Surge protection for CCTV systems
White Paper
CCTV systems are used in all sectors for access control and cable. Coaxial cables are used for unbalanced transmission, in
facility supervision. In the following, surge protection meas- other words the video signal is transmitted through the core
ures will be described which meet the high availability require- of the coaxial cable (inner conductor). The shield (earth) is the
ments of CCTV systems. reference point for signal transmission. Balanced transmission
A CCTV system consists of at least one camera, one monitor
(baluns) where the coaxial signal is converted to a two-wire
and one suitable video transmission path. Remotely controlled
signal is used for two-wire cables.
camera stations are typically equipped with a pan / tilt head
which allows the operator to individually adjust the position The voltage supply cable is often routed separately. In case of
and the perspective of the station. IP cameras, however, a single cable is used for the transmis-
In the simplest case, the transmission line between the junc- sion of the video signal and for voltage supply. An RS 485 bus
tion box and the monitor is a coaxial or a balanced two-wire controls the panning and tilting of the camera.
junction box
short coaxial or
steel mast two-wire cable
junction box
230 V cable RS 485 cable
MEB
Figure 1 Camera connected to a building with external lightning protection system and lightning current carrying surge protective devices
on both ends
coaxial or
two-wire cable
junction box
Figure 2 Camera connected to a building without external lightning protection system with surge protective devices on both ends
the metal mast. If this is not possible, the camera cable must
IP camera camera PC be routed in a metal tube and conductively connected to the
mast. In this case, surge protective devices do not have to be
installed in the junction box if the cable length does not ex-
ceed some metres.
junction box Lightning equipotential bonding must be established at the
entrance point into the building for all cables mentioned above
which are routed from the junction box at the mast to a build-
ing with external lightning protection system (Table 1).
If cameras are mounted on the outer façade of a building, it
junction box should be ensured that the camera is located in the protected
volume or is protected from direct lightning strikes by an air-
termination system.
LAN cable
DEHNshield
DEHNshield
DEHNguard
DEHNguard
BLITZDUCTOR XT
Basic circuit diagram BXT ML2 BD HFS Dimension drawing BXT ML2 BD HFS
Space-saving combined lightning current and surge arrester module with LifeCheck feature for protecting one pair of unearthed high-frequency bus
systems or video transmission systems, with direct or indirect shield earthing. If LifeCheck detects thermal or electrical overload, the arrester has to be
replaced. This status is indicated contactlessly by the DEHNrecord LC / SCM / MCM reader.
Type BXT ML2 BD HFS 5
Part No. 920 271
SPD monitoring system LifeCheck
SPD class M
Nominal voltage (UN) 5 V
Max. continuous operating d.c. voltage (UC) 6.0 V
Max. continuous operating a.c. voltage (UC) 4.2 V
Nominal current at 45 °C (IL) 1.0 A
D1 Total lightning impulse current (10/350 µs) (Iimp) 9 kA
D1 Lightning impulse current (10/350 µs) per line (Iimp) 2.5 kA
C2 Total nominal discharge current (8/20 µs) (In) 20 kA
C2 Nominal discharge current (8/20 µs) per line (In) 10 kA
Voltage protection level line-line for Iimp D1 (Up) ≤ 25 V
Voltage protection level line-PG for Iimp D1 (Up) ≤ 550 V
Voltage protection level line-line at 1 kV/µs C3 (Up) ≤ 11 V
Voltage protection level line-PG at 1 kV/µs C3 (Up) ≤ 550 V
Series resistance per line 1.0 ohm(s)
Cut-off frequency line-line (fG) 100.0 MHz
Capacitance line-line (C) ≤ 25 pF
Capacitance line-PG (C) ≤ 25 pF
Operating temperature range (TU) -40 °C ... +80 °C
Degree of protection (plugged-in) IP 20
Pluggable into BXT BAS / BSP BAS 4 base part
Earthing via BXT BAS / BSP BAS 4 base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21 / EN 61643-21, UL 497B
)
SIL classification up to SIL3 *
ATEX approvals DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc
IECEx approvals DEK 11.0032X: Ex nA IIC T4 Gc
CSA & USA Hazloc approvals (1) 2516389: Class I Div. 2 GP A, B, C, D T4
CSA & USA Hazloc approvals (2) 2516389: Class I Zone 2, AEx nA IIC T4
Approvals CSA, UL, GOST, VdS
Weight 22 g
Customs tariff number 85363010
GTIN 4013364117556
PU 1 pc(s)
)
* For more detailed information, please visit www.dehn-international.com.
BLITZDUCTOR SP
)
* For more detailed information, please visit www.dehn-international.com.
BLITZDUCTOR
Basic circuit diagram with and without plugged-in module Dimension drawing BXT BAS
The BLITZDUCTOR XT base part is a very space-saving and universal four-pole feed-through terminal for the insertion of a protection module without
signal interruption if the protection module is removed. The snap-in mechanism at the supporting foot of the base part allows the protection module
to be safely earthed via the DIN rail. Since no components of the protective circuit are situated in the base part, only the protection modules must be
maintained.
Type BXT BAS
Part No. 920 300
Operating temperature range (TU) -40 °C ... +80 °C
Degree of protection IP 20
For mounting on 35 mm DIN rails acc. to EN 60715
Connection (input / output) screw / screw
Signal disconnection no
2
Cross-sectional area, solid 0.08-4 mm
2
Cross-sectional area, flexible 0.08-2.5 mm
Tightening torque (terminals) 0.4 Nm
Earthing via 35 mm DIN rails acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour yellow
)
ATEX approvals DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc *
)
IECEx approvals DEK 11.0032X: Ex nA IIC T4 Gc *
Approvals CSA, VdS, UL, GOST
Weight 34 g
Customs tariff number 85369010
GTIN 4013364109179
PU 1 pc(s)
)
* only in connection with an approved protection module
DEHNgate
Basic circuit diagram DGA BNC VCID Dimension drawing DGA BNC VCID
DEHNpatch
Basic circuit diagram DPA M CAT6 RJ45S 48 Dimension drawing DPA M CAT6 RJ45S 48
Universal arrester for Industrial Ethernet, Power over Ethernet (PoE+ according to IEEE 802.3at up to 57 V) and similar applications in structured
cabling systems according to Cat. 6 and class EA up to 500 MHz. Fully shielded type for DIN rail mounting.
Accessories: Earthing bracket with flat connector sleeve
Type DPA M CAT6 RJ45S 48
Part No. 929 100
SPD class T
Nominal voltage (UN) 48 V
Max. continuous operating d.c. voltage (Uc) 48 V
Max. continuous operating a.c. voltage (Uc) 34 V
Max. continuous operating d.c. voltage pair-pair (PoE) (Uc) 57 V
Nominal current (IL) 1 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1 kA
C2 Nominal discharge current (8/20 µs) line-line (In) 150 A
C2 Nominal discharge current (8/20 µs) line-PG (In) 2.5 kA
C2 Total nominal discharge current (8/20 µs) line-PG (In) 10 kA
C2 Nominal discharge current (8/20 µs) pair-pair (PoE) (In) 150 A
Voltage protection level line-line for In C2 (UP) ≤ 190 V
Voltage protection level line-PG for In C2 (UP) ≤ 600 V
Voltage protection level line-line for In C2 (PoE) (UP) ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 (UP) ≤ 145 V
Voltage protection level line-PG at 1 kV/µs C3 (UP) ≤ 500 V
Voltage protection level pair-pair at 1 kV/µs C3 (PoE) (UP) ≤ 600 V
Insertion loss at 250 MHz ≤ 2 dB
Capacitance line-line (C) ≤ 165 pF
Capacitance line-PG (C) ≤ 255 pF
Operating temperature range (TU) -20 °C ... +60 °C
Degree of protection IP 20
For mounting on 35 mm DIN rails acc. to EN 60715
Connection (input / output) RJ45 connecting line / RJ45 connecting line
Pinning 1/2, 3/6, 4/5, 7/8
*
Connecting line A = approx. 0.5 m, G = approx. 3 m )
Connector Stewart 39 series
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material zinc die-casting
Colour bare surface
Test standards IEC 61643-21 / EN 61643-21
Transmission class according to ISO/IEC 11801 Cat. 6
Transmission class according to EN 50173-1 Class EA
Transmission class according to ANSI/TIA/EIA-568 cat. 6A in the channel
Approvals GHMT, GOST
Accessories fixing material
Weight 244 g
Customs tariff number 85363010
GTIN 4013364102170
PU 1 pc(s)
*)
Special lengths on request
DEHNpatch
Basic circuit diagram DPA CLE RJ45B 48 Dimension drawing DPA CLE RJ45B 48
Universal arrester for Industrial Ethernet, Power over Ethernet (PoE+ acc. to IEEE 802.3at up to 57 V) and similar applications in structured cabling
systems according to class E up to 250 MHz. Protection of all pairs by means of powerful gas discharge tubes and one adapted filter matrix per pair.
Fully shielded type with sockets for DIN rail mounting (up to 1 Gbit Ethernet).
Accessories: Earthing bracket with flat connector sleeve
Type DPA M CLE RJ45B 48
Part No. 929 121
SPD class T
Nominal voltage (UN) 48 V
Max. continuous operating d.c. voltage (Uc) 48 V
Max. continuous operating a.c. voltage (Uc) 34 V
Max. continuous operating d.c. voltage pair-pair (PoE) (Uc) 57 V
Nominal current (IL) 1 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 0.5 kA
C2 Nominal discharge current (8/20 µs) line-line (In) 150 A
C2 Nominal discharge current (8/20 µs) line-PG (In) 2.5 kA
C2 Total nominal discharge current (8/20 µs) line-PG (In) 10 kA
C2 Nominal discharge current (8/20 µs) pair-pair (PoE) (In) 150 A
Voltage protection level line-line for In C2 (UP) ≤ 180 V
Voltage protection level line-PG for In C2 (UP) ≤ 500 V
Voltage protection level line-line for In C2 (PoE) (UP) ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 (UP) ≤ 180 V
Voltage protection level line-PG at 1 kV/µs C3 (UP) ≤ 500 V
Voltage protection level pair-pair at 1 kV/µs C3 (PoE) (UP) ≤ 600 V
Insertion loss at 250 MHz ≤ 3 dB
Capacitance line-line (C) ≤ 30 pF
Capacitance line-PG (C) ≤ 25 pF
Operating temperature range (TU) -40 °C ... +80 °C
Degree of protection IP 10
For mounting on 35 mm DIN rails acc. to EN 60715
Connection (input / output) RJ45 socket / RJ45 socket
Pinning 1/2, 3/6, 4/5, 7/8
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material zinc die-casting
Colour bare surface
Test standards IEC 61643-21 / EN 61643-21
Approvals CSA, UL, GOST
Accessories fixing material
Weight 123 g
Customs tariff number 85366910
GTIN 4013364118935
PU 1 pc(s)
UGKF
www.dehn-international.com/partners
Type designations of products mentioned in the white paper being at the same time registered trademarks are not especially marked. So if there is no marking of ™ or ® this does not
mean that the type designation is a free trade name. Neither it can be seen whether patents or utility models and other intellectual and industrial property rights are available. We reserve
the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.
Misprints, errors and modifications excepted. Reproduction in any form whatsoever is forbidden without our authorisation.
actiVsense, BLITZDUCTOR, BLITZPLANER, DEHN, DEHN Logo, DEHN schützt, DEHNbloc, DEHNfix, DEHNgrip, DEHNguard, DEHNport, DEHNQUICK, DEHNrapid, DEHNshield, DEHNsnap,
DEHNventil, HVI, LifeCheck, Red/Line are protected by German Trade Mark, by Community Trade Mark (EU) and/or in other countries.