INDIAN STANDARD-
CODE OF PRACTICE FOR INDUSTRIAL LIGHTING
TABLE 2 RECOMMENDED VALUES OF ILLUMINATION AND LIMITING
VALUES OF GLARE INDEX
4. Assembly Shops
a. Rough work, for example, frame 150 28
assembly of heavy machinery
b. Medium work for example, 300 25
machined parts, engine assembly
vehicle body assembly
c. Fine work, for example, radio and 700 22
telephone equipment, typewriter
and office machinery assembly
d. Very fine work, or example, 1500* 19
assembly, of very small precision