Professional Documents
Culture Documents
ABSTRACT The on-load tap changer (OLTC) switching arc will affect the life of the contact, so it
is necessary to test its working condition. Based on DQ coordinate transformation, fundamental wave
component extraction, and wavelet algorithm, proposed an OLTC arc detection method based on energy
conservation theory in this paper. Used the fundamental wave component extraction algorithm extracted the
transformer excitation parameters, and established the OLTC equivalent circuit by combining the Habedank
arc model. Compared the differences between the follow effect and frequency calculation of simulated
and measured waveforms, which were caused by the five orthogonal transformation algorithms, including
Transport-Delay, Hilbert Transformation, Inverse Park Transformation, SOGI and Improved SOGI. The DQ
coordinate transformation based on the Transport-Delay orthogonal converter is determined to calculate the
active power of each part of the circuit. According to the principle of energy conservation, obtained the data
of arcing loss under nine simulated conditions. Based on the simulation circuit, built the OLTC prototype
and dSPACE hardware in loop simulation platform, and measured three load conditions. The sampling signal
was filtered by the wavelet algorithm. Considering the measurement and calculation errors, the simulation
and measured results show that the actual arcing power has a consistent change with the calculated value
between different working conditions, and the maximum difference between simulation results and measured
results is thirty times and ten times. It can distinguish the difference of arcing energy of diverter switch under
different working conditions and has the measurability. Meanwhile, it verifies the effectiveness of this study,
hoping to provide a theoretical basis for developing OLTC on-line contact detection system.
INDEX TERMS On-load tap changer, arcing power, condition monitoring, orthogonal transformation, DQ
coordinate transformation.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see http://creativecommons.org/licenses/by/4.0/
VOLUME 7, 2019 180793
D. Song et al.: Research on the Switching Arc Loss of OLTC
uα = Um Hα (t)
Um
q
= Um sin ωt − p sin(ω 1−(k/2)2 t)e−kωt/2
1−(k/2)2
(20)
uβ = Um Hβ (t)
Um
= −Um cos ωt − p
1−(k/2)2 FIGURE 10. Calculation results of system voltage and frequency by each
q algorithm.
× cos(ω 1−(k/2)2 t −ϕ)e−kωt/2 (21)
k/2
where, ϕ = arctan( √ ). The value of bandwidth dynamic adjustment performance. Other algorithms show the
1−(k/2)2
coefficient k affects the response speed of the system, and obvious transition process for the current mutation informa-
the empirical value of 1.5 could be taken. tion at each switching point, and the Inverse Park Transforma-
(5) Improved SOGI. After the difference between the origi- tion is the most serious one. Only the Transport-Delay could
nal signal and the output α phase of SOGI algorithm, the har- lock the signal amplitude of each switching interval, and all
monic component in the original signal is obtained, which other algorithms have overshoot.
is removed by filtering to get the dc offset, and then it is The Fig. 10 shows the frequency calculation results of the
subtracted from the β phase parameters to realize the filtering simulation and measured of each algorithm, respectively. The
effect on the β phase parameters. The structure is shown fundamental frequency is 50Hz, and the measured waveform
in Fig.7b. The filter design can refer to the filter parameters contains certain harmonic components.
in the Inverse Park Transform algorithm. The relative errors between the d-axis component and
The αβ parameters obtained by the above method can real- the actual amplitude of the original signal obtained by the
ize Park transformation in combination with phase-locked θ, Transport-Delay, Hilbert Transformation and the Inverse Park
and the phase-locked loop can adopt PI adjustment algorithm, Transformation were calculated, which are 4.40%, 4.76% and
with the structure shown in the Fig.8. Phase lock angle is 4.71% respectively. Numerically, the three algorithms had
captured by PI adjustment, in the case that axis d is ahead similar computing errors. In this study, the fundamental com-
of the coordinate system of axis q, θ is the phase lock angle, ponent was extracted before DQ transformation to eliminate
and when the phase lock is complete, ωt = θ, or uq = 0. uq is the pulsation component of d-axis component. Therefore, the
connected to the PI regulator, and the change in uq will lead Transport-Delay with relatively good amplitude following
to the same change in ω, and then the same change in θ after effect was selected for the follow-up study.
integration,
The above five orthogonal converter algorithms were sim- B. FUNDAMENTAL WAVE COMPONENT EXTRACTION
ulated and analyzed. According to Fig.3a, established OLTC When there was (inter) harmonic in the original sam-
simulation model and experimental circuit, and obtain the pling signal, d and q axis components will contain pul-
system current signal and corresponding dc component. The sating components, generating deviations in the calculation
simulation and measurement data were shown in the Fig.9. and requiring filtering processing, used Fourier algorithm,
Each switching point can be identified by the algorithm, Kalman filtering algorithm and adaptive filtering, etc. The
which is consistent with Fig. 3b. Space lest mean square algorithm was used to extract (inter)
All the algorithms could follow the amplitude of the sam- harmonic parameters, and compared with Prony, DFT, win-
pling signal with good effect. The d-axis component obtained dowed DFT and other algorithms, [12]. The waveforms of
by the Transport-Delay and Hilbert Transformation has good arc furnace and frequency converter were analyzed by Prony
B. SIMULATED ANALYSIS
Simulation results of each working condition are drawn in
which is expressed by the product of the voltage at the switch Fig.16. There is the actual and calculated arcing energy of
end and the conduction current. See Fig.13. the switch at K1 and K2 respectively.
At the breaking point of K1 , the waveform of PdeltRarc and Due to the larger switching current and change gradient of
Pk1arc rises at the same time, and the process coincides. The K1 , the transient transition process of DQ transformation is
calculated power difference at K2 breaking point is consistent more serious than that of K2 , and the calculation deviation
with the actual arcing power. The values of arcing power and increases. According to the data, the position deviation of
energy in the two places are shown in Table 2. Arcing energy K1 is related to the nature of the load. Under inductive load,
is the integral value of arcing power in the arcing interval. the calculated value of arcing power is close to the actual
(2) RC load. Based on the d-axis components of each value. The reason is that the actual arcing power is large due
parameter, the power difference calculated at the position K1 , to the inductive load, which accounts for the main component
K2 and the actual arcing power curve are obtained, as shown in PdeltRarc .
in Fig.14. Fig.17 and 18 respectively show the curves of PdeltRarc ,
Similar to the results in the upper working condition, Pk1arc and Pk2arc with different loads under the other two arc
the calculated arcing power at the K1 breaking point is large, parameters.
and the calculated value at the K2 breaking point is close to Three kinds of arc parameters determine the difference of
the actual value. The power data is shown in Table 3. arcing energy, as the load current is small, the actual arcing
(3) RL load. The curve of calculated and actual arcing power at K1 and K2 breaking points under RC load is small,
power of K1 and K2 underRL load is shown in Fig.15. and the actual arcing power under RL load is larger. Under
FIGURE 17. Comparison waveform of arcing power difference and actual FIGURE 20. D-axis test waveform of voltage and current in the
arcing power (condition 1). transformer system.
FIGURE 18. Comparison waveform of arcing power difference and actual FIGURE 21. Test waveform of system power difference.
arcing power (condition 3).
VII. CONCLUSION
To realize the measurement of OLTC switching arc param-
eters, based on DQ coordinate transformation, fundamental
wave component extraction and wavelet algorithm, this paper
proposes an OLTC switching arc monitoring model based
on energy conservation theory, and obtains the following
K3 , which is preliminarily considered to be caused by the conclusions:
closure of K3 . To prove that the power peak at the breaking (1) The simulation model was established, and the param-
points of K1 and K2 is consistent with the arcing power at the eters of arc with different load and different arc parameters
two places of ACC, measured the actual arc parameters of the at K1 and K2 breaking points were calculated. In different
switches at two positions, and the branch current and end volt- working conditions, the calculated arcing power changes by
age data of the switches are obtained. Meanwhile, the closed the actual value. Under inductive load, the calculated value
transient process of the end of K3 is measured and compared of arcing power was close to the actual value. The maximum
in the figure. As shown in Fig.22, the waveform Pk1arc , Pk2arc , difference of calculated value between different loads was
Pk3arc and the calculated power difference waveform PdeltRarc thirty times of magnitude. Arcing power can be distinguished
of K1 ∼K3 are shown. and identified.
It can be seen from the figure that the difference between (2) According to the simulation model, a laboratory OLTC
the measured arcing power and the calculated power differ- prototype and dSPACE hardware in loop simulation plat-
ence of the energy consumption model in the three places form were built to complete the measurement and calculation
is partially consistent, but the phase and amplitude between of three kinds of load switching. There were differences
waveforms are greatly deviated due to sampling and other between the arcing power calculation and the actual value,
factors. The arcing process does exist at the closure of K3 , but the variation trend of different working conditions was
confirming the previous hypothesis. The power data is shown consistent and the calculated value of differrent loads varied
in Table 5. by a maximum of ten times, which could be distinguished.
(3) The integration of measured sampling step and filtering
B. CONTRASTIVE ANALYSIS results in the difference between simulation and measured
For the convenience of analysis and comparison, the calcula- data. However, independent analysis shows that both of them
tion and actual arcing energy of K1 and K2 under three load met the measurable conclusion of arcing power, which could
conditions are drawn in Fig.23. reflect OLTC switching contact condition and transformer
system power loss indirectly, and verify the effectiveness of DONGDONG SONG received the B.Sc. and
this method. master’s degrees in electric engineering from
Hebei Agriculture University, Baoding, China,
in 2005 and 2008, respectively. He is currently
REFERENCES pursuing the Ph.D. degree with China Agricul-
[1] Z. Li, Q. Li, Z. Wu, J. Yu, and R. Zheng, ‘‘A fault diagnosis method for on ture University, Beijing, China. He is a Lecturer
load tap changer of aerospace power grid based on the current detection,’’ with the Hebei Normal University of Science and
IEEE Access, vol. 6, pp. 24148–24156, 2018. Technology, Qinhuangdao, China. His research
[2] Q. Li, T. Zhao, L. Zhang, and J. Lou, ‘‘Mechanical fault diagnostics of interests include new energy power generation,
onload tap changer within power transformers based on hidden Markov intelligent monitoring of electrical equipment, and
model,’’ IEEE Trans. Power Deli., vol. 27, no. 2, pp. 596–601, Apr. 2012. digital signal processing.
[3] R. Yang, D. Zhang, Z. Li, K. Yang, S. Mo, and L. Li, ‘‘Mechanical fault
diagnostics of power transformer on-load tap changers using dynamic time
warping,’’ IEEE Trans. Instrum. Meas., vol. 68, no. 9, pp. 3119–3127,
Sep. 2019.
[4] E. F. Simas F, L. A. L. de Almeida, and A. C. de C. Lima, ‘‘Vibration JIWEI MA received the B.Sc. and master’s degrees
monitoring of on-load tap changers using a genetic algorithm,’’ in Proc. in measuring and testing technologies and instru-
IEEE Instrum. Meas. Technol. Conf., vol. 3, May 2005, pp. 2288–2293. ments from Yanshan University, Qinhuangdao,
[5] E. Rivas, J. C. Burgos, and J. C. Garcia-Prada, ‘‘Condition assessment of China, in 1990 and 1993, respectively. She is
power OLTC by vibration analysis using wavelet transform,’’ IEEE Trans. currently an Associate Professor with the Hebei
Power Del., vol. 24, no. 2, pp. 687–694, Apr. 2009. Normal University of Science and Technology,
[6] J. Seo, M. Hui, and T. K. Saha, ‘‘On Savitzky–Golay filtering for online
Qinhuangdao. Her research interests include mea-
condition monitoring of transformer on-load tap changer,’’ IEEE Trans.
surement and controlling systems.
Power Del., vol. 33, no. 4, pp. 1689–1698, Aug. 2018.
[7] T. B. Shanker, H. N. Nagamani, and G. S. Punekar, ‘‘Acoustic emission
signal analysis of on-load tap changer (OLTC),’’ in Proc. CACON, Kolkata,
India, 2013, pp. 347–352.
[8] R. Bhuyan, A. R. Mor, P. Morshuis, and G. C. Montanari, ‘‘Analysis
of the arcing process in on-load tap changers by measuring the acoustic
YUQUAN MA received the B.Sc. degree in
signature,’’ in Proc. EIC, Philadelphia, PA, USA, 2014, pp. 193–197.
electric engineering from Xi’an Jiaotong Uni-
[9] B. Feizifar and O. Usta, ‘‘A new arc-based model and condition monitoring
algorithm for on-load tap changers,’’ Electr. Power Syst. Res., vol. 167,
versity, Xi’an, China, in 1993, and the master’s
pp. 58–70, Oct. 2019. degree in electric engineering from the Hebei
[10] M. Wang, A. J. Vandermaar, and K. D. Srivastava, ‘‘Review of condition University of Technology, Tianjin, China, in 2009.
assessment of power transformers in service,’’ IEEE Elect. Insul. Mag., He is currently an Associate Professor with the
vol. 18, no. 6, pp. 12–25, Nov./Dec. 2002. Hebei Normal University of Science and Technol-
[11] M. Duval, ‘‘A review of faults detectable by gas in oil analysis in transform- ogy, Qinhuangdao, China. His research interests
ers,’’ IEEE Elect. Insul. Mag., vol. 18, no. 3, pp. 8–17, May/Jun. 2002. include electric machinery and intelligent moni-
[12] X. Hui and Z. Peng, ‘‘Subspace-Least mean square method for accurate toring of electrical equipment.
harmonic and interharmonic measurement in power systems,’’ IEEE Trans.
Power. Del., vol. 27, no. 3, pp. 1260–1267, Jul. 2017.
[13] A. Bracale, G. Carpinelli, R. Langella, and A. Testa, ‘‘Accurate methods
for signal processing of distorted waveforms in power systems,’’ EURASIP
J. Adv. Signal Process., vol. 2007, no. 19, pp. 1–14, 2007. HONGJU LIN received the B.Sc. degree in com-
[14] K. Alireza, F. Sreffen, G. Sergey, U. Dirk, and R. F. Merhling, ‘‘Electrical puter and its application from Jilin University,
arc model based on physical parameters and power calculation,’’ IEEE Changchun, China, in 2000, the master’s degree in
Trans. Plasma Sci, vol. 43, no. 8, pp. 2721–2729, Aug. 2015. power electronics and electric drives from Xihua
[15] G. Bizjak, P. Zunko, and D. Povh, ‘‘Circuit breaker model for digital University, Chengdu, China, in 2005, and the
simulation based on Mayr’s and Cassie’s differential arc equations,’’ IEEE Ph.D. degree in instruments science and tech-
Trans. Power Del., vol. 10, no. 3, pp. 1310–1315, Jul. 1995. nology from Yanshan University, Qinhuangdao,
[16] K. Alireza, F. Steffen, G. Sergey, U. Dirk, M. Ralf, and W. Klaus-Dieter,
China, in 2018. He is currently an Associate Pro-
‘‘An improve arc model based on the arc diameter,’’ IEEE Trans. Power.
fessor with the Hebei Normal University of Sci-
Del., vol. 31, no. 3, pp. 1335–1341, Jun. 2016.
[17] U. Habedank, ‘‘Application of a new arc model for the evaluation of
ence and Technology, Qinhuangdao. His research
short-circuit breaking tests,’’ IEEE Trans. Power Del., vol. 8, no. 4, interests include network control technology and system simulation.
pp. 1921–1925, Oct. 1993.
[18] V. Kaura and V. Blasko, ‘‘Operation of a phase locked loop system
under distorted utility conditions,’’ IEEE Trans. Ind. Appl., vol. 33, no. 1,
pp. 58–63, Jan./Feb. 1997.
[19] G. Hsieh and J. C. Hung, ‘‘Phase-locked loop techniques—A survey,’’
IEEE Trans. Ind. Electron., vol. 43, no. 6, pp. 609–615, Dec. 1996. SHENGTAO LIU received the B.Sc. and mas-
[20] F. Xiao, L. Dong, L. Li, and X. Liao, ‘‘A frequency-fixed SOGI-based PLL ter’s degrees in electric engineering from Harbin
for single-phase grid-connected converters,’’ IEEE Trans. Power. Electron., Engineering University, China, in 2001 and 2004,
vol. 32, no. 3, pp. 1713–1719, Mar. 2017. respectively. He is currently a Lecturer with the
[21] Z. Leonowicz, T. Lobos, and J. Rezmer, ‘‘Advanced spectrum estimation Hebei Normal University of Science and Tech-
methods for signal analysis in power electronics,’’ IEEE Trans. Ind. Elec- nology, Qinhuangdao, China. His research interest
tron., vol. 50, no. 3, pp. 514–519, Jun. 2003. includes control systems engineering.
[22] M. Meunier and F. Brouage, ‘‘Fourier transform, wavelets, prony analysis:
Tool for harmonics and quality of power,’’ in Proc. 8th Int. Conf. Harmon.
Qual. Power, Athens, Greece, 1998, pp. 71–76.