a.

Minimum air rate at Tl2 = 110 oF of Hy2 = 84,3 is need of operation line

Equation (10.5-2)

G (Hy2 – Hy1) = L. Cl (Tl2 – Tl1) Where Cl = 1 btu/lbm OF

G (84,3 – 30,85) = 2000. 1. (110 – 85)

G 53,45 = 50000

G = 935 lbm air / h.ft2

b. Tower height needed if the air flow 0f 1400 lbm air/h.ft2

Use operating G = 1400

G (Hy2 – 30,8) = 2000 (1) (110 – 85)

1400 (Hy2 – 30,85) = 50000

1400 Hy2 – 43120 = 50000

Hy2 = 66,5