You are on page 1of 3

Air Valve Sizing Software Program

Val-Matic Valve and Manufacturing Corporation

905 Riverside Drive


Elmhurst, IL 60126 USA

PROJECT INFORMATION

PROJECT: LORETO MUSHUÑAN 1

OWNER: Erika Morales


ENGINEER: NELSON PEDRAZA

MEDIA: Water - ANSI/NSF 61 Certified


PIPE MATERIAL: Plastic
PIPE INSIDE DIAMETER: 285.0 mm
PLASTIC PIPE COLLAPSE PRESSURE: 2 MPa

MAX FLOW RATE: 122.0 L/sec


FILL RATE: 100.0 L/sec
SELECTED SAFETY FACTOR: 2:1
DIFF. PRESS. FOR VAC. SIZING: 1.00 Psi

VALVE RATING: 75 Psig (Class 125 Iron)

FLOW DIRECTION: With Increasing Stations


VALVE SELECTION CRITERIA: Dual Body Comb Air Valves

PIPELINE AIR VALVE SCHEDULE:


Station Elevation Description Recommended Valve Size/Model Flow Rate
M M CFS

9957383 2842 Beginning of Pipeline No valve necessary 0.00


9957390 2840 Decrease in Down Slope No valve necessary 0.00
9957421 2839 Increase in Down Slope 2.25
9957467 2835 Decrease in Down Slope No valve necessary 0.00
9957512 2833 Decrease in Down Slope No valve necessary 0.00
9957542 2832 Decrease in Down Slope No valve necessary 0.00
9957563 2831 Increase in Down Slope 2.96
9957572 2830 Decrease in Down Slope No valve necessary 0.00
9957583 2828 Low Point No valve necessary 6.60
9957592 2828 Increase in Up Slope No valve necessary 0.00
9957599 2829 Increase in Up Slope No valve necessary 0.00
9957607 2830 Increase in Up Slope No valve necessary 0.00
9957616 2832 High Point 8.51
9957625 2832 Increase in Down Slope 3.40
9957635 2830 Decrease in Down Slope No valve necessary 0.00
9957662 2827 Increase in Down Slope 0.16
9957679 2823 Decrease in Down Slope No valve necessary 0.00
9957693 2821 Increase in Down Slope 3.91
9957708 2817 Decrease in Down Slope No valve necessary 0.00
9957734 2812 Decrease in Down Slope No valve necessary 0.00
PIPELINE AIR VALVE SCHEDULE:
Station Elevation Description Recommended Valve Size/Model Flow Rate
M M CFS

9957747 2810 Decrease in Down Slope No valve necessary 0.00


9957765 2808 Increase in Down Slope 0.02
9957783 2806 Decrease in Down Slope No valve necessary 0.00
9957806 2804 Low Point No valve necessary 6.64
9957810 2805 Decrease in Up Slope 1.20
9957834 2807 Increase in Up Slope No valve necessary 0.00
9957864 2808 High Point 7.35
9957895 2806 Decrease in Down Slope No valve necessary 0.00
9957921 2805 Low Point No valve necessary 6.56
9957946 2806 Increase in Up Slope No valve necessary 0.00
9957977 2807 High Point 6.12
9958002 2806 Low Point No valve necessary 6.12
9958032 2806 High Point 10.11
9958059 2802 Decrease in Down Slope No valve necessary 0.00
9958090 2801 Increase in Down Slope 6.40
9958116 2795 Decrease in Down Slope No valve necessary 0.00
9958146 2792 Increase in Down Slope 5.27
9958175 2785 Decrease in Down Slope No valve necessary 0.00
9958202 2781 Increase in Down Slope 1.44
9958220 2778 Increase in Down Slope 1.18
9958233 2776 Increase in Down Slope 5.87
9958269 2769 Decrease in Down Slope No valve necessary 0.00
9958302 2764 Increase in Down Slope 4.89
9958335 2754 Decrease in Down Slope No valve necessary 0.00
9958361 2748 Increase in Down Slope 32.65
9958372 2690 Low Point No valve necessary 45.72
9958375 2745 High Point 45.97
9958376 2705 Low Point No valve necessary 39.45
9958377 2716 High Point 32.82
9958381 2744 End No valve necessary 32.82
(*) These Stations were added because the segment length exceeded 2500 ft. (762 M)

1) The flow rate is the line-break flow in the adjecent line. At changes in the upslope or downslope, the flow rate is computed by subtracting the flow rate in the feeding leg from
the flow rate in the lower leg. For long ascents and descents, the flow rate is one half of the line-break flow.

2) Air release valve model numbers are for full size connections; smaller connections are available.

3) In accordance with State EPA requirements, all potable water air valves must be ANSI/NSF 61 Certified.

4) Stations are added as needed (i.e. 1600) to provide a maximum spacing of 2500 ft (760 M).

NOTES

The project has been pre-determined to illustrate the AirValve program functionality.

PREPARED BY: DATE: 05/15/2019

Disclaimer Notice
This Air Valve Sizing Software Program was developed by Val-Matic® Valve and Manufacturing Corporation as a convenience to its customers and should be utilized only as a
guide for the selection and placement of Air Valves along a pipeline. This software program is not presented as, nor is it intended to be used as, a complete hydraulic transient
study. This software program is offered on an as is basis. All risk regarding the appropriateness of the application are assumed by the user. Val-Matic makes no warranty or
representation as to the accuracy or completeness of this software program or its output. Use of this software program or its output should be made under the direction of trained
engineers or design professionals exercising their independent judgment regarding the suggested use of the valve types and sizes.