Eaton 9PHD Industrial Technical Specifications

General
UPS output power rating 30, 40, 50, 80, 100, 120, 150, 160, 200 kW
(1.0 p.f.)
Efficiency in double Up to 97%
conversion mode
Efficiency in Energy Saver > 99%
System (ESS)
Inverter/rectifier topology Transformer-free IGBT with PWM
Audible noise 30–50 kW: < 60 dBA
80–200 kW: < 65 dBA
ESS operation: < 47 dBA
Ambient temperature 0°C to 40°C at 1000m altitude, higher temperatures are optional
Ingress protection IP23, Optional: IP33;IP54

Input
Input wiring 3 ph + N + PE or 3 ph + PE
Nominal voltage rating 380 V - 480 V, 50/60 Hz
(configurable)
With optional transformer 208 V - 690 V, 50/60 Hz
Input voltage range Rectifier input +20%, if voltage >440V then +10%,
Low -15% at 100% load, -40% at 50% load without battery discharge
Bypass input +10% to -15%
Input frequency range 40-72 Hz
Input power factor 0.99
Input ITHD 30 kW: < 4.5%
40-200 kW: < 3%
Soft start capability Yes
Internal backfeed Yes
protection

Output
Output wiring 3 ph + N + PE or 3 ph + PE
Nominal voltage rating 380 V - 480 V, 50/60 Hz
(configurable)
With optional transformer 208 V - 690 V, 50/60 Hz
Output UTHD < 1% (100% linear load); < 5% (reference non-linear load)
Rated output power factor 1.0
Permitted load power 0,8 lagging - 0,8 leading
factor
Overload on inverter 10 min 102-110%; 60 sec 111-125%; 10 sec 126-150%; 300 ms > 150%.
On battery mode 300 ms > 126%
Overload when bypass Continuous < 125%, 10 ms 1000%
available Note: Bypass fuses may limit the overload capability!

Battery
Battery type VRLA, Ni-CD
Charging method ABM technology or Float
Temperature Optional
compensation
Battery nominal voltage From 432 V (36 x 12 V, 216 cells) or
(VRLA) 480 V (40 x 12 V, 240 cells)
Note: Strings with different battery voltage may not be paralleled!
Charging current 30–50 kW: 29.3 A
maximum* 80–100 kW: 58.6 A
120–150 kW: 87.9 A
160–200 kW: 117.2 A
Battery start capability Yes

Accessories

Accessories for UPS Internal transformers; Cabinet protection IP33, IP54; Vibration dampers with mounting brackets; Seismic kit; ATS automatic transfer switch; Single feed kit;
Earth fault monitoring; 24V Emergency Power Off (EPO); Special system voltages
Accessory cabinets Industrial battery cabinets with long-life batteries; Matching transformer cabinet for one or two transformers; External maintenance bypass switch.
Communication options Web/SNMP, ModBus/Jbus, Industrial Relay

Communications
MiniSlot 4 communication bays
Network/SNMP interface Yes, standard
Serial ports Built-in host and device USB
Relay inputs/outputs 5 relay inputs and dedicated EPO
1 relay output
Compliance with standards
Safety (CB certified) IEC 62040-1
EMC IEC 62040-2
Performance IEC 62040-3
Seismic testing Meets NEBS GR-63-CORE, Zone 4 requirements with seismic withstand on up to 1g acceleration/8.3 Richter Magnitude.

* when load level ≤ 40 kW/UPM

Due to continuing product improvement programs, specifications are subject to change without notice.