The procedure to be followed for water circuit preservation shall depend on the ambient
conditions during the shutdown.
1. All the water circuits, that is, chilled water, cooling water and condensate water from steam
circuit, shall be completely filled with water.
2. The water quality shall be maintained by necessary chemical dosing to avoid algae and
bacterial growth.
3. Pumps shall be operated for 20-30 mins every 15 days to circulate water in each circuit to
avoid algae and bacterial growth due to stagnant conditions. This shall help replacing the
stagnant water in the chiller with fresh water.
1. The chilled water and cooling water circuits shall be completely drained using the drain ports
Provided on Absorber and Evaporator Headers.
2. If scaling is prevalent, then the tubes shall be cleaned as per recommendation.
3. After complete draining and cleaning, the tubes shall be dried by blowing dry
compressed/pressurized air.