Professional Documents
Culture Documents
L1 Reducing The Impact of Wind Farms On The Electric Power System by
L1 Reducing The Impact of Wind Farms On The Electric Power System by
Renewable Energy
journal homepage: www.elsevier.com/locate/renene
a r t i c l e i n f o a b s t r a c t
Article history: The deployment of wind power is rapidly growing worldwide. Intermittent, unpredictable availability of
Received 11 January 2019 wind energy destabilizes the work of the whole power system, which causes additional consumption of
Received in revised form resources. When fossil fuel power plants are affected by this phenomenon, they are forced to cycle
6 May 2019
(change their load) more often, which results in higher consumption of fuel. This negative effect,
Accepted 7 June 2019
expressed by means of thermo-ecological cost (TEC) can be significant in comparison to the TEC of
Available online 14 June 2019
construction phase of wind turbines. TEC is defined as the cumulative consumption of non-renewable
exergy connected with the fabrication of a particular product. Power plant cycling could be minimized
Keywords:
Electricity generation
by applying an energy storage system responding to variations in wind power availability. In the present
Energy storage work, several scheduling strategies for cooperation of an energy storage system with wind turbines are
Power plant cycling investigated. The effect is assessed in local and global balance boundaries. Employing energy storage
Thermo-ecological cost reduces the energy losses in thermal power plants, but at the same time, energy losses appear in the
Wind power plants storage itself. However, depending on the strategy of energy storage scheduling, in some cases the overall
consumption of primary exergy in the whole system may be lower.
© 2019 Elsevier Ltd. All rights reserved.
1. Introduction e renewable energy sources and energy stems mainly from the fact that wind energy can be harvested with
storage relatively little constraints regarding the location, when compared
with water or solar energy. Both mainland and offshore locations
Progressive depletion of reserves of fossil fuels as well as are possible. For many regions, wind energy is the only renewable
worries of the global climate change are the main incentives for source that can be utilized on a large scale comparable with con-
replacing the existing fossil fuel based energy system with ventional energy sources [3,4]. The “energy payback time” of a
renewable energy sources (RES). This finds reflection in energy wind turbine, defined as the amount of time in which the device
policies of various countries, for example in the Renewable Energy produces the amount of energy used for its fabrication, is only a few
Directive of the European Union. It obliges the EU to reach the level months [4,5]. While wind farms do not directly pollute the envi-
of 20% of renewable energy in the energy mix by the year 2020 [1]. ronment with harmful gases, they still do have some negative
Currently, in the renewable electricity sector of the EU, hydropower impact on the environment, such as generated noise, visual intru-
plants contribute to the greatest extent (38% in the year 2015). sion into the landscape or potential harmfulness for wildlife
Nonetheless, wind is the type of renewable energy source which (mostly flying animals) [4,6,7]. Nevertheless, the environmental
exhibits the quickest expansion in terms of installed power. Its advantages of wind power plants generally outweigh their
presence has more than quadrupled over the period 2004e2015. In drawbacks.
2015, it accounted for 31% share in renewable electricity genera- In the European Union, electric energy produced from RES is
tion, or 24.6 Mtoe in absolute terms. It is expected that in 2020 the provided guaranteed access or priority access to the grid [1]. It is an
production of electricity from wind turbines and the production of important incentive for development of RES, but also a possible
electricity from hydropower plants will level up [2]. threat to the stability of the electric power system. Power output of
The worldwide popularity of wind as a renewable energy source RES such as wind farms or solar power plants depends on the
weather, and as such cannot be precisely predicted or controlled.
Wind turbines especially may exhibit strong transient fluctuations
of available power output. This effect becomes particularly visible
* Corresponding author.
E-mail addresses: tomasz.simla@polsl.pl (T. Simla), wojciech.stanek@polsl.pl in power systems with high share of wind energy (high “wind
(W. Stanek). penetration”). From the perspective of the electric grid such
https://doi.org/10.1016/j.renene.2019.06.028
0960-1481/© 2019 Elsevier Ltd. All rights reserved.
T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782 773
variability is very undesirable. In each moment the grid must sources alone cannot fully cover the system's demand for electric
maintain the balance of supply and demand. When no energy energy. It would require an overscaled system of renewable sour-
storage is used, the remaining power generation units (mostly fossil ces, characterized by huge losses of energy (defined as forced
fuel-based thermal units), have to be used for regulation purposes. curtailment of production due to lack of demand). Such in-
It results in more frequent changes in the power plants' load as well vestments would therefore be not feasible. The required storage
as increases the number of shut-down/start-up procedures. This capacity for various levels of renewable energy penetration in the
phenomenon is referred to as “cycling” of power plants. Overall, system is also determined in that study. Regarding the cooperation
such working regime reduces the efficiency of power plants. This of renewable sources with thermal power generators, scheduling of
issue is addressed in further sections of the paper. an energy storage system for an isolated power system comprising
The most desirable method of mitigation of cycling of thermal wind turbines and diesel engine is investigated in Ref. [27]. Study
power plants would be application of large-scale energy storage. It [28] examines combining a wind farm and a conventional thermal
would also improve the overall performance and efficiency of the unit with a CAES unit in order to increase profits and reduce costs
power system. Methods of energy storage can be categorized into for the owner of such system. A similar topic, but in a larger scale, is
several main groups. Since it is difficult to directly store electric investigated in Ref. [29]. Related research in Ref. [30] focuses on
energy (only capacitors and superconductors fall into this cate- optimizing the cost of energy in the network and investment-
gory), the majority of methods rely on converting electric energy in operational costs of the storage units, considering their practical
order to store it in a different form. The most common methods are characteristics as a design variable.
mechanical and chemical energy storage. Mechanical methods The abovementioned works focus mainly on the technical and
include pumped hydro storage (PHS), compressed air storage design aspects of energy storage units and/or economy, yet the
(CAES) and flywheels. Among chemical methods there are various system effects, including the overall consumption of resources are
kinds of electrochemical batteries (BES), as well as electrolyzers/ rarely investigated. The aim of this paper is to examine strategies
fuel cells (for storing energy in the form of hydrogen). Other for system-scale cooperation of renewable electric energy sources,
methods utilize thermal energy storage (i.e. storing energy in energy storage units and conventional thermal power plants with
suitable materials at high or low temperatures and then utilizing it the focus on consumption of non-renewable primary energy. En-
in a heat engine, thus producing electricity). All these technologies ergy losses both in storage units and thermal power plants are
vary greatly in terms of main characteristics, which are: storage taken into account.
capacity, power output, energy density, power density, response
time, charge/discharge duration, lifetime and round-trip efficiency. 2. Losses induced by wind power intermittency
Depending on these factors, different technological solutions are
applicable for various purposes that could be served for the energy The performance of thermal power plants is the best if they
system. The purposes are associated with the possible duration of operate under their nominal, design conditions. It is possible to
energy storage and include: power quality support, load levelling, reduce the load of these plants, in some cases even to a level as low
spinning reserve, energy arbitrage and long-term energy storage as 40%, but it comes at a cost of decreased efficiency. Efficiency
[8e10]. Table 1 presents a summary of the most common methods characteristic of a typical coal-fired power plant is presented in
of energy storage together with their main characteristics. Fig. 1. Efficiency drop affects not only the specific consumption of
The problem of scheduling energy storage units cooperating fuel and emission of carbon dioxide, but also increases the specific
with renewable electric energy sources is widely studied in the emissions of toxic gases such as SOX and NOX [5,31e34].
literature. Research in Refs. [11e15] focuses on use of energy stor- Introduction of highly variable wind sources to the grid imposes
age system (usually BES) to smoothen the output of a wind farm additional cycling, causing power plants to operate with lower ef-
and a solar photovoltaic plant, so that they can be dispatched on an ficiency more often. In addition, it increases the number of shut-
hourly basis like any other conventional generator and actively take down/start-up procedures. This is a problem especially in the
part in the market [16]. Similarly, studies [17e22] deal with optimal case of coal-fired power plants, because they have low flexibility
scheduling of renewables-storage generation systems focusing and high thermal inertia. The process of starting up a coal-fired
mainly on the technical constraints of various analysed storage power plant may take up several hours and is associated with
systems. Studies [23e25] investigate a control strategy for an en- considerable energy losses. Gas turbines perform much better in
ergy storage system which aims to increase the RES penetration such case; their start-up time is counted in minutes. However, in
level while improving the electric grid reliability and power gen- the absence of such flexible generation units, there is a need to
eration scheduling. Since the grid imposes a set of requirements maintain an extra spinning reserve, that is to keep some power
regarding the quality of electric energy, it does not permit presence plants operating at low load, so that they can respond quickly to a
of highly variable sources (such as wind) over a certain threshold. sudden shortage of power supply to the grid. The likelihood of
Smoothening the power output from these sources would allow for unexpected shortages increases with growing deployment of
a better integration of renewables into the grid. Research in intermittent, weather-dependent generation units, such as wind
Ref. [26] proves that due to their intermittent nature, renewable turbines.
Table 1
Comparison of technological solutions of energy storage [8e10].
Table 2
Thermo-ecological cost of electric energy [40].
Technology TEC
hel yearly average efficiency of the system of thermal power charged and negative value means that storage is discharged.
plants, Additionally, in order to avoid cumulation of energy in the
hel av ðtÞ hourly average electric efficiency of the system of storage over time, the model assumes that the amount of energy
thermal units, available in the storage Est at the end of the year must be the same
Eel coal total amount of electric energy produced by thermal as at the beginning of the year:
plants throughout the year,
SNtpp ðtÞ total output power of thermal power plants, Est ðt ¼ 0Þ ¼ Est ðt ¼ 8760Þ (5)
DEch loss chemical energy loss associated with a start-up pro- The amount of energy available in the storage at the beginning
cedure of a thermal unit, of the year Est ðt ¼ 0Þ must be large enough so that Est ðtÞ does not
P
Dn total number of start-up procedures per year, drop below zero throughout the year. Therefore, for each analysed
Dt time step (1 h). case it is determined as the lowest value which fulfils condition (6):
The superscript wind refers to the actual work of the system, and Est ðtÞ 0 (6)
the superscript no wind refers to the hypothetical situation when
there are no wind sources.
For the actual data for Poland from 2015 (with wind energy 3.1. Analysed variants
covering 6.6% of the total demand), the result of TECcomp turned out
to be rather low (in the range of 0e0.03) [37]. However, the Several variants of controlling the charge/discharge schedule of
simulation showed that if the wind penetration rises, its adverse the energy storage subsystem were conceived and investigated;
influence on the remaining part of the power system increases they are described below. They differ in terms of determining Nst ðtÞ
correspondingly. For wind penetration exceeding 20% the value of appearing in balance (4).
TECcomp reaches the level of 0.06e0.12, which is the same order of
magnitude as the value of “investment” TEC of wind turbines
3.1.1. Variant 1
(resulting from consumption of materials and energy in the con-
This variant assumes that energy storage is unavailable and
struction phase) presented in Table 2. Therefore, the discussed
therefore it can be treated as a reference for the other variants. It
phenomenon should not be neglected within evaluation of fossil
contains an assumption regarding the need to ensure spinning
fuel based energy systems with high share of wind energy.
reserve in thermal units in case of a sudden drop of power output
from wind turbines. The required reserve was assumed to be equal
3. Methodology to the maximum assumed hourly decrease of the total wind power
output. This value is calculated from the actual data on the
The next phase of the above described research is introducing observed hourly total wind power output, with an assumption that
energy storage units to the analysed system and examining stra- the spinning reserve requirement must be met 99% of the time. Due
tegies for system-scale cooperation of renewable electric energy to the assumptions regarding scaling of wind profile, the required
sources, energy storage units and conventional thermal power spinning reserve will increase with increasing wind penetration.
plants. The aim of this research is not to determine the physical or The number of required reserve thermal power plants nreserve can
ownership structure of the energy storage system, but rather to test be calculated using the following formula:
the potential effects of large scale energy storage on the perfor-
DNwind max
mance of the power system as a whole. For this purpose, the model nreserve ¼ (7)
contains as little constraints regarding the storage system as Ntpp max Ntpp min
possible: no specific energy storage technology is chosen and en-
ergy storage units are simply modelled as a “black box” with given
round-trip efficiency and no restrictions regarding storage capacity
or charge/discharge rate. Several heuristic methods for energy DNwind max maximum assumed hourly decrease of the total wind
storage scheduling are investigated. Results from these simulations power output,
will serve as a base for further research with the use of optimization Ntpp max maximum power output of a thermal power plant
methods. The round trip-efficiency was assumed in the range of (equal to 240 MW),
65e90% (compare with Table 1); calculations were repeated for Ntpp min minimum power output of a thermal power plant (equal
various values. The simulations of work of the power system were to 144 MW).
based on the previously developed model, quoted above [37]. Cal-
culations were performed based on the actual hourly demand As a consequence, even if the net demand for power is lower
profile of Polish power system and energy production of wind than the total power output from these reserve plants, they are not
turbines installed in the system (data from the year 2017) [41]. shut down. In such case, an overproduction of electric energy in the
During the simulations, energy production from wind was scaled to system Nsurplus ðtÞ appears:
obtain results for various levels of penetration of wind energy into
Nsurplus ðtÞ ¼ max 0; nreserve Ntpp min Ndem ðtÞ (8)
the system (the actual value for year 2017 was 8.56%). The method
of scaling the wind power profile is described in Appendix A. Therefore, one of the aims of this variant is to estimate the
The total power output of the thermal power plants SNtpp ðtÞ in amount of “redundant” wind energy, production of which must be
each hour is calculated from the following balance: curtailed in order to ensure the stability of the power system.
The presented assumption does not apply to the other variants,
SNtpp ðtÞ ¼ Ndem ðtÞ þ Nst ðtÞ (4)
since they employ energy storage, which can provide the power
Ndem ðtÞ system's net demand for electric power, that is the total reserve.
demand reduced by the power generation by non-dispatchable
power sources, including wind farms. 3.1.2. Variant 2
Nst ðtÞ power of the storage; positive value means that storage is Variant 2 aims to equalize the power output from the wind
776 T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782
farms. In reality, it would correspond to an assumption that each nf ðtÞ number of operating thermal power plants in a given hour,
wind farm is equipped with an energy storage unit, which attempts according to the forecast of demand,
to ensure a constant power output from the wind farm. Therefore, nðtÞ actual number of operating thermal power plants in a given
energy storage is charged when wind power is greater than the hour.
average, and discharged when wind power is lower than average:
In this case, the number of operating thermal power plants in
Nst ðtÞ ¼ Nwind ðtÞ Nwind av (9) the analysed hour is fixed according to the equation:
n h
Nwind ðtÞ total power output of the wind farms. nðtÞ ¼ min nðt 1Þ; max nf ðt þ 1Þ; nf ðt þ 2Þ; nf ðt þ 3Þ;
The “average” wind power used in calculations must be io
assumed in such a way, so that condition (5) is fulfilled. Therefore, it nf ðt þ 4Þ; nf ðt þ 5Þ; nf ðt þ 6Þ (13)
must be lower than the arithmetic average wind power, due to
energy losses during storage. For this reason, it is calculated
and the power directed to the storage is calculated using the
numerically for each simulated case.
formula:
3.1.3. Variant 3 Nst ðtÞ ¼ max 0; nðtÞ Ntpp min Ndem ðtÞ (14)
Here, the purpose of energy storage is to reduce the phenom-
enon of cycling by fixing a minimum and maximum number of Conversely, energy storage is discharged when condition (15) is
thermal units that can operate in the system. Energy storage will be fulfilled:
charged during periods of low power demand and discharged n o nh i h
during periods of high power demand, thus effectively relocating nf ðtÞ > nðt 1Þ ∧ nf ðt þ 1Þ nðt 1Þ ∨ nf ðt þ 2Þ
the power demand from peaks to valleys. First, the distribution of i h
net demand throughout the year is determined. A value of mini- nðt 1Þ ∨ nf ðt þ 3Þ
mum net demand Ndem min is assumed in such a way, that net de- i h
mand lower than Ndem min occurs only 10% of the time. (If the value nðt 1Þ ∨ nf ðt þ 4Þ
of Ndem min would be negative, then 0 is assumed instead.) If the net i h
nðt 1Þ ∨ nf ðt þ 5Þ
demand drops below Ndem min, the load of power plants is not
i h
further decreased and storage is charged instead: nðt 1Þ ∨ nf ðt þ 6Þ
io
Nst ðtÞ ¼ Ndem min Ndem ðtÞ (10) nðt 1Þ (15)
Similarly, energy storage is discharged if the net demand is
higher than assumed maximum Ndem max : In this case, the number of operating thermal power plants in
the analysed hour is fixed according to the equation:
Nst ðtÞ ¼ Ndem max Ndem ðtÞ (11) n h
nðtÞ ¼ max nðt 1Þ; min nf ðt þ 1Þ; nf ðt þ 2Þ; nf ðt þ 3Þ;
The value of Ndem max is calculated numerically for each simu-
io
lated case, so that condition (5) is fulfilled. nf ðt þ 4Þ; nf ðt þ 5Þ; nf ðt þ 6Þ (16)
3.1.4. Variant 4
and the power extracted from the storage is calculated using the
Variant 4 is similar to the previous one in terms of reducing
formula:
cycling. However, it bases on a forecast of net demand. The gross
demand of the system is easy to predict, as its nature does not
Nst ðtÞ ¼ max 0; Ndem ðtÞ nðtÞ Ntpp max (17)
change much over years and there is extensive amount of historical
statistical data. Exact power output of wind turbines is difficult to Independently from the procedure described above, this variant
predict, but nevertheless, it was assumed that the grid operator contains two more assumptions. The first one makes sure that if the
knows the exact value of the net demand 6 h in advance. If it turns amount of wind energy exceeds the system's demand, or in other
out that in the forecasting horizon a thermal unit would need to be words, if the net energy demand of the system in a given hour is
started up and then quickly shut down (or the opposite e shut negative, the surplus energy is directed to the storage:
down and then started up), the energy storage intervenes to pre-
vent such situations. Therefore, local peaks and depressions of the Nst ðtÞ ¼ maxð0; Ndem ðtÞÞ (18)
net demand are smoothened. Additionally, as the simulations proved that this control strategy
Energy storage is charged when condition (12) is fulfilled: may result in cumulation of energy in storage over time, condition
n o nh i h (11) was also applied to this variant. The value of Ndem max is
nf ðtÞ < nðt 1Þ ∧ nf ðt þ 1Þ nðt 1Þ ∨ nf ðt þ 2Þ calculated numerically for each simulated case, so that condition
i h (5) is fulfilled.
nðt 1Þ ∨ nf ðt þ 3Þ
i h
nðt 1Þ ∨ nf ðt þ 4Þ 3.2. Assessment indicators
i h
nðt 1Þ ∨ nf ðt þ 5Þ System effects are assessed with a series of indicators, both
i h locally and globally. Local balance boundary includes only the
nðt 1Þ ∨ nf ðt þ 6Þ thermal power plants and allows to determine whether introduc-
io tion of energy storage helps to reduce cycling of these plants and
nðt 1Þ (12) improve their efficiency. Global balance boundary covers the whole
electric energy system and considers the additional use of primary
energy due to losses in storage. Comparing these two balance
T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782 777
(b)
(c)
Fig. 3. Comparison of work of the system: (a) between Variants 1 and 2, (b) between Variants 1 and 3, (c) between variants 1 and 4.
T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782 779
Fig. 7. Required power of the energy storage system as a function of wind penetration.
Fig. 4. Comparison of load distribution curve of the system.
Fig. 6. Average efficiency of the system of thermal power plants as a function of wind Fig. 8. Required capacity of the energy storage system as a function of wind
penetration. penetration.
780 T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782
Table 3
Comparison of assessment indicators (for actual level of wind penetration in the year 2017).
Indicator Variant
0 1 2 3 4
Table 4
Comparison of assessment indicators (for 4 times higher wind penetration than in 2017).
Indicator Variant
0 1 2 3 4
5. Summary and conclusions It would also provide a better estimation of the losses of energy
during start-ups. Substituting the “black box” model of energy
In the present work, several scheduling strategies for coopera- storage with concrete technological solution would allow to
tion of an energy storage system with wind power sources and consider the actual efficiency characteristics of given energy stor-
thermal power plants were investigated. A thermo-ecological cost age units. The results of simulations regarding the power and ca-
was proposed and applied for the evaluation of local and global pacity of energy storage presented in this paper can be treated as
performance of such system. The presence of intermittent wind input assumptions to the developed model, to specify the scale of
energy sources in the system was proven to induce losses in ther- the storage system. Optimization methods can then be applied to
mal power plants which make the dominant part of the energy find the most beneficial strategy of energy storage dispatching.
system. Obtained results show that the compensation part of TEC Additionally, performing a “full” thermo-ecological analysis
may have a significant value when compared to the TEC resulting (including the “investment” TEC of energy storage units) will be
from life cycle assessment of wind turbines. For this reason, if a life possible, especially in cases when electric energy is not the final
cycle (or similar) analysis of wind energy sources is performed, the product of energy storage. An example of such situation is con-
adverse effects induced on the thermal power plants cooperating verting the surplus energy to the form of hydrogen.
with these wind sources should be also considered, particularly for Finally, an economic analysis of various solutions of energy
systems with high share of wind energy. It was determined that storage systems can be performed. It would determine whether
introducing energy storage may reduce these losses. Among the such systems would be profitable and competitive on the market or
analysed variants of energy storage scheduling, the one most if they would require some form of support, similar to that offered
beneficial was based on forecasting of the system's net demand for for renewable sources by governments in many countries. The TEC
energy and smoothening the local peaks and depressions of the net methodology proposed in this paper can be used for objective
demand. Not only did it improve the performance of the thermal determination of subsidies for renewable power plants and energy
power plants, but also decreased the overall consumption of non- storage units.
renewable resources in the system. However, as proven by the
other Variants, introduction of energy storage, while locally Acknowledgements
improving the performance of thermal power plants, may increase
the overall consumption of non-renewable resources due to the The support from the statutory research fund of the Faculty of
energy losses associated with storage. Nevertheless, the develop- Power and Environmental Engineering of SUT, Gliwice, Poland is
ment and application of large-scale energy storage is a necessity if gratefully acknowledged.
we want to achieve independency from fossil fuels and rely solely
on renewable energy. The necessity stems from weather- Appendix A
dependent nature of most RES and the inability to dispatch these
sources according to the needs of the power system. Fig. A1 presents the weekly standard deviation of total power
Next steps in the research include preparing a more detailed output of the wind farms in Poland as a function of their weekly
model of the Polish power system and replacing the “black box” average power output. The data covers three years of operation of
model of energy storage with specific technologies. More detailed wind farms in Poland e 2016, 2017 and 2018 [41]. A correlation
model of the power system would distinguish between the between the two presented variables can be observed. The hourly
different types of centrally dispatched power plants present in variations of the wind power profile (expressed by standard devi-
Poland (differentiating their capacity and efficiency characteristics). ation) increase with growing wind power output.
Fig. A1. Correlation between the standard deviation of wind power output and the average wind power output.
782 T. Simla, W. Stanek / Renewable Energy 145 (2020) 772e782
Scaling of the wind power profile, performed in order to simu- operation of grid-scale energy storage, Energies 7 (9) (Sep. 2014) 5847e5862.
[16] M. Dicorato, G. Forte, M. Pisani, M. Trovato, Planning and operating combined
late the work of the power system for various levels of wind
wind-storage system in electricity market, IEEE Trans. Sustain. Energy 3 (2)
penetration, has been done by a combination of multiplying the (Apr. 2012) 209e217.
wind profile by a constant factor a and elevating it by a constant [17] D. Yang, J. Wen, K. Chan, G. Cai, Dispatching of wind/battery energy storage
value b: hybrid systems using inner point method-based model predictive control,
Energies 9 (8) (Aug. 2016) 1e16.
[18] M. Xiong, F. Gao, K. Liu, S. Chen, J. Dong, Optimal real-time scheduling for
Nwind ðtÞ ¼ a Nwind 0 ðtÞ þ b (A.1) hybrid energy storage systems and wind farms based on model predictive
control, Energies 0 (8) (Aug. 2015) 8020e8051.
The coefficients a and b have been determined in such way, so [19] A. Nottrott, J. Kleissl, B. Washom, Energy dispatch schedule optimization and
that the following conditions are fulfilled: cost benefit analysis for grid-connected, photovoltaic-battery storage systems,
Renew. Energy 55 (Jul. 2013) 230e240.
[20] W.S. Ho, S. Macchietto, J.S. Lim, H. Hashim, Z.A. Muis, W.H. Liu, Optimal
N wind ¼ s Nwind 0 (A.2) scheduling of energy storage for renewable energy distributed energy gen-
eration system, Renew. Sustain. Energy Rev. 58 (May 2016) 1100e1107.
[21] M. Khalid, A.V. Savkin, An optimal operation of wind energy storage system
s ¼ a s Nwind 0 þ b (A.3) for frequency control based on model predictive control, Renew. Energy 48
(Dec. 2012) 127e132.
[22] E. Reihani, M. Motalieb, R. Ghorbani, L.S. Saoud, Load peak shaving and power
smoothing of a distribution grid with high renewable energy penetration,
Nwind average yearly wind power,
Renew. Energy 86 (Feb. 2016) 1372e1379.
s scaling factor, [23] A. Damiano, G. Gatto, I. Marongiu, M. Porru, A. Serpi, Real-time control
s yearly standard deviation of the wind power, strategy of energy storage systems for renewable energy sources exploitation,
a; b correlation coefficients for standard deviation, as seen in IEEE Trans. Sustain. Energy 5 (2) (Apr. 2014) 567e576.
[24] J. Yi, P.F. Lyons, P.J. Davison, P. Wang, P.C. Taylor, Robust scheduling scheme
Fig. A1, for energy storage to facilitate high penetration of renewables, IEEE Trans.
Sustain. Energy 7 (2) (Apr. 2016) 797e807.
The subscript 0 refers to the reference wind profile. [25] J. Zhu, W. pan, X. Li, Energy storage scheduling design on friendly grid wind
power, Sustain. Energy Technol. Assess. 25 (8) (Feb. 2018) 111e118.
The used method is a tradeoff between simple scaling (a ¼ s and
[26] S.G. Goyena, O.A. S
adaba, Sizing and analysis of big scale and isolated electric
b ¼ 0), which would overestimate the variations of wind profile, systems based on renewable sources with energy storage, in: Proceedings of
and simple elevating (a ¼ 1 and b ¼ ðs 1Þ Nwind 0 ), which would 2009 IEEE PES/IAS Conference on Sustainable Alternative Energy, 2009.
[27] M. Ross, R. Hidalgo, C. Abbey, G. Joo s, Energy storage system scheduling for an
not affect the variations of wind profile at all. isolated microgrid, IET Renew. Power Gener. 5 (Jul. 2010) 117e123.
[28] M. Abbaspour, M. Satkin, B. Mohammadi-Ivatloo, F. Hoseinzadeh Lotfi,
References Y. Noorollahi, Optimal operation scheduling of wind power integrated with
compressed air energy storage (CAES), Renew. Energy 51 (Mar. 2013) 53e59.
[29] S. Reddy, Optimal scheduling of thermal-wind-solar power system with
[1] Directive 2009/28/EC of the European Parliament. Available at: <http://eur-
storage, Renew. Energy 101 (Feb. 2017) 1357e1368.
lex.europa.eu/legal-content/EN/TXT/?q¼1487081346577&uri¼CELEX:
[30] R. Hemmati, Optimal design and operation of energy storage systems and
32009L0028> [accessed 14.2.2017].
generators in the network installed with wind turbines considering practical
[2] reportRenewable Energy Progress Report. Available at: <https://eur-lex.
characteristics of storage units as design variable, J. Clean. Prod. 185 (Jun.
europa.eu/legal-content/EN/TXT/?qid¼1531746737191&uri¼CELEX:
2018) 680e693.
52017DC0057> [accessed 26.07.2018].
[31] N. Troy, E. Denny, M. O'Malley, Base-load cycling on a system with significant
[3] Tabassum-Abbasi, M. Premalatha, T. Abbasi, S.A. Abbasi, Wind energy:
wind penetration, IEEE Trans. Power Syst. 25 (2) (May 2010) 1088e1097.
increasing deployment, rising environmental concerns, Renew. Sustain. En-
[32] F. Gutierrez-Martín, R.A. Da Silva-Alvarez, P. Montoro-Pintado, Effects of wind
ergy Rev. 31 (Mar. 2014) 270e288.
intermittency on reduction of CO2 emissions: the case of the Spanish power
[4] R. Saidur, N.A. Rahim, M.R. Islam, K.H. Solangi, Environmental impact of wind
system, Energy 61 (Nov. 2013) 108e117.
energy, Renew. Sustain. Energy Rev. 15 (5) (Jun. 2011) 2423e2430.
[33] R. Turconi, C. O'Dwyer, D. Flynn, T. Astrup, Emissions from cycling of thermal
[5] Y. Yang, H.S. Solgaard, W. Haider, Wind, hydro or mixed renewable energy
power plants in electricity systems with high penetration of wind power: life
source: preference for electricity products when the share of renewable en-
cycle assessment for Ireland, Appl. Energy 131 (Oct. 2014) 1e8.
ergy increases, Energy Policy 97 (Oct. 2016) 521e531.
[34] D.L. Oates, P. Jaramillo, Production cost and air emissions impacts of coal
[6] K. Dai, A. Bergot, C. Liang, W. Xiang, Z. Huang, Environmental issues associated
cycling in power systems with large-scale wind penetration, Environ. Res.
with wind energy e a review, Renew. Energy 75 (Mar. 2015) 911e921.
Lett. 8 (2) (May 2013) 1e7.
[7] D.Y.C. Leung, Y. Yang, Wind energy development and its environmental
[35] H. Inhaber, Why wind power does not deliver the expected emissions re-
impact: a review, Renew. Sustain. Energy Rev. 16 (1) (Jan. 2012) 1031e1039.
ductions, Renew. Sustain. Energy Rev. 15 (6) (Aug. 2011) 2557e2562.
[8] D. Akinyele, R. Rayudu, Review of energy storage technologies for sustainable
[36] D. Wagman, Rethinking wind's impact on emissions and cycling costs, Power
power networks, Sustain. Energy Technol. Assess. 8 (Dec. 2015) 74e91.
Mag. 157 (Mar. 2013) 62e66.
[9] A. Castillo, D.F. Gayme, Grid-scale energy storage applications in renewable
[37] T. Simla, W. Stanek, L. Czarnowska, Thermo-ecological cost of electricity
energy integration: a survey, Energy Convers. Manag. 87 (Nov. 2014)
generated in wind turbine systems, ASME J. Energy Resour. Technol. 141 (3)
885e894.
(Oct. 2018), 031201-1-031201-7.
[10] M. Yekini Suberu, M. Wazir Mustafa, N. Bashir, Energy storage systems for
[38] J. Szargut, A. Zie˛ bik, W. Stanek, Depletion of the non-renewable natural exergy
renewable energy power sector integration and mitigation of intermittency,
resources as a measure of the ecological cost, Energy Convers. Manag. 43
Renew. Sustain. Energy Rev. 35 (Jul) (2014) 499e514.
(Issies 9e12) (Jun. 2002) 1149e1163.
[11] S. Teleke, M. Baran, A.Q. Huang, S. Bhattacharya, L. Anderson, Control strate-
[39] W. Stanek, Examples of application of exergy analysis for the evaluation of
gies for battery energy storage for wind farm dispatching, IEEE Trans. Energy
ecological effects in thermal processes, Int. J. Thermodyn. 15 (2012) 11e16.
Convers. 24 (3) (Sep. 2009) 725e732.
[40] W. Stanek, L. Czarnowska, W. Gazda, T. Simla, Thermo-ecological cost of
[12] S. Teleke, M.E. Baran, S. Bhattacharya, A.Q. Huang, Rule-based control of
electricity from renewable energy sources, Renew. Energy 115 (Jan. 2018)
battery energy storage for dispatching intermittent renewable sources, IEEE
87e96.
Trans. Sustain. Energy 1 (3) (Oct. 2010) 117e124.
[41] Polskie Sieci Energetyczne, Data on the Power System, Available at: https://
[13] J. Shi, W. Lee, X. Liu, Generation scheduling optimization of wind-energy
www.pse.pl/dane-systemowe/funkcjonowanie-kse/raporty-dobowe-z-pracy-
storage system based on wind power output fluctuation features, IEEE
kse. (Accessed 26 July 2018).
Trans. Ind. Appl. 54 (1) (Jan. 2018) 10e17.
[42] G. Dudek, Ekonomiczny Rozdział Obcia˛ ze _ n Z Zastosowaniem Algorytmo w
[14] S. Dutta, T.J. Overbye, Optimal storage scheduling for minimizing schedule
Ewolucyjnych, Cze˛ stochowa University of Technology, Cze˛ stochowa, 2002.
deviations considering variability of generated wind power, in: Proceedings of
[43] L. Czarnowska, Thermo-ecological Cost of Products with Emphasis on External
2011 IEEE/PES Power Systems Conference and Exposition, 2011.
Environmental Costs, Silesian University of Technology & National Technical
[15] D. Halamay, M. Antonishen, K. Lajoie, A. Bostrom, T.K.A. Brekken, Improving
University of Athens, 2014.
wind farm dispatchability using model predictive control for optimal