Protection Relay REX 521
REX521 Application
3I> example 3
BS
3I>>
3I>>>
TRIP
REX521 Application
START 3I>>
3I> example 2
3I>>
BS 3I>>>
TRIP
REX521 Application
example 1
START 3I>>
3I>
3I>>
3I>>>
TRIP
A052031
Fig. 10.3.5.-1 Phase overcurrent blocking signal overview diagram for the first
three application examples with trip signals from the different
overcurrent stages
173
REX 521 Protection Relay 1MRS751802-MUM
10.4.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Autoreclose function
• Overcurrent protection
• Non-directional earth-fault protection
• Phase discontinuity protection
• Thermal overload protection for cable/line
The network is either resistance or solidly earthed. Three-phase current
measurement is established with a set of current transformers and the neutral current
is measured in a residual connection.
CBCM 0 I
I> 46
3I~harm R
3 49F
CBFP 62
0 I 79 I0
3I
174
1MRS751802-MUM Protection Relay REX 521
1
TRIP circuit breaker
Circuit-breaker failure
protection
External reclosure
initialization signal
REX 521
*)Power flow direction
DC
CB
ES
A052033
175
REX 521 Protection Relay 1MRS751802-MUM
REX 521
A052016
Fig. 10.4.2.-1 Connection diagram for the standard configuration B02 with three
CTs in a residual connection
The technical data of the current transformers are set via the Relay Setting Tool or
the local HMI. The settings can be found in
Main menu\Configuration\Meas. devices\. Refer to REX 521
Technical Reference Manual, General (see Section 1.3. Related documents) for
further information about how to set the rated currents.
10.4.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
The following protection functions can be implemented in the same way as in the
first application example (see Section 10.1. Outgoing feeder, Basic B01):
• Overcurrent protection
• Earth-fault protection
• Phase discontinuity protection
• Thermal overload protection
176
1MRS751802-MUM Protection Relay REX 521
Instant of fault
AR1
(Start signal
from protection)
Trip
Circuit breaker
Shot 1 Shot 2 Shot 3
Start Start Start
delay delay delay
0.1 s 0.3 s 0.2 s
Open signal
Shot 1 Shot 2
Dead time Dead time
0.3 s 120 s
Close signal
A052034
177
REX 521 Protection Relay 1MRS751802-MUM
Instant of fault
Start
Protection
AR1 operation
(Trip signal time
from protection)
Circuit breaker
Shot 1 Shot 2
Dead time Dead time
Close signal
Discrimination
Time
Alarm
Definite Trip
A052035
178
1MRS751802-MUM Protection Relay REX 521
179
REX 521 Protection Relay 1MRS751802-MUM
0
CB
REX 521
A052036
Fig. 10.4.5.-1 Connection diagram for the standard configuration B02 with
breaker status indication and the control signals for opening and
closing of the circuit breaker
10.4.6. Implementations
In the section below a few implementation examples for the standard configuration
B02 are presented.
180
1MRS751802-MUM Protection Relay REX 521
DC
0
CB
ES
External re-closure
initialization signal
Definite Trip Alarm
REX 521
A052037
Fig. 10.4.6.2.-1 Connection diagram for the standard configuration B02 with the
breaker status indication, control and alarm signals.
181
182
1MRS751802-MUM Protection Relay REX 521
11.1.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Overcurrent protection
• Directional earth-fault protection
• Phase discontinuity protection
• Thermal overload protection for cable/line
The network is compensated earthed or isolated. Three-phase current measurement
is established with a set of current transformers and the neutral current is measured
with a cable transformer. The residual voltage is measured with a set of voltage
transformers in an open-delta connection.
CBCM 0 I
I> 46
3I~harm R
3 49F
CBFP 62
3I I0
U0
Fig. 11.1.1.-1 REX 521 M01 used for protection, measuring and supervision on
an outgoing feeder in a single busbar system. The system earthing
of the supplying network is either compensated or isolated.
183
REX 521 Protection Relay 1MRS751802-MUM
1
TRIP circuit breaker
Circuit-breaker failure
protection
5
v
REX 521
100V
0,2
dn
DC
CB
ES
A052039
184
1MRS751802-MUM Protection Relay REX 521
da dn
100V
v Uo
0,2
5 b
REX 521
A052040
11.1.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
The following protection functions can be implemented in the same way as in the
first application example (see Section 10.1. Outgoing feeder, Basic B01).
• Overcurrent protection
• Phase discontinuity protection
• Thermal overload protection
185
REX 521 Protection Relay 1MRS751802-MUM
186
1MRS751802-MUM Protection Relay REX 521
CB 0
REX 521
A052041
Fig. 11.1.3.3.-1 Connection diagram for the standard configuration M01 with
breaker status indication and control signals for opening and
closing of the circuit breaker
11.1.4. Implementations
In the section below a few implementation examples for the standard configuration
M01 are presented.
187
REX 521 Protection Relay 1MRS751802-MUM
In this example the digital input DI8 is connected to the input signal BACTRL and
then routed to the BACTRL input of the directional earth-fault functions. The
BACTRL signal can be found in Main menu\Configuration\Input
Signals\BACTRL\ where DI8 is selected. The checksum for the switchgroup in
Main menu\Configuration\Input SWGRP\BACTRL\ should be 3 to change the
angle on Io>--> and Io>>-->. Refer to the CD-ROM Technical Descriptions of
Functions (see Section 1.3. Related documents) for more information about the basic
angle control (directional earth-fault function).
188
1MRS751802-MUM Protection Relay REX 521
The CBFP signals from the protection functions are routed to the output signals via
the output switchgroups. These settings can be found in
Main menu\Configuration\Output SWGRP\CBFP. When the two-stage
overcurrent, the two-stage directional earth fault, the unbalance and thermal
overload protection are selected the checksum for CBFP will be 221.
The CBFP signal is then connected to any of the output relays via
Main menu\Configuration\Output Signals\, and in this example the
circuit-breaker failure signal is connected to power output 1, PO1.
189
REX 521 Protection Relay 1MRS751802-MUM
DC
0
CB
ES
REX 521
A052042
Fig. 11.1.4.5.-1 Connection diagram for the standard configuration M01 with
breaker status indication, control and alarm signals.
190
1MRS751802-MUM Protection Relay REX 521
11.2.1. Features
This application example describes an incoming feeder to a single busbar including:
• Overcurrent protection
• Residual voltage protection
The network is either compensated earthed or isolated. The three-phase current
measurement is established with current transformers and the residual voltage is
measured with a set of voltage transformers in an open-delta connection.
CBCM 0 I
CBFP 62
3I~harm R
3I
U0
Fig. 11.2.1.-1 REX 521 M01 used for protection, measuring and supervision on
an incoming feeder in a single busbar system. The system earthing
on the supplying network is compensated or isolated.
191
REX 521 Protection Relay 1MRS751802-MUM
1
TRIP circuit breaker
Circuit-breaker failure
protection
OC blocking signal to
the HV relay (3I>> START)
OC blocking signal
from the outgoing feeders
to the 3I>>> stage
Second settings
b
Uo
0
REX 521
100V
0,2
dn
da
A
DC
CB
A052044
192
1MRS751802-MUM Protection Relay REX 521
100V
v Uo
0,2
5 b
da dn
REX 521
Fig. 11.2.2.-1 Connection diagram for the standard configuration M01 for
protection of an incoming feeder and as back-up protection of the
outgoing feeders
The technical data of the current transformers and the voltage transformer are set via
the Relay Setting Tool or the local HMI. The settings can be found in
Main menu\Configuration\Meas. devices\. Refer to REX 521
Technical Reference Manual, General (see Section 1.3. Related documents) for
further information about how to set the rated currents and voltage.
193
REX 521 Protection Relay 1MRS751802-MUM
11.2.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
11.2.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
194
1MRS751802-MUM Protection Relay REX 521
11.2.5. Implementations
In the sections below a few implementation examples for the standard configuration
M01 are presented.
11.2.5.1. Start signal from the second residual voltage stage to release
blocking
The start signal from the residual voltage high stage can be routed to an output relay
to release the blocking signal for the non-directional earth-fault stages on the
outgoing feeders of the network. To use the start signal from the residual protection
function, the signal has to be routed via
Main menu\Configuration\Output SWGRP\Start 1 or \Start 2.
When the start signal has been routed, the output relay has to be selected in
Main menu\Configuration\Output Signals.
In this example, the directional earth-fault stage Io>>--> is configured as a Uo>>
protection and the start signal is routed via Start 1 and then connected to the signal
output 2, SO2. The checksum in this application example for Start 1 is 16.
195
REX 521 Protection Relay 1MRS751802-MUM
196
1MRS751802-MUM Protection Relay REX 521
197
REX 521 Protection Relay 1MRS751802-MUM
0
CB
DC 1
0
Second settings
OC-blocking signal to
HV-relay (3I>> START)
1
Uo>> Start to release blocking
of outgoing feeders
Circuit-breaker failure
protection
OC-blocking signal
from outgoing-feeders
to 3I>>> stage Uo>> TRIP to outgoing feeders
REX521
A052046
Fig. 11.2.5.7.-1 Connection diagram for the standard configuration M01 with
breaker status indication, control and alarm signals.
198
1MRS751802-MUM Protection Relay REX 521
11.3.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Autoreclose function
• Overcurrent protection
• Directional earth-fault protection
• Phase discontinuity protection
• Thermal overload protection for cable/line
The network is either compensated or isolated. Three-phase current measurement is
established with a set of current transformers and the neutral current is measured
with a cable transformer. The residual voltage is measured with a set of voltage
transformers in an open-delta connection.
CBCM 0 I
I> 46
3I~harm R
3 49F
CBFP 62
0 I 79 I0
3I
U0
Fig. 11.3.1.-1 REX 521 M02 used for protection, measuring and supervision on
an outgoing feeder in a single busbar system. The supplying
network is either compensated or isolated.
199
REX 521 Protection Relay 1MRS751802-MUM
1
TRIP circuit breaker
Circuit-breaker failure
protection
5
v
REX 521
100V
0,2
dn
DC
CB
ES
A052048
200
1MRS751802-MUM Protection Relay REX 521
da dn
100V
v Uo
0,2
5 b
REX 521
11.3.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
The overcurrent, the phase discontinuity and thermal overload protection can be
implemented in the same way as in the first application example (see Section 10.1.
Outgoing feeder, Basic B01) and the directional earth-fault protection as in the fifth
application example (seec Section 11.1. Outgoing feeder, Medium M01).
201
REX 521 Protection Relay 1MRS751802-MUM
In the following example two auto-reclosures initiated by the start of the protection
are carried out. The auto-reclosures are subject to a preset start-delay time initiated
from the start signal of the protection. The first auto-reclosure is delayed only
slightly to avoid unwanted auto-reclosures (100 ms). Shot 1 is a high-speed auto-
reclosure (short dead time 300 ms) mainly used for extinguishing the arc at the fault
place. Before the second shot is initiated, a longer start delay time is used to attempt
to burn the fault (300 ms). The dead time of Shot 2 is long, a so called delayed
autoreclose, that typically lasts minutes, (in this case 2 min). Should the fault still
persist when Shot 2 has been performed (after 200 ms), the final circuit-breaker
tripping will follow and a DEFTRIP alarm signal is activated and can be routed to
an output (contact if needed).
The operate time of the protection is longer than the operate times of the autoreclose
function and the final trip-time. Thus the protection operates as a back-up for the
autoreclose function, if the tripping carried out by the autoreclose function fails.
Instant of fault
AR1
(Start signal
from protection)
Trip
Circuit breaker
Shot 1 Shot 2 Shot 3
Start Start Start
delay delay delay
0.1 s 0.3 s 0.2 s
Open signal
Shot 1 Shot 2
Dead time Dead time
0.3 s 120 s
Close signal
A052034
202
1MRS751802-MUM Protection Relay REX 521
Instant of fault
Start
Protection
AR1 operation
(Trip signal time
from protection)
Circuit breaker
Shot 1 Shot 2
Dead time Dead time
Close signal
Discrimination
Time
Alarm
Definite Trip
A052035
203
REX 521 Protection Relay 1MRS751802-MUM
method chosen for closing of the breaker. If the trip is activated during the close-
pulse period, the close signal is deactivated. Alarms and action signals are available
as three different signals from the autorecloser. The signals can be found in
Main menu\Configuration\Output SWGRP\ and they are named as
O-->I ACTIVE, O-->I Alarm1 and O-->I Alarm2. Refer to the CD-ROM
Technical Descriptions of Functions (see Section 1.3. Related documents) for more
information about the auto-reclosing function.
0
CB
REX 521
A052050
Fig. 11.3.5.-1 Connection diagram for the standard configuration M02 with
breaker status indication and control signals for opening and
closing of the circuit breaker
204
1MRS751802-MUM Protection Relay REX 521
11.3.6. Implementations
In the sections below a few implementation examples for the standard configuration
M02 are presented.
205
REX 521 Protection Relay 1MRS751802-MUM
DC
0
CB
ES
External reclosure
initialization signal Definite trip alarm
Control signal for selecting
the basic angle of Io>-->
(BACTRL) Circuit-breaker failure
protection
REX 521
A052051
Fig. 11.3.6.3.-1 Connection diagram for the standard configuration M02 with breaker status indication, control
and alarm signals.
206
1MRS751802-MUM Protection Relay REX 521
12.1.1. Features
This application example describes an incoming feeder to a single busbar with
parallel feeders including:
• Directional overcurrent protection
• Non-directional overcurrent protection
• Synchro-check and voltage-check
This application example is an optional solution for the application example 9 (see
Section 12.2. Incoming feeder, High H02), if there is a parallel generator feeder
connected to the same busbar.
The network is either compensated earthed or isolated. The directional overcurrent
protection is used because of the parallel feeders. There is no earth-fault protection
included in this application example, because residual voltage-based protection can
be located on the measurement cubicle of the busbar.
The three-phase current measurement is established with Rogowski sensors and the
residual voltage is calculated from phase-to-earth voltages which are measured by
the voltage dividers. Phase-to-phase voltage of the busbar for synchro- and voltage-
check is measured by the voltage transformer.
G
3I> 67 MCS 000
TCS
VD
3I > 50/51
CBCM 0 I
CBFP */62
3I~harm R
SYNC 25
3I P
3U U0 Q
f pf E
A052052
Fig. 12.1.1.-1 REX 521 High H01 used for protection, measuring and supervision
on an incoming feeder in a single busbar system with parallel
generator feeder. The system earthing on the supplying network is
compensated or isolated.
207
REX 521 Protection Relay 1MRS751802-MUM
2
TCS1
HSPO1
0
1
TRIP1 circuit breaker
3 4 1
Q
P
E
X4. 2
P03
R
I
000
CLOSE circuit breaker
U0
pf
17 18
P02
3I ~har m
CBCM
3I> -> TRIP2 to the
TCS
MCS
3U
3I
HV side circuit breaker
f
14 15
P01
Circuit-breaker failure
protection
9 12 13
50/ 51
* / 62
S02
25
67
OC blocking signal to the
HV-side 3I>> stage (3I>>-> START)
6 10 11
SYNC
3I >
CBFP
S01
OC blocking signal to the
3I >
3I>>> stages (3I>-> START)
3 8 7
Internal relay fault
IRF
5 4
TempAlarm
2
Mains ACFail
1X4. 1
OC blocking signal
1 2
DI9
and the bus sectionalizer
X3. 1
DI8
DI7
DI6
DI5
U12b
I ob
Io
DI4
8 9 10
Sensor VD2
Sensor VD1
Sensor RS2
Sensor RS1
Sensor VD3
Sensor RS3
DI3
VT1
CT5
CT4
DI2
5 6 7
DI1
REX 521
X4. 2
DIFF
DIFF
DIFF
DIFF
DIFF
DIFF
0. 2A
1A
5A
100V
1A
X1. 1
X2. 2
X2. 3
X2. 5
X2. 6
X2. 1
X2. 4
10
11
12
13
14
15
16
18
2
2
2
{
{
L2
L3
L1
2
A
DC
CB
A052053
208
1MRS751802-MUM Protection Relay REX 521
12.1.2. Measurements
Following measurements are supported in this application example:
• True RMS measurement of phase currents
• True RMS measurement of phase-to-earth voltages
• True RMS measurement of residual voltage (calculated value from phase-to-earth
voltages)
• Fundamental frequency active power [kW]
• Fundamental frequency reactive power [kVAr]
• Fundamental frequency displacement power factor cos (φ)
• Power factor PF including the harmonics
• Fundamental frequency active energy [kWh]
• Fundamental frequency reactive energy [kvarh]
• System frequency measurement
12.1.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
209
REX 521 Protection Relay 1MRS751802-MUM
12.1.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
210
1MRS751802-MUM Protection Relay REX 521
12.1.5. Implementations
In the sections below a few implementation examples for the standard configuration
H01 are presented.
211
REX 521 Protection Relay 1MRS751802-MUM
12.2.1. Features
This application example describes an incoming feeder to a single busbar with
parallel incoming feeders including:
• Directional overcurrent protection
• Non-directional overcurrent protection
The network is either compensated earthed or isolated. The directional overcurrent
protection is used because of the parallel incoming feeders. There is no earth-fault
protection included in this application example because residual voltage-based
protection can be located on the measurement cubicle of the busbar.
The three-phase current measurement is established with current transformers and
the residual voltage is measured with a set of voltage transformers in an open-delta
connection. Phase-to-phase voltage measurements are established with voltage
transformers.
TCS
3I > 50/51
CBCM 0 I
CBFP */62
3I~harm R
3U~harm
3I P
3U U0 Q
f pf E
A052054
212
1MRS751802-MUM Protection Relay REX 521
2
TCS1
HSPO1
0
1
TRIP1 circuit breaker
34 1
X4.2
P03
Q
P
E
CLOSE circuit breaker
17 18
R
000
P02
3I> -> TRIP2 to the
pf
0
U0
HV side circuit breaker
14 15
3I~harm
3U~harm
P01
CBCM
TCS
MCS
Circuit-breaker failure
3U
3I
f
protection
9 12 13
S02
OC blocking signal to the
HV-side 3I>> stage (3I> START)
50/51
6 10 11
*/62
67
S01
OC blocking signal to the
3I>> stages (3I>-> START)
3I >
CBFP
3 87
3I>
Internal relay fault
IRF
54
TempAlarm
2
Mains ACFail
1X4.1
OC blocking signal
1 2
DI9
and the bus sectionalizer
X3.1
DI8
DI7
DI6
DI5
Iob
U23
U12
U31
IL2
IL1
IL3
Io
Uo
DI4
8 9 10
DI3
CT3
VT1
CT5
CT2
VT3
VT2
CT4
CT1
VT4
DI2
5 6 7
DI1
REX 521
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
X1.1
10
11
12
13
14
15
16
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
L2
L3
L1
N
A
S1
S2
P1
P2
DC
CB
A052055
213
REX 521 Protection Relay 1MRS751802-MUM
12.2.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
214
1MRS751802-MUM Protection Relay REX 521
Start time of the relay + Input delay on the relay + Retardation time + Margin
(40 ms) to be blocked (30 ms) (20 ms)
(10 ms)
The set operate time of a back-up protection stage 3I> of the incoming feeder can be
calculated as follows:
12.2.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
215
REX 521 Protection Relay 1MRS751802-MUM
12.2.5. Implementations
In the sections below a few implementation examples for the standard configuration
H02 are presented.
12.2.5.1. Blocking signal received from the outgoing feeder and the bus
sectionalizer
The start signals from the overcurrent protection of the outgoing feeder and bus
sectionalizer can be connected in order to block the overcurrent protection stage on
the incoming feeder. There are two input blocking signals, Blocking 1 and Blocking
2, which can have different functions depending on the different protections. See
Fig. 12.2.5.1.-1.
On the overcurrent stages 3I>-->, 3I> and 3I>>, the Blocking 1 input signal is
connected to the BS1 input and the Blocking 2 input signal is connected to the BS2
input of the function. In this application example, the BS1 will stop the DT or IDTM
timer and the BS2 will block the trip signal. Refer to the CD-ROM Technical
Descriptions of Functions (see Section 1.3. Related documents) for more
information about the different protection function blocks.
In this application example the digital input DI9 is connected to the input signal
Blocking 1 and then routed to the BS1 input of the overcurrent stage 3I>>. The
Blocking 1 signal can be found in Main menu\Configuration\Input
Signals\Blocking 1\ with DI9 is selected. The checksum for the SWGRP in
Main menu\Configuration\Input SWGRP\Blocking 1\ should be 8
to the block 3I>>.
216
1MRS751802-MUM Protection Relay REX 521
BS BS
3I>> 3I>>
3I>>> 3I>>>
TRIP
TRIP
START 3I>
START 3I>
REX 521 REX 521
Trip 2
3I> 3I>
Trip 2
Incoming feeder 3I> 3I> Incoming feeder
(H02) (H02)
START 3 I>->
START 3 I>->
BS 3I>> BS 3I>>
Trip 1
Trip 1
REX 521 REX 521
START 3I>>
START 3I>>
3I> 3I>
START 3I>>
3I>
TRIP
3I>>
BS
TRIP
Outgoing feeder (H04) 3I>>>
Outgoing feeder (H04)
Bus sectionalizer (H03)
A052056
217
REX 521 Protection Relay 1MRS751802-MUM
218
1MRS751802-MUM Protection Relay REX 521
12.3.1. Features
This application example describes a bus sectionalizer of a single busbar including:
• Overcurrent protection
• Synchro-check and
• Voltage-check function
The network can be compensated, isolated, resistance or solidly earthed. Three-
phase current measurement is established with a set of current transformers. Phase-
to-phase voltage measurements are established with voltage transformers in both
sections of the busbar.
The High H03 variant of REX 521 is selected to be used in this application because
of the synchro-check and voltage-check functionality. This selection makes it
possible to extend the automatic supervision functionality in the substation. The
synchro-check function does not allow closing of the bus sectionalizer if the
operation criteria are not fulfilled.
TCS
CBFP */62
CBCM 0 I
3I > 68
2f 3I~harm R
SYNC 25 3U~harm
3I
3U
Fig. 12.3.1.-1 H03 is used for protection, measuring and supervision on a bus
sectionalizer in a single busbar system. The supplying network can
be compensated, isolated, solidly or resistance earthed.
219
REX 521 Protection Relay 1MRS751802-MUM
2
TCS1
0
HSPO1
TRIP circuit breaker
3 4 1
X4.2
P03
CLOSE circuit breaker
17 18
E
P02
R
000
Blocking signal to incoming
pf
0
14 15
feeder (START 3I>>)
P01
3U~harm
3I~harm
CBCM
MCS
TCS
3U
Circuit-breaker failure
3I
9 12 13
protection
S02
Definite trip alarm
6 10 11
50/51
25
68
*/62
S01
CBFP
SYNC
3I 2f>
3 8 7
3I>
Internal relay fault
IRF
5 4
TempAlarm
2
Mains ACFail
1 X4.1
Blocking signal
2
feeders
X3.1
11 12 13 14 15 16 17 18
L2
L3
L1
DI8
DI7
DI6
DI5
U12b
U23
U12
Iob
Uo
IL2
IL1
IL3
Io
DI4
N
A
8 9 10
DI3
DI2
CT3
VT1
VT3
VT2
CT5
CT2
CT4
CT1
VT4
7
5 6
REX 521
DI1
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
10
12
13
X1.1
14
15
16
11
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
P1 S1
S2
P2
DC
CB
N
A
L2
L3
L1
A052058
220
1MRS751802-MUM Protection Relay REX 521
12.3.2. Measurements
Following measurements are supported in this application example:
• True RMS measurement of phase currents
• True RMS measurement of phase-to-phase voltages
• System frequency measurement
12.3.3. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
Start time of the relay + Input delay on the relay + Retardation time + Margin
(40 ms) to be blocked (30 ms) (20 ms)
(10 ms)
The set operate time of a back-up protection stage 3I> of the bus sectionalizer can
be calculated as follows:
221
REX 521 Protection Relay 1MRS751802-MUM
222
1MRS751802-MUM Protection Relay REX 521
Before the function block allows the closing of the CB, it ensures that the phase
difference remains within the setting range until the CB closes.
The command mode is used as a basic control principle of the synchro-check
function. In command mode, the synchro-check function directly uses the output
signal to close the circuit breaker. The close command for example from the HMI is
connected to the synchro-check function. When the close command is activated, the
synchro-check function checks the closing criteria and if they are fulfilled, it will
route the command to the output relay of the protection relay. In this application
example the close signal is connected to the power output PO3.
The command mode principle means that the interlocking logic related to the control
functionality will affect the synchro-check function as well. If blocking is needed it
can be carried out by using the ready-made interlocking logic, for example in a case
where the phase-to-phase voltage is missing from either side of the circuit breaker
because of the open miniature circuit breaker (MCB) of the measurement circuit.
12.3.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
223
REX 521 Protection Relay 1MRS751802-MUM
12.4.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Autoreclose function
• Overcurrent protection
• Directional and non-directional earth-fault protection
• Phase discontinuity protection
• Thermal overload protection for cable or line
This application example is an optional solution for the seventh application example
(chapter 10.3), if extended earth-fault protection against a cross-country fault is
required or wider range of measurements is needed.
The network is either compensated or isolated. Three-phase current measurement is
established with a set of current transformers. The neutral current I0b is measured
with a cable current transformer and the neutral current I0 is measured with the sum
connection of the phase current transformers. The residual voltage is measured with
a set of voltage transformers in an open-delta connection. Phase-to-phase voltage
measurements are established with voltage transformers.
I 0> TCS
50N/51N
CBCM 0 I
I 0> 67N
3I~harm R
I> 46
3U~harm
3 49F
3I I0 P
0 I 79
CBFP */62 3U U0 Q
f pf E
Fig. 12.4.1.-1 REX 521 H04 used for protection, measuring and supervision on
an outgoing feeder in a single busbar system. The supplying
network is either compensated or isolated.
224
1MRS751802-MUM Protection Relay REX 521
2
TCS1
HSPO1
0
1
TRIP circuit breaker
3 4 1
X4.2
P03
CLOSE circuit breaker
17 18
Q
P
E
P02
R
Blocking signal to incoming
000
14 15
I0
feeder (START 3I>>)
U0
pf
0
P01
3U~harm
3I~harm
Circuit-breaker failure
CBCM
9 12 13
MCS
TCS
3U
f
protection
3I
S02
Definite trip alarm
6 10 11
50N/51N
50/51
49F
67N
S01
46
79
*/62
I
CBFP
3 8 7
I>
I 0>
3I >
3
I 0>
0
Internal relay fault
IRF
5 4
TempAlarm
2
Mains ACFail
1
2 X4.1
DI9
1
DI8
(BACTRL)
External reclosure
DI7
initialization signal
DI6
DI5
U23
U12
U31
Iob
Uo
IL2
IL1
IL3
Io
DI4
8 9 10
DI3
CT3
VT1
CT5
CT2
VT3
VT2
CT4
CT1
VT4
DI2
7
5 6
DI1
REX 521
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
10
12
13
X1.1
14
15
11
16
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
L2
L3
L1
N
A
S1
S2
S2
S1
P1
P2
DC
CB
ES
A052060
225
REX 521 Protection Relay 1MRS751802-MUM
12.4.2. Measurements
Following measurements are supported in this application example:
• True RMS measurement of phase currents
• True RMS measurement of neutral current
• True RMS measurement of phase-to-phase voltages
• True RMS measurement of residual voltage
• Fundamental frequency active power [kW]
• Fundamental frequency reactive power [kVAr]
• Fundamental frequency displacement power factor cos (φ)
• Power factor PF including harmonics
• Fundamental frequency active energy [kWh]
• Fundamental frequency reactive energy [kvarh]
• System frequency measurement
12.4.4. Protection
All the necessary settings for the protection functions can be set via the Relay
Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
The overcurrent, the phase discontinuity and thermal overload protection can be
implemented in the same way as in the first application example Section 10.1.
Outgoing feeder, Basic B01, and the directional earth-fault protection as in the fifth
application example Section 11.1. Outgoing feeder, Medium M01.
226
1MRS751802-MUM Protection Relay REX 521
EF in phase L2
EF in phase L3
A052061
12.4.5. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
12.4.6. Implementations
The implementations for the seventh application example (see Section 11.3.
Outgoing feeder, Medium M02) are also applicable for this application example.
227
REX 521 Protection Relay 1MRS751802-MUM
12.5.1. Features
This application example describes an incoming feeder to a single busbar including:
• Overcurrent protection
• Non-directional earth-fault protection
• Overvoltage protection
• Undervoltage protection
This application example is an optional solution for the second application example
(Section 10.2. Incoming feeder, Basic B01), if overvoltage and undervoltage
protection is required or wider range of measurements is needed.
The network is resistance or solidly earthed. The three-phase current measurement
is established with current transformers. The neutral current is measured via a
current transformer located in the neutral earthing circuit on the LV side of the
power transformer. Phase-to-phase voltage measurements are established with
voltage transformers.
I 0> TCS
50N/51N
CBCM 0 I
3U> 59
3I~harm R
3U< 27
3U~harm
CBFP */62
3I I0 P
3U Q
f pf E
A052062
Fig. 12.5.1.-1 H05 and H50 are used for protection, measuring and supervision
on an incoming feeder in a single busbar system. The supplying
network is either solidly or resistance earthed
228
1MRS751802-MUM Protection Relay REX 521
2
TCS1
HSPO1
TRIP circuit breaker
3 4 1
X4.2
P03
Q
P
E
CLOSE circuit breaker
R
17 18
000
P02
I0
0
pf
Io>>> TRIP to breaker on
14 15
3U~harm
3I~harm
HV side of transformer
CBCM
MCS
TCS
P01
3U
3I
f
Circuit-breaker failure
9 12 13
protection
S02
OC blocking signal to
50N/51N
the HV relay (3I>> START)
50/51
27
6 10 11
59
*/62
S01
CBFP
3U<
3U>
I 0>
3I >
3 8 7
Internal relay fault
IRF
5 4
TempAlarm
2
Mains ACFail
1 X4.1
OC blocking signal
2
DI9
1
DI8
DI7
DI6
DI5
U23
U12
U31
Iob
Uo
IL2
IL1
IL3
Io
0
DI4
8 9 10
DI3
DI2
CT3
VT1
VT3
VT2
CT5
CT2
CT4
CT1
VT4
7
5 6
REX 521
DI1
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
10
12
13
X1.1
14
15
16
11
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
L2
L3
L1
S2
S1
A
S1
S2
P1
P2
DC
CB
A052063
229
REX 521 Protection Relay 1MRS751802-MUM
12.5.2. Measurements
Following measurements are supported in this application example.
• True RMS measurement of phase currents
• True RMS measurement of neutral current
• True RMS measurement of phase-to-phase voltages
• Fundamental frequency active power [kW]
• Fundamental frequency reactive power [kVAr]
• Fundamental frequency displacement power factor cos (φ)
• Power factor PF including harmonics
• Fundamental frequency active energy [kWh]
• Fundamental frequency reactive energy [kvarh]
• System frequency measurement
12.5.3. Protection
All the necessary settings for the protection functions can be set by means of the
Relay Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
230
1MRS751802-MUM Protection Relay REX 521
85% 115%
t(s)
70% 130% DT operation
100 60 s
60 s
IDMT operation
10
3s
1
0.1 s
70 80 90 100 110 120 130
U/Un(%)
UNDERVOLTAGE
U< = 0.85 x Un, t> = 60 s, DT
U<< = 0.7 x Un, t> = 3 s, DT
OVERVOLTAGE
U> = 1.15 x Un, t> = 60 s, DT
or U> = 1.09 x Un, k = 0.2, p = 2, IDMT
12.5.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
231
REX 521 Protection Relay 1MRS751802-MUM
12.5.5. Implementations
In the sections below a few implementation examples for the standard
configurations H05 and H50 are presented.
12.5.5.3. Earth-fault stage Io>>> to trip the breaker on the HV side of the
transformer
The earth-fault stage Io>>> to trip the breaker on the HV side of the transformer can
be implemented as described in the second application example (Section 10.2.
Incoming feeder, Basic B01). The earth-fault stage Io>>> is not found in H50.
232
1MRS751802-MUM Protection Relay REX 521
233
REX 521 Protection Relay 1MRS751802-MUM
12.6.1. Features
This application example describes a measurement cubicle in a single busbar system
including:
• Overvoltage protection
• Undervoltage protection
• Residual voltage protection
• Underfrequency protection with two stages
The network is either compensated or isolated. The residual voltage is measured
with a set of voltage transformers in an open-delta connection. Phase-to-phase
voltage measurements are established with voltage transformers.
3U> TCS
59
3U~harm 0 I
3U< 27
R
f< 81U
3U U0
A052065
234
1MRS751802-MUM Protection Relay REX 521
2
TCS1
HSPO1
TRIP1 to the incoming feeder
3 4 1
Uo>>>,Uo>>
X4.2
P03
R
000
TRIP3 to all outgoing feeders
17 18
U0
0
Uo>>>,Uo>>, U<, U<<, U>, U>> and f<<
P02
3U~harm
MCS
TCS
TRIP2 to the load shedding group 1f<
14 15
3U
f
P01
9 12 13
59N
81U
59
27
S02
6 10 11
f<
U 0>
3U<
3U>
S01
Earth-fault alarm Uo>
3 8 7
IRF
5 4
TempAlarm
2
Mains ACFail
1
2 X4.1
DI9
1 X3.1
11 12 13 14 15 16 17 18
DI8
DI7
DI6
DI5
U23
U12
U31
Iob
Uo
IL2
IL1
IL3
Io
DI4
8 9 10
DI3
DI2
CT3
VT1
VT3
VT2
CT5
CT2
CT4
CT1
VT4
7
5 6
REX 521
DI1
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
10
12
13
X1.1
14
15
16
11
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
L2
L3
L1
ES
DC
N
A
A052066
235
REX 521 Protection Relay 1MRS751802-MUM
12.6.2. Measurements
Following measurements are supported in this application example:
• True RMS measurement of phase-to-phase voltages
• True RMS measurement of residual voltage
• System frequency measurement
12.6.3. Protection
All the necessary settings for the protection functions can be set by means of the
Relay Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
236
1MRS751802-MUM Protection Relay REX 521
85% 115%
t(s)
70% 130% DT operation
100 60 s
60 s
IDMT operation
10
3s
1
0.1 s
70 80 90 100 110 120 130
U/Un(%)
UNDERVOLTAGE
U< = 0.85 x Un, t> = 60 s, DT
U<< = 0.7 x Un, t> = 3 s, DT
OVERVOLTAGE
U> = 1.15 x Un, t> = 60 s, DT
or U> = 1.09 x Un, k = 0.2, p = 2, IDMT
12.6.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
237
REX 521 Protection Relay 1MRS751802-MUM
The trip signal (Trip 2) of the underfrequency stage f< protection function is routed
to the power output PO2 (x4.2.14/15).
The trip signals (Trip 3) of the residual voltage stages Uo>>> and Uo>>,
undervoltage, overvoltage and underfrequency stage f<< protection function are
routed to the power output PO3 (x4.2.17/18).
The trip signals from the protection functions are routed to the output relay via the
output switchgroups. These settings can be found in
Main menu\Configuration\Output SWGRP\.
As the HSPO1 is always named as the “Trip 1" output signal, the settings are made
directly in Main menu\Configuration\Output SWGRP\Trip 1 where
the checksum of the settings is displayed (255 by default).
The Trip 2 has to be set to PO2 and the Trip 3 to PO3 in
Main menu\Configuration\Output Signals\. The trip signals from the
protection functions can be set to the correct trip group in
Main menu\Configuration\Output SWGRP\Trip 2…3 where the
checksum of the settings is displayed (255 by default).
Using the HMI:
To change the settings for Trip 1 go to Output SWGRP\Trip 1 and press the
[E]-button. The different protection functions are displayed one at a time. By
pressing the [→] or [←] navigation push button, it is possible to scroll between the
different protections. By pressing the [↑] or [↓] navigation push button, the specific
protection function trip signal can be connected or disconnected.
To change the settings for PO2 and PO3 go to Output Signals\PO2…PO3 and
press the [E]-button. The different signals (Trip 2, Trip 3, CBFP, etc.) are displayed
one at a time. By pressing the [→] or [←] navigation push button, it is possible to
scroll between the different signals. By pressing the [↑] or [↓] navigation push
button, the specific signal can be selected. Select the Trip 2 for the PO2 and Trip 3
for the PO3.
To define settings for Trip 2 and Trip 3 the same principle as shown above for the
Trip1 can be used.
When the residual voltage stages Uo>>> and Uo>> are selected the checksum for
Trip 1 is 384.
When the underfrequency protection stage f< is selected for the load shedding group
1, the checksum for Trip 2 is 512.
When the residual voltage stages Uo>>> and Uo>>, two-stage overvoltage (U> and
U>>), two-stage undervoltage (U< and U<<) and underfrequency protection stage
f<< are selected the checksum for Trip 3 is 2492.
238
1MRS751802-MUM Protection Relay REX 521
The settings are made by means of the Relay Setting Tool or the local HMI. The
settings can be found in:
Main menu\Configuration\Input Signals\
Main menu\Configuration\Input SWGRP\
Main menu\Configuration\Output Signals\
Main menu\Configuration\Output SWGRP\.
12.6.5. Implementations
In the sections below a few implementation examples for the standard configuration
H06 are presented.
239
REX 521 Protection Relay 1MRS751802-MUM
240
1MRS751802-MUM Protection Relay REX 521
12.7.1. Features
This application example describes a single busbar motor feeder including:
• Non-directional overcurrent protection
• Negative phase sequence (NPS) protection
• Motor start-up supervision
• Thermal protection for motors
• Non-directional undercurrent protection (only in H07)
• Phase reversal protection
• Fuse fail protection
Three-phase current measurement is established with current transformers, and
residual voltage is measured with a set of voltage transformers in an open-delta
connection. Phase-to-phase voltage measurements are established with voltage
transformers.
CBCM 0 I
3U< 27
3I~harm R
Is2t,n< 48,14,66
3I 3U~harm
3I 46R
I2> 46 3I I0 P
3I< 37
3U U0 Q
F
60
3 49
f pf E
CBFP */62
M
A052067
Fig. 12.7.1.-1 H07 and H51 are used for protection, measuring, and supervision
of a single busbar motor feeder
241
L1
242
L2
L3
A
N
REX 521
0
0
CB
1
DC 1
ES
protection
Prior alarm
Speed Switch
RESTART enable
Circuit-breaker failure
CLOSE circuit breaker
P1 S1
Protection Relay
S2
P2
X4.2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 X3.1 1 2 X4.1 1 2 5 4 3 8 7 6 10 11 9 12 13 14 15 17 18 X4.2 3 4 1 2
Mains
S1 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9
IRF S01 S02 P01 P02 P03 HSPO1
Technical Reference Manual, Standard
S2 X1.1
ACFail
25
24 TCS
TCS1
100V
VT3 U23
I 0> 50N/51N
22
21 CBCM 0 I
100V
VT2 U12 3U< 27
Fig. 12.7.1.-2 Connection overview diagram of the single busbar motor feeder
19
3I~harm R
18 VT1 Is2t,n< 48,14,66
100V Uo
16
15 0.2A 3I 3U~harm
14 1A CT5 Iob 46R
13 3I
12 1A
11 5A CT4 P
Io I2> 46 3I I0
10
9 1A
8 5A CT3 IL3 3I< 37
7
6 1A 3U Q
U0
5 5A
CT2 IL2 F
60
4
M 3
2
1A
5A CT1 IL1 3 49
1 f pf E
A052068
1MRS751802-MUM Protection Relay REX 521
12.7.2. Measurements
The following measurements are supported in this application example:
• True RMS measurement of phase currents
• True RMS measurement of phase-to-phase voltages
• True RMS measurement of neutral current
• True RMS measurement of residual voltage
• Fundamental frequency active power [kW]
• Fundamental frequency reactive power [kVAr]
• Fundamental frequency displacement power factor cos (φ)
• Power factor PF including the harmonics
• Fundamental frequency active energy [kWh]
• Fundamental frequency reactive energy [kvarh]
• System frequency measurement
12.7.3. Protection
All the necessary settings for the protection functions can be set via Relay Setting
Tool or the local HMI. The settings can be found in Main menu\Protection\.
243
REX 521 Protection Relay 1MRS751802-MUM
244
1MRS751802-MUM Protection Relay REX 521
8h
Dts
[s]
50
Start 3
40
20
Start 1
10
t
A052069
For readability reasons the time scaling in the diagram is not the
same for start-up versus cooling-down sequences.
245
REX 521 Protection Relay 1MRS751802-MUM
175
K 2 = --------------2-
( I LR )
where
ILR = locked-rotor current (times the Full Load Current of the motor
246
1MRS751802-MUM Protection Relay REX 521
Example:
Motor start-up current is 5.2 x FLC and thereby the estimated K-setting is
175/(5.2)2 = 6.5%.
The most severe unbalance is caused by an broken phase. It should be checked that
in case of broken (open) phase the operation time of the unbalance protection is
shorter than the permissible locked-rotor jam time.
247
REX 521 Protection Relay 1MRS751802-MUM
12.7.5. Connections
All the necessary settings for the connections and signal routings can be set by using
Relay Setting Tool or a local HMI.
248
1MRS751802-MUM Protection Relay REX 521
249
REX 521 Protection Relay 1MRS751802-MUM
12.8.1. Features
This application example describes an incoming feeder to a single busbar including:
• Overcurrent protection
• Non-directional earth-fault protection
• Overvoltage protection
• Undervoltage protection
This application example is an optional solution for the second application example
(Section 10.2. Incoming feeder, Basic B01), if overvoltage and undervoltage
protection is required or wider range of measurements is needed.
The network is resistance or solidly earthed. The three-phase current measurement
is established with current transformers. The neutral current is measured via a
current transformer located in the neutral earthing circuit on the LV side of the
power transformer. Phase-to-earth voltage measurements are established with
voltage transformers.
I 0> TCS
50N/51N
CBCM 0 I
3U> 59
3I~harm R
3U< 27
3U~harm
CBFP */62
3I I0 P
3U 3U_B Q
f pf E
A052070
250
1MRS751802-MUM Protection Relay REX 521
2
TCS1
H SPO1
TRIP circuit breaker
3 4 1
X4.2
P03
Q
P
E
CLOSE circuit breaker
R
17 18
000
3U_B
P02
I0
0
pf
Io>>> TRIP to breaker on
14 15
3U~harm
3I~harm
HV side of transformer
CBCM
MCS
TCS
P01
3U
3I
f
Circuit-breaker failure
9 12 13
protection
S02
OC blocking signal to
50N/51N
the HV relay (3I>> START)
50/51
27
6 10 11
59
*/62
S01
CBFP
3U<
3U>
I 0>
3I >
3 8 7
Internal relay fault
IRF
5 4
TempAlarm
2
Mains ACFail
1 X4.1
OC blocking signal
2
DI9
1
DI8
DI7
DI6
DI5
Iob
Uo
U2
U1
IL2
IL1
U3
IL3
Io
0
DI4
8 9 10
DI3
DI2
CT3
VT1
VT3
VT2
CT5
CT2
CT4
CT1
VT4
7
5 6
REX 521
DI1
X4.2
0.2A
100V
100V
100V
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
10
12
13
X1.1
14
15
16
11
18
19
21
22
25
24
27
7
8
9
4
5
6
1
2
3
L2
L3
L1
S2
S1
A
S1
S2
P1
P2
DC
CB
A052071
251
REX 521 Protection Relay 1MRS751802-MUM
12.8.2. Measurements
The following measurements are supported in this application example.
• True RMS measurement of phase currents
• True RMS measurement of neutral current
• True RMS measurement of phase-to-earth voltages
• True RMS measurement of calculated phase-to-phase voltages
• Fundamental frequency active power [kW]
• Fundamental frequency reactive power [kVAr]
• Fundamental frequency displacement power factor cos (φ)
• Power factor PF including harmonics
• Fundamental frequency active energy [kWh]
• Fundamental frequency reactive energy [kvarh]
• System frequency measurement
12.8.3. Protection
All the necessary settings for the protection functions can be set by means of the
Relay Setting Tool or the local HMI. The settings can be found in
Main menu\Protection\.
252
1MRS751802-MUM Protection Relay REX 521
85% 115%
t(s)
70% 130% DT operation
100 60 s
60 s
IDMT operation
10
3s
1
0.1 s
70 80 90 100 110 120 130
U/Un(%)
UNDERVOLTAGE
U< = 0.85 x Un, t> = 60 s, DT
U<< = 0.7 x Un, t> = 3 s, DT
OVERVOLTAGE
U> = 1.15 x Un, t> = 60 s, DT
or U> = 1.09 x Un, k = 0.2, p = 2, IDMT
12.8.4. Connections
All the necessary settings for the connections and signal routings can be set via the
Relay Setting Tool or the local HMI.
253
REX 521 Protection Relay 1MRS751802-MUM
12.8.5. Implementations
In the sections below a few implementation examples for the standard
configurations H08 and H09 are presented.
12.8.5.3. Earth-fault stage Io>>> to trip the breaker on the HV side of the
transformer
The earth-fault stage Io>>> to trip the breaker on the HV side of the transformer can
be implemented as described in the second application example (Section 10.2.
Incoming feeder, Basic B01)
254
1MRS751802-MUM Protection Relay REX 521
255
256
1MRS751802-MUM Protection Relay REX 521
3I > 50/51 = multiple-stage three-phase overcurrent protection, low-set, high-set and instantaneous
stage available
I0> 50N/51N = multiple-stage earth-fault protection, low-set, high-set and instantaneous stage
available
I0> 67N = multiple-stage directional earth-fault protection, low-set, high-set and instantaneous
stage available
U0> 59N = multiple-stage residual overvoltage protection, low-set, high-set and instantaneous
stage available
3I2f > 68 = inrush detection based on the 2nd harmonic content of phase currents, applied for
preventing possible unnecessary operation of overcurrent or earth-fault protection
during transformer switching-in or to start cold load pick-up logic
DI> 46 = phase discontinuity protection
0 I 79 = multiple-shot auto-recloser
257
REX 521 Protection Relay 1MRS751802-MUM
= disturbance recorder
A052073
258
1MRS751802-MUM Protection Relay REX 521
14. Abbreviations
AR Auroreclose
ASCII American Standard Code for Information Interchange
CB Cicuit breaker
CBFP Circuit creaker failure protection function
CRC Cyclic redundancy check
CT Current transformer
DC Disconnector
DI Digital input
ES Earth switch
HMI Human-machine interface
HSPO High-speed power output
IDMT Inverse definite minimum time
IRF Internal relay fault
LCD Liquid crystal display
LED Light-emitting diode
MCB Miniature circuit breaker
MMI Man-machine interface
NC Normally closed
NO Normally open
NPS Negative phase sequence
PO Power output
RS Rogowski sensor
RTC Real-time clock
RTU Remote terminal unit
SA Substation automation
SO Signalling output
TCS Trip-circuit supervision
VD Voltage divider
VT Voltage transformer
259
1MRS751802-MUM EN 09.2006
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa
FINLAND
Tel. +358 10 22 11
Fax. +358 10 224 1094
www.abb.com/substationautomation