You are on page 1of 12

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No.

4; August 2014 1735

Pollution Flashover Calculation Model


Based on Characteristics of AC Partial Arc
on Top and Bottom Wet-polluted Dielectric Surfaces
Yawei Li, Hao Yang, Qiaogen Zhang, Xiaolei Yang, Xinzhe Yu
State Key Laboratory of Electrical Insulation and Power Equipment,
School of Electrical Engineering, Xi’an Jiaotong University,
Xi’an, 710049, PR China

and Jun Zhou


China Electric Power Research Institute
Beijing, 100192, PR China

ABSTRACT
A double-arc model, which considers the differences between characteristics of AC
partial arcs on top and bottom surfaces, was proposed for predicting the flashover
voltage of polluted insulators in this paper. The arc constants parameters, the arc re-
ignition criteria, as well as the radii of arc columns in the proposed model were
determined by measuring partial arcs on the top and bottom wet-polluted surfaces of a
triangular glass plate separately. A “ɉ” type glass model was made to investigate the
partial arc propagation process by using an ultra-high speed camera. It has been found
that the arc length increased linearly with leakage current amplitude, the ratio of arc
length increments on top and bottom surface was related to salt deposit density (SDD)
rather than leakage current. Based on above-mentioned researching results, the double
arc calculation model was established, and the calculated results were in good
agreement with the experimental results.
Index Terms — AC partial arc, top and bottom wet-polluted dielectric surfaces,
arc characteristic, pollution flashover calculation.

1 INTRODUCTION In the original work, Obenaus proposed two constants of A and


n to describe the V-I characteristic of partial arc [9]. Around these
POLLUTION flashover of outdoor insulators is one of the major two constants, many researchers obtained different values in
problems for power systems in China and some other countries [1-
various circumstances, such as different voltage types, different
8]. Despite a lot of works have been done for studying the
altitudes and so on [1-4]. Nevertheless, there was a big difference
mechanism and phenomena, pollution flashover faults still occur at
in the values of A and n obtained by different researchers even in
times. The demand of electric power is increasing with
the same experimental condition [11-15].
technological advancements, so the damage caused by pollution
flashover will make heavy loss in the future [1]. Therefore, Rizk proposed that models based on Obenaus’ model should
researches about pollution flashover should be intensified. take the AC partial arc re-ignition criteria into account [9]. Hence,
he deduced the re-ignition criteria by using the dielectric
Obenaus pioneered an electric circuit model of a partial arc in
breakdown theory [9]. Claverie and Pocheron measured the peak
series with a residual pollution layer resistance to present the arc
re-ignition voltage as a function of the leakage current peak value
discharge on the polluted surface of insulators [9]. Based on this
in the previous half-cycle [16]. Otherwise, Guan obtained the
classic model, many researchers have done a lot of experimental
“recovery” criteria by experiments and theoretical derivation [17].
and theoretical works on the mechanism of arc discharge on
polluted insulators [9, 10]. Agreements have been reached that These authors ignored the effects of surrounding circumstance
investigations of partial arc characteristics and residual pollution on the arc column, i.e., heat dissipating condition of arc column
layer resistance are of great importance for arc propagation resulted of floating off the surface. And those data used in
modeling. establishing the empirical expression were obtained when the arc
root was just reached the measuring electrode, at that moment the
arc column was in an unstable state. Moreover, these researchers
Manuscript received on 29 August 2013, in final form 7 March 2014, took it for granted that the arc in different position of the insulator
accepted 15 March 2014. surface had the same V-I characteristic and re-ignition criteria.

DOI 10.1109/TDEI.2014.004291
1736 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc

The differences between cooling conditions of top and bottom of the gap between measuring electrode and ground electrode
wet-polluted dielectric surfaces not only result in discrepancies of was measured by a capacitive voltage divider with a voltage
V-I characteristic and re-ignition criteria of AC partial arcs, but ratio of 1000:1.
also the differences in arc column radius and arc propagation
process.
In this paper, arc characteristics including static V-I
characteristic, re-ignition criteria and column radii of partial
arcs on top surface (AT) and bottom surface (AB) were
investigated respectively. Meanwhile, the radius and the
length of partial arc mentioned above were obtained with
ultra-high speed camera. Based on the acquired results, a
mathematic model was established to calculate the flashover
voltage. It was found that the calculated results were in good
agreement with experimental data.
2 FACILITIES AND PROCEDURES
Figure 2. Triangular glass plate.
2.1 TEST EQUIPMENT
The partial arc experiments were implemented in an A “Ȇ” type glass model was also made to investigate the
artificial climate chamber located in Xi’an Jiaotong University partial arc evolution and the influencing factors on both top
(XJTU). The radius and height of the artificial climate and bottom surfaces, as shown in Figure 3. The copper bar in
chamber located in XJTU are 4 and 5.2 m, respectively. The Figure 3 was used to connect the upper and bottom surfaces of
size and facilities of both chambers meets the requirements for the model. It can be seen in Figure 3 that the contamination
contamination flashover tests. was deposited on the inner side of the glass model. Also, an
ultra-high speed camera RedLake HS-4 was installed to record
the images of arc propagation process horizontally.

Figure 1. Schematic circuit of XJTU chamber.

The experimental circuit model of XJTU chamber is shown Figure 3. “Ȇ” type glass model.
in Figure 1. The test power is generated by a 150 kV/4 A, 600
kVA transformer with short circuit impedance less than 5% (B 2.3 TEST PROCEDURE AND METHOD
in Figure 1). The applied voltage is measured by a capacitive According to the IEC 507 [18], the solid-layer method was
voltage divider with a voltage ratio of 10000:1. The leakage chosen to pollute the specimens before the experiments. The
current is acquired by measuring the voltage of sampling artificial contamination was a mixture of sodium chloride,
resistance in series with the sample (S in Figure 1). All the kaolin and de-ionized water. In this investigation, the SDD
measured signals were recorded by a digital storage were 0.03, 0.05, 0.10 and 0.15 mg/cm2 respectively. And the
oscilloscope of TEK DPO4054. non-soluble deposit density (NSDD) of kaolin kept a constant
2.2 TEST SPECIMENS value of 1 mg/cm2.
The complex geometric shapes of real insulators made it After 24 h natural drying, the specimens were wetted by
difficult to record the images of arc propagation, let alone artificial fog, composition of which was distilled water, until
study the characteristics of partial arc. Hence, a triangular the contamination layer became “saturated” with water. The
glass flat plate was installed to investigate V-I characteristic temperature in the chamber was kept about 30 ºC during the
and re-ignition criteria of AT and AB respectively, as shown whole wetting process.
in Figure 2. After contaminating, the distance between In the partial arc characteristics measuring experiments
measuring electrode and ground electrode was adjusted to conducted on the triangular glass plate and the “Ȇ” type glass
certain value corresponding to desired arc length. The voltage mold, even-raising method [18] was adopted. A low voltage
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 4; August 2014 1737

increase rate of 2 kV/s was employed in the experiments in The applied voltage, the voltage of the gap and the leakage
order to observe the arc propagation more distinctly. current was recorded accurately during the arc propagating
process, as shown in Figure 4. And the arc resistance at the peak
2.4 POLLUTION FLASHOVER TESTS ON
moment is also calculated and given in Fig 4. The ultra-high
INSLATORS
speed camera could be synchronized externally via a trigger
The three types of porcelain insulators were widely used in source in the form of a TTL pulse, which was generated by
Super-high and Ultra-high transmission lines in China. The DG535 and triggered by the oscilloscope. The delay time of the
configurations and parameters of them are shown in Table 1, whole trigger circuit was less than 100 ns. The obtained images
in which H is the structure height, L is the creepage distance, of arc at the peak of positive half cycle of leakage current were
D is the nominal diameter. shown in Figure 5, in which (a) - (h) correspond to the same
Table 1. Characteristics of the insulators (in cm). identification labels marked in Figure 4.
Type CA-590EZ XWP-300 CA-878EY

Configu-
ration

H 19.5 19.5 20.5


L 50.5 49.5 65.0
D 32.0 33.0 40.0
The experiments were implemented in an artificial climate
chamber located UHV Test Base of State Grid Corporation of
China (SGCC), and the dimension of artificial climate
chamber is 12 m × 12 m × 12 m. The schematic circuit of
SGCC was quite similar to the one of XJTU shown in Figure 1.
The test power was a 200 kV/5 A, 1000 kVA transformer. The
applied voltage was measured by a capacitive voltage divider
with a voltage ratio of 1000:1.
Figure 4. Calculated arc resistance, ra; applied voltage, um; voltage of the gap,
In the tests, up-and-down method [18] was adopted to ua; and leakage current, i.
acquire the 50% flashover voltage, U50%. More than ten valid As shown in Figures 4 and 5, after the arc reached the
data were obtained in the same condition, and U50% can be measuring electrode (shown in Figure 2), the gap between the
expressed as: measuring electrode and ground electrode was entirely bridged
by arc and the voltage of gap declines smoothly. It could be
U 50%
¦n uu i i
(1) concluded from Figure 5 that the radius and brightness of arc
N column increased till reaching a stable state with the increase
Where, ui is an applied voltage, kV; ni is the number of the of leakage current. At the stable moment, which was marked
tests at the voltage of ui; N is the number of valid tests, N • 10. with dotted line in Figure 4 and corresponding to the image of
Figure 5d, the leakage current amplitude value reached
2.5 MEASUREMENT OF ARC CHARACTERISTICS maximum Im (in A) and the voltage amplitude of the gap was
In the partial arc characteristic experiments conducted on minimum Ua (in V). After the stable state, arc levitation
the triangular glass plate, the arc initiated near the ground caused by thermal buoyancy was about to take place, as shown
electrode due to the high electric field strength. With the in Figure 4e. With the arc column elongated by the thermal
increase of applied voltage, the arc elongated. buoyancy continuously, the arc resistance increased and the

(a) (b) (c) (d)

(e) (f ) (g) (h)


Figure 5. Images of partial arc (the length of the gap is 5 cm).
1738 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc

leakage current value decreased till the partial arc could not be Table 2. Arc constants obtained by other researchers.
sustained and then draw back. Consuming resistivity of the arc Type of medium A n
state shown in Fig 5d was lowest, which means that the heat Polluted surface [19] 63 0.5
Air gap [20] 100.25 0.66
loss of arc was minimum, and the arc column press to the
Inside snow [20] 826 0.36
surface closely. Polluted surface [19] 40-50 0.83
Figure 6a is the waveforms of voltage and leakage current Ice surface [21] 168 0.325
of the partial arc in a single period. In the figure, i is leakage Ice surface[22] 204.7 0.5607
current; u is voltage drop of arc channel; t is time. The 1/4 Table 3. Arc re-ignition constants.
period of leakage current waveform between A and B Type of medium K b
corresponds to the process that the arc evolves gradually from Polluted surface [16, 23] 940 0.5
re-ignition to steady state; the next 1/4 period between B and Polluted surface [9, 24] 2080 1
C corresponds to the arc extinction process, and the part Polluted surface [17, 25, 26] 531/1050 1
between C and D corresponds to the arc zero-current area. If Inside snow [20] 6370 0.49
the voltage increase again, the primary arc channel will be Ice surface [22] 1118/1300 0.5277
breakdown again, the corresponding u and i waveforms
changing process is shown between Bƍ and B, the leakage According to Tables 2 and 3, it can be concluded that the
current increases as sine wave, and the voltage decreases arc characteristics are susceptible to thermal environments,
rapidly. Therefore, Figure 6a reflects the re-ignition and different surrounding medium corresponding to different arc
extinction process of the partial arc, which is used to characteristics. Thermal buoyancy results in the AT drifting
determine whether the arc is re-ignited. away from the top surface, and the AB close to the surface,
this phenomenon make the heat dissipation of AT and AB
300
10
different, so there must be some significant differences
i between the arc characteristics between AT and AB.
200 u
5
With the same thermal environment, different researchers
100 got different arc characteristics, and this is because all these
D results were obtained by measuring the voltage and current at
i(mA)

u(kV)

0 0
A B' B C the moment that the arc root just reached the measurement
-100 electrode. However, it must take some time for the arc
-5 converts from unsteady state to steady state, so the above
-200 results are the dynamic arc characteristics corresponding to
-10 different unsteady instant, and this is why different researchers
-300
0 5 10 15 20 got different results with the same measuring method.
t(ms)
Figure 6a. Waveforms of voltage and leakage current of partial arc in a single
Therefore, the method that measuring the static arc
period. characteristics of AT and AB on top and bottom surfaces of
triangular glass flat plate separately is according to practice.
In conclusion, V-I characteristics of this moment was the And the measuring method, which chooses the leakage current
static V-I characteristics of the arc. Many researchers proposed on the maximum peak value Im, the corresponding arc voltage
that the arc column propagating on the insulator surface was in drop Ua, and the peak value of applied voltage on the next half
a quasi-equilibrium state, in this situation the input energy was period Um, as the valid data of a test, and then, the expressions
consumed by ionization inside the arc column rather than the of V-I characteristic and re-ignition criteria can be obtained by
streamer initiation in front of the arc roots. So that the V-I regression analyzing abundant valid data. The method is
characteristics of ac arc in stable state can describe the arc shown in Figures 5 and 6a, which can decrease the dispersion
propagating on the real insulator more accurately. The mean of the results. A more accurate static arc characteristic
electric strength Ea (in V/cm) of the arc can be expressed as: contribute to calculate the flashover voltage of insulator more
Ua precisely, because that the input energy is tend to promote the
Ea AI m n (2)
ionization inside the arc channel to make the arc steady, rather
x
than accelerating the arc root propagation before the arc
where, x is the length of the arc, cm; A and n are arc constants. reaches the steady state.
As mentioned in previous work [9, 10, 17], the arc re-ignition
criteria was also considered in this paper: 3 CHARACTERISTICS OF PARTIAL ARCS
Um KxI m-b (3)
3.1 STATIC V-I CHARACTERISTICS
where, Um is peak voltage in previous half-cycle of point d, as In order to determine the static V-I characteristic of AT and
shown in Fig 4, V; K and b are re-ignition constants. AB, a large number of tests were carried out on the
Some of previous research results about A, n and K, b are contaminated triangular glass plate. Two arc lengths (5 cm and
shown in Tables 2 and 3, respectivly: 10 cm) were chosen to be tested.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 4; August 2014 1739

The results corresponding to arc characteristics of AT and AT


1000
AB are presented in Figure 6b. The arc constants, A and n, are AB
determined by adopting regression analysis. 800 Rahal
Guan
The V-I characteristics of AT and AB can be expressed as

E a(V/cm)
600 Ghosh
follows:
400
Eat 112.1I m0.82 (4)
200
Eab 65.8I m1.13 (5)
where, Eat and Eab are the mean electric strength of AT and 0
0.0 0.5 1.0 1.5 2.0
AB, V/cm. I(A)
Figure 8. The comparison of the V-I characteristics of AC arc obtained.
by ,other researchers as well as obtained in this paper.
800
x=5cm
700
x=10cm It can be concluded that the V-I characteristic curve
600 Fitting curve
obtained in this paper is lower than other researchers’ results
Eat(V/cm)

500
[27-29]. It is caused by differences in the selecting criterions
400
of valid data. The peak values of the cycle in which the arc
300 reached the measuring electrode were adopted as valid data in
200 literature [15, 17]. As mentioned above, the arc column will
100 come to the stable state a while after it reaches the measuring
0.0 0.2 0.4
Im(A)
0.6 0.8 1.0 electrode.
(a) V-I characteristic of AT 3.2 RE-IGNITION CRITERIA
1200
x=5cm As mentioned previously, the arc re-ignition criteria can be
1000 x=10cm expressed by equation (3). A large number of tests were
Fitting curve
800 carried out in order to obtain the re-ignition constants k and b
E ab(V/cm)

600 of partial arcs on both top and bottom wet contamination


surface. The experimental results and fitting curve are shown
400
in Figure 9.
200
3
6x10
0 x=5cm
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 3
Im(A) 5x10 x=10cm
3 Fitting curve
(b) V-I characteristic of AB 4x10
Em(V/cm)

Figure 6b. V-I characteristics of AT and AB. 3


3x10
3
The values of A and n measured by different researchers 2x10
vary over a wide range for different types of arcs, which is 1x10
3

caused by the difference of propagation medium [2, 3, 9, 15- 0


17]. As for differences in V-I characteristics of AT and AB, 0.0 0.2 0.4 0.6 0.8
Im(A)
even though the propagation medium is the same, the shapes (a) Re-ignition criteria of AT
of AT and AB are different, as shown in Figure 7. 4
1.2x10
x=5cm
4
1.0x10 x=10cm
3 Fitting curve
8.0x10
Em(V/cm)

3
6.0x10
3
4.0x10
3
2.0x10
0.0
Figure 7. The section diagram of top and bottom partial arc. 0.0 0.3 0.6 0.9 1.2 1.5 1.8
Im(A)
It is well known that the direction of thermal buoyancy is (b) Re-ignition criteria of AB
straight up, so that AB clings to the glass surface compared Figure 9. Re-ignition criteria of AT and AB.
with AT. The differences of thermal conductivity of air and
glass result in the differences in V-I characteristics. It can be concluded that from Figure 9 there is a difference
A comparison of V-I characteristics of ac arc obtained by between the re-ignition criteria of partial arcs on top and
other researchers as well as obtained in this paper is shown in bottom surfaces to some extent. The arc re-ignition constants,
Figure 8. K and b, were determined by using the regression analysis.
1740 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc

The re-ignition criteria of partial arcs on top and bottom than AT in the same leakage current peak value. The “cold
surfaces can be expressed as follows: wall effect” acting on AB is much stronger than on AT, by
adopting the points mentioned in literature [30], which results
U mt t 701.5 xt I m1.00 (6)
in the thinner AB. The calculation result proposed by Wilkins
0.86
Umb t 878.6x I b m (7) is very close to the radius of AT, as shown in Figure 11, which
where, Umt and Umb are re-ignition voltage for AT and AB, means that Wilkins only took the heat dissipation condition of
V/cm. xt and xb are the length of AT and AB, cm. AT into consideration in his original works.
A comparison of arc re-ignition criteria of AT and AB is 0.6
rt
shown in Fig 10. In which, Em=Um/x. If leakage current value 0.5
rb
is larger than 0.2 A, the re-ignition voltage in per unit length Wilkins
0.4
of AT is smaller than that of AB at the same current values.

r(cm)
As mentioned in Section 3.1, AB has a better heat dissipation 0.3
condition than the one on top surface, thus the dielectric
0.2
performance of bottom surface recover better than that of top
surface when leakage current crossing zero, so higher voltage 0.1
is necessary for arc re-ignition on bottom surface compare 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
Im(A)
with the one on top surface [30, 31].
Figure 11. The arc column radii of AT and AB and the calculated result
8 proposed by Wilkins.
AT
7
AB The fitting curves are obtained by adopting the regression
6
5
analysis. The radius of AT and AB can be expressed as
E m (kV/cm)

4
follows:
3 rt 0.51I m0.57 (8)
2 rb 0.62I 0.47
m
(9)
1
0 3.4 PROPAGATION PROCESSES
0.0 0.5 1.0 1.5 2.0
Im(A) The “Ȇ” type glass model was used to investigate the length
Figure 10. The comparison of arc re-ignition criteria of AT and AB. changing of AT and AB with different SDD of contamination
layer, as shown in Figure 3. The ultra-high speed camera with
3.3 COLUMN RADII 1000 fps was implemented to record the arc propagation
The column radii of AT and AB were also investigated in process, as shown in Figure 12. In all the images of Figure 12,
this paper. The obtained results and the calculated result the upper arc column propagates on the bottom surface of the
proposed by Wilkins [32] are shown in Figure 11. The glass plate and the down arc propagates on the top surface of
symbols rt (in cm) and rb (in cm) represent the radius of AT the glass. The arc length varies with leakage current peak
and AB respectively, and r is the arc column radius. It can be value in different SDD is shown in Figure 13. It can be
concluded from Figure 11 that the arc column radius increases concluded that the length of AT and AB change with leakage
with leakage current peak value, and the radius of AB is less current peak almost linearly.

(a) 0ms (b) 20ms (c) 40ms (d) 140ms

(e) 200ms (f) 220ms (g) 225ms (h) 226ms


Figure 12. The section diagram of top and bottom arc.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 4; August 2014 1741
50 50
xt xt
40 xb 40 xb

30 30

x/cm
x/cm
20 20

10
10

0
0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Im/A Im/A
2 2
(a) ȡSDD=0.03mg/cm (b) ȡSDD=0.05mg/cm
50 50
xt xt
40 xb 40 xb

30 30

x/cm
x/cm

20
20

10
10
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 0.2 0.4 0.6 0.8 1.0 1.2 1.4
Im/A Im/A
(c) ȡSDD=0.10mg/cm2 (d) ȡSDD=0.15mg/cm2
Figure 13. The length of AT and AB varies with leakage current peak value.

The relationship between arc root propagation speed and the There are rarely any researches about the propagation speed
electric field strength was studied by many researchers [33-38], of arc root so far, but the present researches indicate that the
and the propagation speed of arc root caused by the traction of arc length increases linearly with leakage current increasing
electrostatic force was obtained [34, 37 , 39, 40].
3H 0 E 2 l Because the length of AT and AB vary with leakage current
v (10) almost linearly, the ratio of AT increment ǻxt to AB increment
4S r U
ǻxb for the same increment of Im is shown in Figure 14.
where, İ0 is permittivity of vacuum, E is the electric field The parameter k was designed to stand for the ratio of ǻxb to ǻxt:
strength in front of the arc root, l is the arc length, Then, take
the relationship I g E 2 l [34] into consideration, we can get k ' xb ' x t (16)

12 Experimental result
3H 0 I (11)
v Fitting curve
4S g U r
9
where, g is a parameter about electron mobility, ȝ [34]
6
k

g 2S H 0 P (12)
Hence, the propagation speed of arc root can be expressed as 3

1 3I (13)
v 0
2S 2 UP r 0.04 0.08 2
0.12 0.16
USDD(mg/cm )
Take the difference between arc column radius of AT and Figure 14. Ratio of AB increment ǻxb to AT increment ǻxt.
AB into consideration, the arc root propagation speed of AT By using the regression analysis, k is expressed as follows:
and AB can be expressed as follow separately 1.32
k 0.12 USDD (17)
1 3I (14)
vt where, USDD is the SDD, mg/cm . The fitting correlation 2
2S 2 U P rt
coefficient R2 is 0.94, which means the fitting curve is in good
agreement with the obtained values from the tests.
1 3I (15)
vb
2S 2 U P rb
4 MODELING OF POLLUTION FLASHOVER
So it is clear that vt ˘ vb, duo to the relationship rt ˚ rb. 4.1 EFFECTIVE CREEPAGE DISTANCE OF
Therefore, it is easy to understand that the length of AB is INSULATOR
longer than that of AT corresponding to the same leakage During the contamination flashover process of real
current. insulator strings, it can be obviously investigated that the
1742 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc

propagation speed of arc on bottom surface is faster than


that on top surface, and the radius of AT is bigger than that
of AB. however, the partial arcs don’t always propagate
along the surface because of the complicated insulator
surface; there are some parts of arcs bridge the adjacent
sheds, this phenomenon is shown in Fig 15 and Fig 16. The
arc bridging phenomenon short some parts of the creepage
distance, leads to the flashover voltage decrease. So it is
significant that the arc bridging phenomenon should be Figure 17. Schematic diagram of effective creepage distance.
taken into consideration in the pollution flashover
where, x1 and x2 are the partial arcs of insulator surface at the
calculation, otherwise, the calculating result will has large
moment of pre-flashover, so the critical arc length xc can be
error.
expressed as follows:
xc x1  x2 (18)
And the effective creepage distance Le can be expressed as
Le xc  Lr (19)
The experiments, analysis and theoretical derivation for
establishing the calculation method of Le has been fully
detailed in another literature [40], and the Le calculating
empirical equation of outer-rib type and under-rib type
insulators are given separately by
c
0.072 § S De ·
(a) Real process
Le 0.147
(1.161USDD  0.352G CF USDD )¨ ¸ L (20)
© d0 ¹
c
0.211 § S De ·
0.384 (21)
Le (0.805 U SDD
 0.119G CF U )¨SDD ¸ L
© d0 ¹
where, įCF is the creepage factor of the insulator string; De is the
equivalent diameter of insulator, cm; c is constant, c=0.60; d0 is the
ideal rectangular pollution layer surface, which creepage distance is
(b) Schematic diagram fully utilized, in above-mentioned two equations, d0=10cm. the
Figure 15. the propagating process of partial arcs on the surface of XWP-300 effective creepage distances of both under-rib type and outer-rib
insulator with the SDD value 0.08 mg/cm2. type insulators can be calculated by equations (16) and (17).
4.2 RESIDUAL CONTAMINATION RESISTANCE
Wilkins proposed a function to calculate the residual
contamination resistance by adopting the method of images
[32]. However, his equation is too complicated to be used in
the calculation. Guan [28] obtained residual contamination
resistance by adopting electric axis method, and the equation
is expressed as follows:
(a) Real process 1 Lx (22)
R x ln
SJ e r0
Je is expressed as:
J e 1.25J (23)
where, Je is surface conductivity at the critical moment; Jis the
surface conductivity obtained with normal method. The
relationship between Jand ȡSDD was given in literature [41]:
(b) Schematic diagram
Figure 16. The propagating process of partial arcs on the surface of CA-
J 369.05USDD  0.42 u106 (24)
590EZ insulator with the SDD value 0.03 mg/cm2. Equation (22) was widely used in the calculation of residual
contamination, but it assumed that the arc radius was the same
In order to represent the phenomenon that the flashover on different position of insulators, which was not
voltage of insulator doesn’t increase linearly with its creepage correspondent to the fact. Considered of the radius difference
distance increasing, the conception “effective creepage of AT and AB, the residual contamination resistance is
distance” was proposed, and it can be descript as follows: calculated by adopting electric axis method in this paper.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 4; August 2014 1743

For modeling of two ac arc columns propagation, the arc re-


ignition criteria should be considered:
U m t K t xt I mbt (30)
U m t K b xb I mbb (31)
where, Kt and bt are arc re-ignition constants of AT; kb and bb
are arc re-ignition constants of AT. In the critical case of AC
arc re-ignition criteria, equations (30) and (31) is rewritten as
Figure 18. Schematic diagram of electric axis method [17]. follows:
As shown in Fig 18, the two circular electrodes represent Um K t xt I m bt  K b xb I m bb (32)
AT and BT, in addition, -Wand +W represent two charged thin
As mentioned in Section 3.4, the relationship between xt
wires with charge linear density of W. The distance D between
and xb can be expressed as follows:
the two circle centers is the length of residual contamination.
According to literature [17], the potential difference Mtb xb kxt (33)
between A and B can be obtained:
Without this relationshipˈthe critical values of xt and xb
M tb
W
ln
b  h1  rt b  h2  rd (25) cannot be determined by equation (29).
2SJ e b  h1  rt b  h2  rd In conclusion, the double-arc model can be re-write as
Thus, the resistance between the two small circular follow:
electrodes can be expressed as follows: ­U m At xt I m nt  Ab xb I m nb  I m R xt , xb
° (34)
R
Mtb 1
ln
b  h1  rt b  h2  rb (26)
® U m K t xt I m bt  K b xb I m bb
°
W 2SJ e b  h1  rt b  h2  rb ¯ xt kxb
Because rt << b and rb << b, thus,
b  h1  h2 (27) 4.4 CALCULATION METHOD OF DOUBLE-ARC
Equation (26) can be rewritten as follows: MODEL
1 ( L  x t  xb ) 2 4.4.1 SOLUTION OF DOUBLE-ARC MODEL
R x t , xb ln (28)
2SJ e rt rb Equation (34) contains transcendental equations, so it is
difficult to solve the equations directly. Therefore, the double-
4.3 DOUBLE-ARC MODEL arc model should be deduced so as to calculate the flashover
Many researchers have confirmed that the contamination voltage of various types of insulators conveniently.
flashover voltage of insulators can be predicted by adopting
Plug equation (28) into equation (29), and then take the
mathematical models based on Obenaus model [9].
derivative of (29) with respect to Im, and set derivative equals
Considered of the differences in the characteristics of AT and
constant, the following relationship can be obtained:
AB mentioned above, an AC double-arc mathematical model
was established in this paper. The model is shown in Figure 19, 0.547
R xt , xb nt At xt I m nt 1  nb Ab xb I m nb 1 + (35)
and the corresponding equation is expressed as follows: SJ e
Um At xt I m nt  Ab xb I m nb  I m R xt , xb (29) In case of xt and xb are known, the value of Im that satisfies the
relationship (35) is the critical leakage current of flashover,
and assume that the critical value is In. Plug Im=In and
equations (28), (35) into (29), and then take the derivative of
(29) with respect to xt and xd respectively, we can obtain
wU m In
At I n n t  (36)
wxt SJ e Le  x t  x b
wU m In
Ab I n n b  (37)
Figure 19. AC double-arc model. wxb SJ e L e  x t  x b
where, Um is the peak value of applied voltage, V; Im is the
Sets wU m wU m 0 , we can get the following relationship by
peak value of leakage current, A; At and nt are the arc wxt wxb
constants of AT; Ab and nb are the static arc constants of AB;
equations (36) and (37):
xt and xb are the length of AT and AB, cm; R (xt, xb) is the 1
residual contamination resistance, :. In this model, creepage ª At nb 1 º nt  nb
distance L is replaced by effective creepage distance, taking Le  xb  xt SJ e « nt 1 » (38)
the arc bridge on the insulator surface into consideration. ¬ Ab ¼
1744 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc

Therefore, the double-arc model can be represented by the glass model and 3 types of suspension insulators. Then the
following equations: results were compared with experimental ones.
Based on the analysis and deduction of double-arc model, a
­U m K t xt I mmt  K b xb I mmb
° MatlabTM program was used for calculating the flashover
° R x , x n A x I  nt 1  n A x I  nb 1 + 0.547 criteria of the specimens. The flashover voltage of the “Ȇ”
t b t t t m b b b m
° SJ e type glass model and U50% of the three types of insulators were
°
® 1 (39) carried out experimentally. The parameters of the insulators
° ª At nb 1 º nt  nb have been provide in Table 1, and the 50% flashover
° Le  xb  xt SJ e « nt 1 »
° ¬ Ab ¼ experimental method was also been proposed in section 2.4.
°¯ xb E xt The comparisons between the experimental result, the
calculated results and the result of model proposed by Guan et
4.4.2 CALCULATING FLOW al [17] are shown in Figure 21. It can be concluded that the
For the aim of calculating the contamination AC flashover calculated results of double-arc model are in good agreement
voltage of insulator, there are several aspects: firstly, calculate the with the experimental data, and the results of double-arc
effective creepage distance Le on the basis of the parameters model is more accurate than that of Guan’s classic model in
including SDD, equivalent diameter De, creepage factor ; secondly, terms of calculating the flashover voltage of insulators.
calculate the ratio between the arc lengths on top and bottom Therefore, the double-arc model is available for practical
surface, ȕ; and then calculate the critical lengths of AT and AB and engineering design.
critical leakage current; finally, calculate the flashover voltage on
the basis of critical arc lengths and critical leakage current. Figure
20 is the calculation flow chart of double arc model:

ȡSDD(mg/cm2) ȡSDD(mg/cm2)
1.32 L dl 6
E 0.12 U SDD De = 2 L ³ J e 1.25
˄369.05 USDD  0.042˅<10 “Ȇ” type glass mold CA-590EZ
0 r (l )

c
­
0.211 0.384 § S De ·
°(0.805 USDD  0.119G CF USDD )¨ ¸ L(under-rib)
° d
© 0 ¹
Le ® c
° 0.147 0.072 § S De ·
°(1.161USDD  0.352G CF USDD ) ¨ ¸ L(outer-rib)
¯ © d0 ¹

ȡSDD(mg/cm2) ȡSDD(mg/cm2)

ª A n 1 º n  n
b t
1
b
XWP-300 CA-878EY
Le  xb  xt SJ e « t n 1 » Figure 21. The comparisons between the tested data, the calculated results
¬ Ab ¼
t

and the result of the model proposed by Guan.

6 CONCLUSIONS
A mathematical was established to calculate the pollution
flashover voltage of insulators. The experimental investigation
made it possible to determine the static arc constants and the
0.547
R xt , xb nt At xt I m  nt 1  nb Ab xb I m  nb 1 + arc re-ignition constants to model the AC arc discharge on
SJ e
wet-polluted surfaces. From the results obtained the following
conclusions may be drawn:
Um M t xt I mmt  M b xb I mmb 1) The re-ignition and static V-I constants of an arc
propagating on top wet-polluted dielectric surface are
different from those obtained for an arc propagating on
bottom wet-polluted dielectric surface; with the same
Figure 20. Calculation flow chart of double arc model.
leakage current and the same arc length, the voltage
gradient of the arc on top wet-polluted surface is bigger
5 VALIDATION OF THE MODEL than that on bottom surface; The re-ignition voltage of arc
In order to validate the double-arc model on the flashover on top surface is smaller than that of arc on bottom
voltage of insulators, the model was applied to the “ɉ” type surface.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 4; August 2014 1745

2) Arc column radius increase with the leakage [17] Z. Guan and R. Zhang, “Analysis of the flashover criterion of polluted
insulator under AC voltage”, J. Tsinghua University, Vol. 26, pp. 30-39,
current increasing exponentially; with the same leakage 1986 (in Chinese).
current, arc column radius on top surface are bigger than [18] IEC 60507, “Artificial pollution tests on HV insulators to be used on
that on bottom surface. AC System”, 1991.
[19] Z. Guan, Insulator and external insulation of transmission and
3) Partial arc lengths increase linearly with the distribution equipment, Tsinghua University Press, Beijing, 2006 (in
leakage current increasing, but the increments Chinese).
corresponding to the same leakage current increment are [20] H. Hemmatjou, M. Farzaneh and I. Fofana, “Modeling of the AC arc
different between the arc propagating on the top surface discharge on snow-covered insulators”, IEEE Trans. Dielectr. Electr.
Insul., Vol.14, pp.1390-1400, 2006
and on the bottom surface, the ratio between them is only [21] Y. Sabri, M. Farzaneh and J. Zhang, “Arc characteristics of polluted
relate to SDD. insulators covered with ice”, IEEE Conf. Electr. Insul. Dielectr.
Phenomena, Chicoutimi, Canada, pp.437-440, 2006.
4) Based on the result of researches in this paper, a
[22] M. Farzaneh and J. Zhang, “A Multi-arc model for predicting AC
double-arc model was established for pollution flashover critical flashover voltage of ice-covered insulators”, IEEE Trans.
calculation. The comparison result indicates that it is Dielectr. Electr. Insul., Vol. 14, pp.1401-1409, 2007
effective to calculate the 50% flashover voltage of under- [23] P Claverie and Y Porchero, “How to choose insulators for polluted
areas”, IEEE Trans. Power App. Syst., Vol. 92, pp.1121-1131, 1973.
rib, two-outer-rib and three-outer-rib type insulators. [24] F. A. M. Rizk, “Analysis of dielectric recovery with reference to dry-
zone arcs on polluted insulators”, IEEE Conf. Paper, PWR, Winter
REFERENCES [25]
Power Meeting, New York. pp.135-138, 1971.
Z. Guan and R. Zhang, “Calculation of dc and ac flashover voltage of
[1] Z. Zhang, X. Jiang, J. Hu and C. Sun, “Characteristic of DC arc under polluted insulator”, IEEE Trans. Electr. Insul., Vol. 25, pp.723-729,
low air pressure”, High Voltage Engineering, Vol. 35, pp.790-797, 1990.
2009 (in Chinese). [26] Z. Guan and R. Zhang, “Calculation of flashover voltage of polluted
[2] Z. Guan, B. Long, F. Zhang, S. Mao, L. Wang, H. Wen and Y. Ma, insulators under DC and AC voltages”, IEEE 2nd Int’l. Conf. Properties
“Flashover performance of different suspension styles of insulators in Applications of Properties and Applications of Dielectr. Materials,
high altitude”, High Voltage Engineering, Vol. 33, pp.1-6, 2007 (in Beijing, China, pp. 229-232, 1988.
Chinese). [27] M. Rahal and C. Huraux, “Flashover mechanism of high voltage
[3] F. Zhang, L. Wang, Z. Guan, X. Wang, Z. Liu, H. Wen and Y. Ma, insulators”, IEEE Trans. Power App. Syst., Vol. 98, pp.2223-2231,
“External insulation characteristic of ultra-high voltage transmission 1979.
line in high altitude area”, High Voltage Engineering, Vol. 34, pp.1089- [28] Z. Guan and R. Zhang, “Calculation of dc and ac flashover voltage of
1095, 2008 (in Chinese). polluted insulator”, IEEE Trans. Electr. Insul., Vol. 25, pp. 723-729,
[4] Z. Zhang, X. Jiang and C. Sun, “Present situation and prospect of 1990.
research on flashover characteristics of polluted insulators”, Power [29] S. Ghosh and N. Chatterjee, “Polluted insulator flashover model for ac
System Technology, Vol. 30, pp. 35-40, 2006 (in Chinese). voltage”, IEEE Trans. Dielectr. Electr. Insul.,Vol. 2, pp.128-136, 1995.
[5] L. Li, X. Jiang and C. Sun, “Study on pollution flashover performance [30] Z. Guo and W. Zhao, Arc and Thermal Plasma, Science Press, Beijing,
of short sample of ±800 kV UHV DC composite insulators”, Proc. 1986 (in Chinese).
Chinese Soc. Electr. Eng., Vol. 27, pp.14-19, 2007 (in Chinese). [31] Q. Wang, Theory of Arc in Electric Equipment, Shanghai science and
[6] Z. Su, “To intensify basic external insulation level of power system- Technology Press, Shanghai, 1963 (in Chinese).
fundamental way for prevention of large-scale pollution flashover”, [32] R. Wilkins, “Flashover voltage of high-voltage insulators with uniform
Electric Power, Vol. 36, pp.57-61, 2003 (in Chinese). surface-pollution films”, IEE Proc.-Electr. Power Applications, Vol.
[7] Z. Liu, “Analysis of fog flashover faults in east China power system at 116, pp.457-465, 1969.
the end of 1996 and its countermeasures”, Power Syst. Techn., Vol.21, [33] Fushun Guo, Study on the streamer characteristics along the polluted
pp. 63-66, 1997 (in Chinese). insulation surface and the development arc energy balance model
[8] Q. Li, Z. Fan, Q. Wu, J. Gao, Z. Su and W. Zhou, “Investigation of ice- under DC voltage, Ph. D. thesis, Chongqing University, 2012.
covered transmission lines and analysis on transmission line failures [34] R. T. Waters, A. Haddad, H. Griffiths, N. Harid and P. Sarkar, “Partial-
caused by ice-coating in China”, Power Syst. Techn., Vol. 32, pp. 33- arc and spark models of the flashover of lightly polluted insulators”,
36, 2008 (in Chinese). IEEE Trans. Dielectr. Electr. Insul., Vol. 17, pp. 417-424, 2010.
[9] F. A. M. Rizk, “Mathematical models for pollution flashover”, Electra, [35] L. Fulcheri, J. D. Rollier and J. Gonzalez-Aguilar, “Design and
Vol.78, pp.71-75, 1981. electrical characterization of a low current-high voltage compact arc
[10] F. A. M. Rizk and Q. Rezazada, “Modeling of altitude effects on AC plasma torch”, Plasma Sources Sci. Techn., Vol. 16, pp.183-192, 2007.
flashover of polluted high voltage insulators”, IEEE Trans. Power [36] M. S. Benilov, “Understanding and modeling plasma-electrode
Delivery, Vol. 12, pp. 810-822, 1997. interaction in high-pressure arc discharges: a review”, J. Phys. D: Appl.
[11] I. Bergman and I. Kolobova, “Some results of investigation of the Phys., Vol. 41, pp. 1-30, 2008.
dielectric strength studies of contaminated line insulation under lower [37] T. M. P. Briels, J. Kos, G. J. J. Winands, E. M. van Veldhuizen, and U.
air pressure conditions”, Elektrotekhnika, Vol. 54, pp. 14-18, 1983. Ebert, “Positive and negative streamers in ambient air: measuring
[12] T. Kawamura, “Pressure dependence of DC breakdown of diameter, velocity and dissipated energy”, J. Phys. D: Appl. Phys., Vol.
contaminated insulators”, IEEE Trans. Dielectr. Electr. Insul., Vol. 25, 41, pp. 1-11, 2008.
pp. 1125-1137, 1990. [38] J. Li, Z. Guan, L. Wang, and H. Yang, “An experimental study of AC
[13] M. Ishii, and K. Shimada, “Flashover of contaminated surface under arc propagation over a contaminated surface”, IEEE Trans. Dielectr.
low atmospheric pressure”, 4th Int’l. Sympos. High Voltage Eng., Electr. Insul., Vol. 19, pp. 1360-1368, 2012.
Athens, Greece, pp.1275-1278, 1983. [39] S. Li, The Mechanism of the Flashover on a Polluted Dielectric Surface
[14] R. Zhang and J. Zheng, “Progress in outdoor insulation research in under AC Voltage, Ph.D. thesis, Tsinghua University, 1988 (in
China”, IEEE Trans. Dielectr. Electr. Insul., Vol. 25, pp. 1125-1137, Chinese).
1990. [40] Y. Li, AC Partial Arc and Flashover Characteristics of Contaminated
[15] M. Farzaneh, J. Zhang and Y. Li, “Effects of low air pressure onAC Insulator Strings under Saturation Humidity Condition, Ph.D. thesis,
and DC arc propagation on ice surface”, IEEE Trans. Dielectr. Electr. Xi’an Jiaotong University, 2014 (in Chinese).
Insul., Vol. 12, pp. 60-71, 2005. [41] V. Topalis, F. Gonosˈand A. Stathopulos, “Dielectric behaviour of
[16] P. Claverie, “Predetermination of the behavior of polluted insulators”, polluted porcelain insulators”, IEE Generation Transmission
IEEE Trans. Power App. Syst., Vol. 90, pp. 1902-1908, 1971. Distribution, Vol. 148, pp. 269-274, 2001.
1746 Y. Li et al.: Pollution Flashover Calculation Model Based on Characteristics of AC Partial Arc
Yawei Li was born in Henan Province, China in Xiaolei Yang was born in Sichuan Province, China,
1980. He received the B.Sc. and M.Sc. degrees from in 1988. He received the B.Sc. degree in electrical
the School of Material Engineering, Henan University engineering from Xi’an Jiaotong University, Xi’an,
of Science and Technology and School of Electrical China, in 2012. He is currently working toward a
Engineering, Sichuan University, China, in 2004 and M.Sc. degree at the High Voltage Division, School of
2007 respectively. He is currently working toward a Electrical Engineering, Xi’an Jiaotong University.
Ph.D. degree at High Voltage Division, School of
Electrical Engineering, Xi’an Jiaotong University.
His major research interests include outdoor
insulation.

Hao Yang was born in Hebei Province, China in Xinzhe Yu was born in Tianjin, China, in 1983. He
1988. He received the B.Sc. degree from the School received the B.Sc. and M.Sc. degrees in electrical
of Electrical Engineering, Xi’an Jiaotong University, engineering from Xi’an Jiaotong University, Xi’an,
China, in 2011. He is currently working toward the China, in 2008 and 2011, respectively. He is currently
Ph.D. degree at High Voltage Division, School of working toward a Ph. D degree at High Voltage
Electrical Engineering, Xi’an Jiaotong University. His Division, School
major research interests include outdoor insulation.

Qiaogen Zhang was born in Jiangsu Province, Jun Zhou was born in Jiangsu province of China in
China, in 1965. He received the B.Sc., M.Sc., and 1973. He received the Ph.D. degree from Tsinghua
Ph.D. degrees from Xi’an Jiaotong University, Xi’an, University, China in 2004. After graduation, he
China, in 1988, 1991, and 1996, respectively. He is worked in China Electric Power Research Institute.
currently a professor with the State Key Laboratory His major research field is external insulation,
of Electrical Insulation and Power Equipment, especially in UHV areas.
School of Electrical Engineering, Xi’an Jiaotong
University. His major research interests include
outdoor insulation, pulse power technology, gas
discharge and its application.

You might also like