You are on page 1of 6

Presentation, Switch mode power supplies and safety

description isolation transformers


ABL2 plate switch mode power supplies

Presentation
rd
ABL2REM series of switch mode power supplies adopt the 3 generation of switch
mode power supply design technologies with a small and exquisite bulk and stable
performance, used to provide the DC voltage necessary for electrical equipment
operating on a safety low voltage. This series of power supplies are able to satisfy all the
demands of standard commercial equipment and meet the current standards throughout
the world. As the equipment groupware, it has advantages of being easy in installation
and suited to different mounting needs on different application occasions.

ABL2REM switch mode power supplies are totally electronic and regulated. They provide the
following benefits:
● Compact bulk to save the mounting space (35W/50W/100W/150W)
● Wide range of input voltage (AC88-264V and DC110-370V. Different power ranges differ.
See the product parameters for details.)
● Stable output voltage, adjustable by the potentiometer.
● Conformity to Standard EN 55022 Class B.
● Overload, short-circuit, overvoltage and superheat protections (the superheat protection is
suitable for 200-350W)
● All models have the mounting accessories with standard guides.

ABL2REM switch mode power supplies provide 24V DC output and have following products
with seven power ranges:
DC 24V 35W, 50W, 100W, 150W, 200W, 250W and 350W

Electromagnetic compatibility
Levels of conducted and radiated emissions are defined in Standards EN 55011 and EN
55022.
The switch mode power supplies in the ABL2REM range are Class B, the strictest level.

Behaviour in the event of short-circuits


ABL2 power supplies are equipped with electronic and thermal overload protection. This
protection resets itself automatically on elimination of the fault, which avoids having to take any
action or change a fuse.

Descriptions
ABL 2REM regulated switch mode power supplies comprise:
1 Two fixing holes for M3 screws.
2 A 115/230 V input voltage selector (on 150 W, 200 W, 250 W and 350 W versions only).
2
3 A 4 mm screw clamp terminal block for connection of the AC input voltage and DC output
voltage.
4 A green LED indicating the presence of DC output voltage.
5 An output voltage adjustment potentiometer (± 10 %).

Characteristics: References: Schemes: Dimensions, mounting:


page 65 page 67 page 67 page 68 and 69
64
Characteristics Switch mode power supplies and safety
isolation transformers
ABL2 plate switch mode power supplies

Technical characteristics
Type of power supply ABL2REM
24015 24020 24045 24065 24085 24100 24150
Product certifications/markings , RoHS
Conforming to Safety According to IEC / EN 60950
standards Generic EMC EN 61000-6-2,EN 61000-4-2,3,4,5,6,8,11,EN 55022 Class B
Input circuit Low frequency harmonic currents –
Input circuit
LED indication –
Nominal input Nominal voltage V AC 100...240 AC 100...120 / 200...240
values Limit voltage AC V 88...264 88...132 /180...264
DC compatible V 110...370 (1) 255...370 (1)
Input current UIn = 230 VAC A 0.4 0.8 1 1.5 2.5 3.5
UIn = 115 VAC A 0.8 1.3 2 3 5 7
Permissible frequencies Hz 47...63
Maximum input inrush current A 30 35 50
Efficiency at nominal load > 84 %
Output circuit
LED indication Green LED
Nominal output Voltage (UOut) V DC 24
values Current A 1.5 2.2 4.5 6.5 8.3 10.5 14.6
Power W 35 50 100 150 200 250 350
Precision Adjustable output voltage ± 10%
Voltage tolerance ± 1%
Ripple and noise mV < 100 (peak-peak)
Start up time ms 500 (80 with loads)
Holding time ms >20 (10 with loads)
Protections Short circuit Down mode, non-permanent shutdown Permanent shutdown, restart after
power-on
Overload Down mode, non-permanent shutdown (at Permanent shutdown, restart after
120...150% of the nominal voltage) power-on (at 120...150% of the
nominal voltage)
Overvoltage Permanent shutdown, restart after power-on (at 115...145%of the nominal voltage)
Overheat None Permanent shutdown, restart after
power-on (at 115...145%of the
nominal voltage)
Operating and environmental characteristics
Connections Input mm2 (2 + earth wire) x 4 (12 AWG)
Output mm2 2 x 4 (12 AWG) 4 x 4 (12 AWG)
Mounting Panel mounting or guide mounting
Operating position Vertical or horizontal, see page 66
Connections Series connection Possible (two at most), see page 66
Parallel connection Not used for the parallel connection
Environment Temperature Operating °C -20…+ 70 (derating from 50 °C), see page 66
Storage °C -20…+ 85
Humidity Operating RH 20…90 %
Storage RH 10…95 %
Temperature coefficient ± 0.03%/ °C (0-50°C)
Vibrations According to Standard EN 61131-2
MTBF at 25 °C > 350 khrs ,Mil-HDBK-217F
Insulation voltage I/ P-O/P:1.5 KVAC,I/P-FG:1.5KVAC,O/P-FG:0.5KVAC
Insulation impedance I/P-O/P,I/P-FG,O/P-FG:100 M ohms/500VDC
Mechanical characteristics
Connections Input mm2 (2 + earth wire) x 4 (12 AWG)
Output mm2 2 x 4 (12 AWG) 4 x 4 (12 AWG)
Mounting Panel mounting or guide mounting
Size (L*W*H) mm 99*82*36 99*97*36 159*97*38 199*98*38 215*115*50
(1) Not indicated on the products.

References: Schemes: Dimensions, mounting:


page 67 page 67 page 68 and 69
65
Characteristics (continued) Switch mode power supplies and safety
isolation transformers
ABL2 plate switch mode power supplies

Output characteristics
Derating
The ambient temperature is a determining factor which limits the power an electronic power
supply can deliver continuously. If the temperature around the electronic components is too high,
their life will be significantly reduced.
The nominal ambient temperature in the ABL2REM range of power supplies is +45°C (horizontal
mounting) or +50°C (vertical mounting with the terminal block leftwards and the venthole
upwards). Above this temperature, it starts derating to the highest temperature of 65°C
(horizontal) and 70°C (vertical) respectively.
The curves below show the relationship between the power (in relation to the nominal power) the
power supplies can deliver continuously and the ambient temperature.

Output derating curve

Load factor (%)


Mounting on the vertical plane

Ambient temperature (℃)


Mounting on the horizontal plane Horizontal Vertical
mounting mounting

Extreme operating conditions


The derating should be considered in extreme operating conditions:
c Intensive operation (the output current should be close to the nominal current for a long time,
combined with a higher ambient temperature);
c The output voltage is set above 24 V.

General rules to be complied with


Intensive operation See the above derating curves.

Rise in the output voltage The nominal power is fixed.


The Increase of the output voltage means that the current delivered must be
reduced.

In all cases, there must be adequate convection round the power supplies to ensure easier
cooling. There must be a clear space of 50 mm above and below the products and of 20 mm at
the sides. The mechanical ventholes of 200W/250 W/350 W must not be blocked out.

Dimensions are in
mm (inch)

Series connection

Presentation: Description: References: Schemes: Dimensions, mounting:


page 64 page 64 page 67 page 67 page 68 and 69
66
References, Switch mode power supplies and safety
schemes isolation transformers
ABL2 plate switch mode power supplies

References
ABL2 plate switch mode power supplies: ABL 2REM

Input voltage Output voltage Nominal Nominal Auto-protect Conforming to Reference


47...63 Hz power current reset standard IEC/EN
61000-3-2
V V W A
AC 100…240 (1) 24 35 1.5 Automatic No ABL 2REM24015

single-phase 50 2 Automatic No ABL 2REM24020


wide range 100 4.5 Automatic No ABL 2REM24045
ABL 2REM24●●●

AC 100...120 24 150 6.5 Automatic No ABL 2REM24065

AC 200...240 (2) 200 8.3 Automatic No ABL 2REM24085


single-phase 250 10.5 Automatic No ABL2REM24100

350 14.6 Automatic No ABL 2REM24150


(1) The compatible input voltage DC 110...370 V is not indicated on the product.
(2) The compatible input voltage DC 255…370 V is not indicated on the product.

Schemes
ABL 2REM24015, 24020 ABL 2REM24045, 24065

ABL 2REM24085, 24100, 24150

Presentation: Description: Characteristics: Dimensions, mounting:


page 64 page 64 page 67 page 68 and 69
67
Dimensions, Switch mode power supplies and safety
mounting isolation transformers
ABL2 plate switch mode power supplies

Dimensions and Mounting (the dimensions are in mm)


ABL 2REM24015
Direct mounting is done by 2 M3 screws.

ABL 2REM24020
Direct mounting is done by 2 M3 screws.

ABL 2REM24045
Direct mounting is done by 2 M3 screws.

Presentation: Description: Characteristics: Dimensions, mounting:


page 64 page 64 page 67 page 68 and 69
68
Dimensions, Switch mode power supplies and safety
mounting isolation transformers
ABL2 plate switch mode power supplies

Dimensions and Mounting (the dimensions are in mm)


ABL 2REM24065
Direct mounting is done by 2 M3 screws.

ABL 2REM24085/100/150
Direct mounting is done by 2 M3 screws.

Presentation: Description: Characteristics: Dimensions, mounting: