Roof Extract Units

50 Hz - Direct Driven

1
2
Contents
Air movement technology is a world of specialised knowledge and one in which Woods Air Movement Limited are not just the specialists
but the acknowledged leaders. Woods extensive knowledge of designs and applications extends back over 90 years of experience as one
of the world’s largest manufacturers of fans and air moving equipment.

Based in Colchester, in the U.K., Woods have extensive laboratories that constantly develop new concepts and product ranges, enabling
the company to maintain its market leadership. In addition Woods have three sales centres in the U.K. together with subsidiary companies
in Italy, Germany, Finland, France, Singapore the U.S.A. and Canada plus, a network of fully trained local staff in 70 different countries
with intimate knowledge of local needs.

In fact Woods products are marketed and installed in over 100 countries, with applications ranging from the world’s largest engineering
projects to the smallest poultry houses.

Whatever the product size or cost it is Woods policy to provide the highest quality at competitive prices, all backed by dedicated staff, fully
trained to provide customer satisfaction.

Woods Air Movement Limited is a BS EN ISO 9001:94 Registered Company.

In line with the Company’s strict adherence to the highest quality assurance standards, regular quality audits occur ensuring that Woods
products consistently meet the catalogue specifications.

For more information, please visit our website on www.woods-fans.com

Products Page:

CDX Series side or vertical discharge


- General Information 4
- Performance data 5-6
- Ancillaries 7-8
Speed Controllers 8
Colchester Range
- General Information 9-10
- Side Discharge - Details & Performance data
DSP 11-15
DSJ (Incorporating JM Plate Mounted Fan) 16-18
DSM 19-23
DSC 24-28
- Vertical Discharge - Details & Performance data
DVP 29-32
DVM 33-36
DVC 37-40
- Wall Extract Units 41
Ancillaries 42-45
CONTENTS

Speed Controllers & Changeover Panels 46


Other Units Available 47-48
Useful Information 49-50

3
General Information - CDX Range

CDV CDX CDH


(can be converted into CDV)

Introduction Construction
The CDX range of roof units are available in three basic variants. The The new range of Roof Extract Units are constructed on a pressed steel
standard CDX is manufactured as a side discharge unit, with a kit of parts base incorporating an integral bell mouth intake aperture. The integrated
supplied to enable a simple conversion to the vertical discharge unit epoxy coated bird guard forms an essential part of the construction and
(CDV). CDV units are also available factory constructed in the vertical provides a stable platform for the motor/impeller mounting.
discharge configuration. An alternative side discharge variant is the CDH,
which provides a lower cost solution to the CDX. The CDX and CDV
units are recommended for use in climates subject to frequent wet weather Motors
conditions as they provide a greater degree of protection from water
ingress. All units are fitted with long-life direct drive external rotor motors.
Bearings are maintenance free with a life expectancy L10 of 40,000 hours.
Sizes comply with standard R20 specification and are in accordance to
DIN323. Fans are speed controllable by either using stepless electronic
● Innovative single cowl design features serving both side and vertical speed controllers, or, where the units are operated in sensitive areas the
applications with one unit recommended 5 step transformer controllers. Rating is to IP44 in sizes
● Available in 8 sizes 225 mm to 630 mm to 355 mm, IP54 in sizes from 400 mm.

● Volume flow up to 2.9 m3/s The motor is mounted within the impeller to form one compact unit.
Ambient operating temperature of -20°C to +45°C.
● Static Pressures up to 650 Pa
All motors are manufactured in accordance with BS5000 and are
● Weatherproof designed to prevent water ingress to ventilated space equipped with thermal overload protection and insulation to part 2 of that
standard.
● Low Noise Level

● Guard fitted as standard


Cowls
● Robust construction
The unique design of the cowl assembly provides the installer with a
● Comprehensive range of ancillary equipment single solution for both side and vertical applications. Full instructions
are provided with each unit so that the customer can modify the unit from
side to vertical discharge when required. Cowls are manufactured from
Sizes robust materials and are capable of withstanding a high level of impact,
mechanical stress and temperature variations. All cowls offer UV
225, 310, 355, 400, 450, 500, 560 and 630 mm fan diameter. protection and are suitable for temperatures -30°C to +75°C.

Standard Finish:
Fan Performance Goosewing Grey - BS5252F-10 A05
All units are fitted with a dynamically balanced single inlet, backward
Pinseal Embossed - SG0953.
curved centrifugal impeller for maximum efficiency and duty.
Contamination from dirt and dust is significantly reduced by using the
backward curved design.
Ancillaries
Temperature Range Motorised and air operated shutters, Acoustic curbs, Speed controllers,
Roof sockets.
-20˚C to +45˚C

4
CDX - Range
Performance
230V/50 HZ/ 1φ - 4 pole
450
450/4
400/4
400

350
Static Pressure (Pa)

355/4
300

310/4
250

200

150

100

225
50

0
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Volume flow (m3/s)

415V/50 HZ/ 3φ - 4 pole


650
560/4
600

500/4
550

500

450/4
450
400/4 630/6
400

350
Static Pressure (Pa)

355/4 560/6
300

CDX - SIDE OR VERTICAL DISCHARGE


310/4 500/6
250

200

150

100

50

0
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Volume flow (m3/s)

Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Speed Pressure Level at 3 m
Code 63 125 250 500 1K 2K 4K 8K dBA re 20µPa
rev/min

225 1425 58 66 60 63 56 56 57 50 44

310 1375 61 66 68 67 64 69 67 52 53

355 1375 60 68 68 65 64 68 58 56 51

400 1350 70 78 78 73 72 73 69 61 58

450 1230 68 76 77 73 68 67 63 66 55

500 1325 73 82 83 78 73 70 75 68 60
880 79 78 79 64 66 69 72 57 56
560 1210 77 87 85 80 75 73 69 69 61
890 83 84 81 66 68 69 71 57 57

630 860 88 88 84 70 71 74 71 60 60

5
CDX - Range
Electrical Data
220-240 V / 50 Hz / 1 φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Speed Controller Full Load Starting Speed Controller Sound
Motor Motor
Code Speed Current Current Current Current Level
Rating Elec- Trans- Rating Elec- Trans-
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
tronic former tronic former dB(A)
(kW) (A) (A) (kW) (A) (A)

CDX225/4 1425 0.05 0.2 0.7 ME1.1 TR1.1.5 44


CDX310/4 1375 0.13 0.6 2.1 ME1.1 TR1.1.5 0.11 0.2 0.7 N/A TR3.1 53
CDX355/4 1375 0.28 1.3 3.1 ME1.3 TR1.1.5 0.26 0.6 1.7 N/A TR3.1 51
CDX400/4 1350 0.47 2.1 5.0 ME1.3 TR1.3.4 0.44 0.8 2.9 N/A TR3.1 58
CDX450/4 1230 0.76 3.4 7.0 ME1.6 TR1.5.0 0.72 1.4 3.4 N/A TR3.2 55
CDX500/6 880 0.39 0.8 2.6 N/A TR3.1 56
CDX500/4 1325 1.19 2.1 8.6 N/A TR3.3 60
CDX560/6 890 0.69 1.5 3.3 N/A TR3.2 57
CDX560/4 1210 1.90 3.5 10.0 N/A TR3.4 61
CDX630/6 860 1.10 2.0 5.9 N/A TR3.3 60

Dimensions and Weights SIDE & VERTICAL DISCHARGE TYPES -


COVER REMOVED FOR CONNECTION TO TERMINAL BOX.
FOUR LIFTING LUGS ( 310 TO 630 SIZES ONLY ).
A
A

G
B

C
Pg 13.5 CABLE
GLAND FOR
CONNECTION
THROUGH
UNIT BASE
H

30

30

ØF - 4 HOLES
J CRS. (Fixing to Roof Curb) J CRS. (Fixing to Roof Curb)
150

ØF - 4 HOLES
150

(FIXING TO ROOF)
E CRS. (Fixing to Roof Socket) E CRS. (Fixing to Roof) (FIXING TO ROOF)
EXTRA CENTRAL
D SQ CURB FIXING D SQ
560/630 ONLY
MINIMUM HEIGHT ABOVE ROOF SURFACE MINIMUM HEIGHT ABOVE ROOF SURFACE
(Roof Socket available) (Roof Socket available)
K

COVER REMOVED FOR


CONNECTION TO FOUR LIFTING LUGS ( 310 TO 500
TERMINAL BOX. SIZES ONLY ).

EXTRA CENTRAL
CURB FIXING
560/630 SIZE ONLY.

Pg 13.5 CABLE GLAND


L

FOR CONNECTION
THROUGH UNIT BASE.
M
30

MINIMUM HEIGHT
ABOVE ROOF SURFACE

J CRS (FIXING TO ROOF CURB) E DIA. FOUR HOLES


IN BASEPLATE
UPPER SURFACE
FOR ROOF
SOCKET MOUNTING.
E CRS (FIXING TO ROOF SOCKET)
D SQ.

Please note that the CDX series of roofs unit are available as demonstrated above in both side and vertical discharge.
Product A B C D E F G H J K L M Weight
Code (Kg)
225 450 236 218 338 245 10 192 50 158 480 224 104 7
310 618 346 320 438 330 10 286 55 258 636 327 155 14
355/400 865 475 405 598 450 12 354 65 360 760 409 240 27
450/500 1050 550 465 668 535 12 458 67 285 936 447 277 42
560/630 1300 636 530 943 750 14 545 87 560 - - - 60

All dimensions shown in mm

6
Ancillaries - CDX
Roof Socket
Roof Sockets are constructed in sea water resistant aluminium, fully
welded and thermally lined to prevent condensation. The roof sockets
D
can be used in conjunction with soaker sheets.
DIA
TAPPED HOLES
Product A B C D E F Weight
Code (Kg)
225 245 294 571 258 M6 300 3.5
C SQUARE
310 330 395 657 345 M6 300 4.5 B SQUARE
A SQUARE
355/400 450 555 817 505 M10 300 6.5
450/500 535 625 877 565 M10 300 7.5
F
560/630 750 895 1147 835 M10 300 10.5

Air Operated Damper E No. OF HOLES F DIA.


BOTH FLANGES
Air operated dampers are constructed from galvanised sheet steel with
sea water resistant aluminium shutters.
D
PC
D

ØA
Product A B C D E F Weight
Code (Kg)
225 183 235 115 213 6 7 1.2
310 256 306 156 285 6 7 2.0
ØB
355/400 402 464 220 438 6 9 4.2
450/500 402 464 220 438 6 9 4.2
C

560/630 569 639 255 605 8 9 6.8

Acoustic Curb
Acoustic curbs are constructed in sea water resistant aluminium, fully
D
welded, and thermally lined to prevent condensation. Splitter sections
are housed in galvanised sheet steel casings.
FOUR E DIA. A SQUARE
TAPPED HOLES
Product A B C D E F Weight
Code (Kg)
225 245 294 571 258 M6 400 6.5 B SQUARE OUTSIDE

310 330 395 710 345 M6 500 10.5


F

355/400 450 555 874 505 M10 650 17.5


450/500 535 625 900 565 M10 650 19.0
C SQUARE
CDX - ANCILLARIES
560/630 750 895 1200 835 M10 750 31.5

Attenuation Pressure Loss


Product Attenuation in dB at medium frequencies in [Hz]
Code Fan Volume Pressure
63 125 250 500 1000 2000 4000 Size Flow Loss
225 2 5 8 12 18 22 20 225 0.1m3/s 6Pa
310 3 5 8 12 19 23 21 310 0.3m3/s 13Pa
355 3 5 8 12 19 21 21 355/400 0.8m3/s 17Pa
400
450/500 1.7m3/s 20Pa
450 3 5 8 13 20 22 21
500 560/630 2.4m3/s 15Pa
560 2 5 9 12 18 21 20
630

7
Ancillaries - CDX
Pre Galvanised Steel Upstand
The pre-galvanised steel upstands provide a low cost method of
mounting the unit. Fitting of the unit is through the sides of the
baseplate, suitable captive nuts are provided in the upstand. This style
of upstand is not suitable for the use with soaker sheets.
D

Product B C D E F
Code
225 333 410 293 M6 150
310 433 510 393 M6 150
C SQUARE
355/400 593 670 553 M6 150 B SQUARE
ØE - 8 OR 12 CAPTIVE NUTS
450/500 663 740 623 M8 150 TO SUIT FAN BASE PLATE.
560/630 935 1012 895 M8 150
F

INLET FLANGES & FLEXIBLE CONNECTOR ASSEMBLIES


( ATTACHMENT TO ROOF UNIT USING
FIXINGS ON UNDERFACE OF BASEPLATE )
Inlet Flanges & Flexible Connectors
Inlet Flexible D PCD
A

Flange Connector
Product A B C D E F G Weight Weight
Code (kg) (kg) E No. OF HOLES F DIA.
225 183 235 130 213 6 7 25 0.4 1.0 ( FLEXIBLE CONNECTOR
BOTH FLANGES )
310 256 306 130 285 6 7 25 0.6 1.5
B
355/400 402 464 130 438 6 9 30 1.0 2.4 INLET
G

450/500 402 464 130 438 6 9 30 1.0 2.4 B FLANGE


560/630 569 639 130 605 8 9 30 1.5 3.5
FLEXIBLE
C

CONNECTOR

Speed Controllers
All single phase fans can be controlled using our ME. range of electronic speed controllers. See page 46 for further details.

5 step transformer speed controllers (TR.) are available for both single and three phase units.

TR1.1.5, 1.3.4, 1.5.0


Current Range 1.5-3.4-5.0 Amp
Standard electrical supply 230V 1φ 50Hz
5 steps: 230V/160V/145V/130V/105V
Mounting - Surface
Construction - Plastic splashproof box

TR3.1,3.2,3.3,3.4
Current Range 1-2-3-4 Amp
Standard electrical supply 400V 3φ 50Hz
5 steps: 400V/280V/230V/180V/140V
Motor protection through thermal contacts
Mounting - Surface
Construction - plastic box except TR3.4 (metal
box) all splashproof

8
General Information - Colchester Range
Mechanical Details The Colchester Roof Unit Range
Weather cap, Motor Compartment and base
These compartments are moulded in ultra violet stabilised polyester resin,
glass reinforced, rendered fire retardant to BS 476: Part 7, Class 2.
Standard Colourant to BS 4800: 08B-21 is built in. Or other B.S. and
R.A.L. colours available.
This material is strong, light in weight, gives excellent resistance to
atmospheric corrosion and is suitable for operational use in a wide range
of climatic conditions. DSP, DSJ, DSC, DSM DVP, DVC, DVM
The unit has been load tested to ensure a generous structural factor of
safety enabling the units to withstand all normally encountered weather
conditions. The caps are secured to the mounting brackets by stainless Speed Regulation
steel screws.
Please refer to page 46 for full details
Mountings
Fan support arms are of mild steel, resiliently mounted to the base.
Electrical Supply, 50 Hz
Mounting position Fans
The units have been designed to operate efficiently when mounted Single phase: 220-240 V
horizontally or on a pitched roof up to an angle of 30° from the horizontal. Three phase: 380-420 V or 220-240 V/380-420 V.
DSP, DSM & DSC units can be wall-mounted, (see page 41). Roof angles Available also for alternative voltages.
above 30° please enquire.
Overheat protection
Purlin mounting Fitted as standard on all non-flameproof single phase motors, (except F22
frames). Available on all others - please enquire.
Purlin boxes, soaker sheets and direct mounting sheets for most popular
profiles are available for most units.
Lubrication
Motor bearings are prelubricated with high quality grease. In ambient
Motor Specification temperatures up to 50°C (122°F) relubrication is recommended after 30,000
hours running or five years intermittent use. Where lubricators are fitted
Totally enclosed motors, single and three phase (normally F22/D132/D160) the motors should be relubricated after two
Metric sized, ball bearing, squirrel cage induction type, for direct on line years.
starting. All have Class F insulation. Ratings comply generally with BS
5000:Pt 99 and IEC 34-1, with degree of motor protection IP 55 to IEC 34-5.

Single phase motor types


BT4, BT5, BT9, CT5, CT9: capacitor start and run with a motor mounted
pre-wired capacitor, where possible. F22: Capacitor start and run with
a separate wall mounting capacitor box. COLCHESTER RANGE
Two speed motors
These are available as shown in the tables.
Single phase: series parallel reconnection
Three phase: BT5, BT9, CT5, CT9, F22, D132, D160 - Pole changing (full and
half speed) or P.A.M. - Pole Amplitude Modulation (full and approx two thirds
speed). D132-Dual wound.

DSP and DVP- please enquire for further information.

Flameproof Motors
Some units can be supplied with flameproof motors type EExd certified for
Groups 11A and 11B in Zone 1 applications. Insulation is Class F. Cable
entries: Tapped hole for conduit or cable gland.
Note: Single phase flameproof motor capacitors are mounted within the
motor enclosure. Isolators are not available with flameproof motors.

9
General Information - Colchester Range
Test Procedures
Aerodynamic
The complete units are air tested according to British Standard BS 848: The spectra quoted are average figures for the performance characteris-
Part 1, 1980 using the chamber method detailed in Paragraph 26.7 (Fan tic. The Sound Power Levels shown are for Open Inlet conditions i.e.
without ductwork connected. To obtain the Sound Power Level, when
powered exhaust ventilators).
ductwork is connected to the unit without an abrupt change of area, the
values shown in the table 'Correction for In-Duct Sound Power Levels'
Sound Levels should be applied.
The Sound Power Level data presented has been established from tests
in accordance with BS 848 Part II, 1966 HEVAC Supplement-Free Field The Sound Pressure Level quoted is the level calculated in dBA at 3 me-
and semi reverberant methods. tres distance over a sphere, under free field conditions and is presented
for comparative purposes. The data refers to a unit mounted in a non-
The Sound Power Level in each octave band is calculated from the meas- reverberant area, in practice the unit will be mounted in a semi-reverber-
ured sound pressure levels. ant area which will result in a higher sound pressure level than indicated
by the dBA figure.

Correction for in-duct sound power levels


Fan Size Curb Inlet Hz
DSC, DVC, Fan Size
DSP, DVP Area
DSM, DVM m2 63 125 250 500 1K 2K 4K 8K
200 - 0.0625 15 9 2 0 -1 -4 -2 -3
250 315/355 0.106 12 7 1 0 -2 -3 -2 -3
330 400 0.16 10 4 1 -1 -2 -3 -3 -3
400 450/500 0.25 9 2 0 -1 -4 -2 -3 -2
500 630 0.49 6 1 0 0 -3 -3 -3 -2
630 710/800 0.64 4 1 -1 -2 -3 -3 -3 -2
760 1000 1.0 2 0 -1 -4 -2 -3 -2 -1

Order Specification Example


• Type of unit DSM
• Fan size 400 mm
• Curb or purlin mounting Curb Mounted
• Impeller rev/min 900 RPM
• Electrical supply - volts, Hz, phase 220/-240V/50Hz/1φ
• Volume flow 0.4m3/s
• Static Pressure 150 Pa
• Quotation ref. Q12345/A

Anti-backdraught shutters
The use of shutters does not reduce fan performance, but will improve weathering under extreme conditions. On side discharge units aluminium shutters are
an optional extra.

All vertical discharge units are fitted with aluminium shutters as standard, being opened by air movement and closed by stainless steel springs.

Where shutters are fitted synthetic rubber buffers are provided to ensure quiet operation.

10
Side Discharge DSP

Specification
The type DSP roof extract unit is designed to satisfy the consultants Most motors have excellent speed control characteristics and can be
functional requirement for a direct drive propeller fan unit of guaranteed regulated down to 20-30% of full speed. Two speed motors are
performance, and the architects aesthetic need for a very low contour available. Motors are rated for continuous running in ambient
glass fibre reinforced cowl. temperatures of up to 50°C (122°F).
DSP units are despatched completely assembled and packed.
The fan is of Woods 2101 GP series powered by a metric motor giving
high efficiency in terms of airflow per Watt and consequent low running Impellers
costs. The impeller is designed to give maximum volume at minimum
noise level for minimum power consumption. Fan diameters 315-710 mm are of aluminium clad steel. Fan diameters
800-1000 mm are of hot dipped galvanised steel blade with aluminium
The range comprises nine sizes with fan inlet diameters from 315 to 1000 hub.
mm and air volume flows of up to 7.2 m3/s.
Balanced to BS6861 Part 1 (ISO 1940, 1986) grade G6.3. Corrosion
All units are available for curb or purlin mounting. Automatic anti- resistant and suitable for continuous outside use.
backdraught shutters, isolators, bird guards, burglar bars, motorised
dampers, pre-fabricated curbs and soaker sheets are available as
optional extras.

Performance Data
315 mm 355 mm
ft3/min 0 200 400 600 800 ft3/min 0 500 1,000 1,500 SIDE DISCHARGE - DSP
m3/hr 0 500 1,000 1,500 m3/hr 0 1,000 2,000 3,000
80 mm in mm in
wg wg wg wg

100 10 0.4
70

60 6 80 8
FAN STATIC PRESSURE Pa

FAN STATIC PRESSURE Pa

0.3
50 0.2
13
8

13 6
0r

60 6
0 re
e v/

40 4
m in

v/m

0.2
in

30 40 4
90 0.1
90
0

20 2
0
re

0.1
rev
v /m

/m

20 2
in

in

10

0 0 0.0 0 0 0.0
0.0 0.1 0.2 0.3 0.4 0.0 0.2 0.4 0.6 0.8
VOLUME FLOW m3/s VOLUME FLOW m3/s

11
Side Discharge DSP
400 mm 450 mm
ft3/min 0 500 1,000 ft3/min 0 1,000 2,000
m3/hr 0 500 1,000 1,500 2,000 m3/hr 0 2,000 4,000
mm in mm in
wg wg wg wg
120
80 8
0.3
100 10 0.4
FAN STATIC PRESSURE Pa

60

FAN STATIC PRESSURE Pa


6
80

1 38
138 0.2

0 re
0 re

v /m
60
v/m
40 4

in
in

5 0.2
40
90 0.1

90
0r
0

20

ev
2
re

68

/m
v/m

0r

in
20 e
in

v/
m
in
0 0 0.0 0 0 0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
VOLUME FLOW m3/s VOLUME FLOW m3/s
500 mm 630 mm
ft3/min 0 1,000 2,000 3,000 ft3/min 0 2,000 4,000
m3/hr 0 2,000 4,000 6,000 m3/hr 0 2,000 4,000 6,000 8,000
mm in mm in
wg wg wg wg
140
100
10 0.4

120

80 8
FAN STATIC PRESSURE Pa

100 0.4 0.3


10
FAN STATIC PRESSURE Pa

136

92 0
80 60 6
0

rev
re v /

/m i
mi n

0.2

n
60
70

40 4
0r

5 0.2
ev /

5
90

min

40
0r

60

0.1
ev /

rev

70
0
mi

20
/m

r 2
n

in
ev

20
/m
in

0 0 0.0 0 0 0.0
0.0 0.4 0.8 1.2 1.6 0.0 0.4 0.8 1.2 1.6 2.0 2.4
VOLUME FLOW m3/s VOLUME FLOW m3/s

710 mm 800 mm
ft3/min 0 2,000 4,000 6,000 ft3/min 0 2,000 4,000 6,000 8,000 10,000
m3/hr 0 2,000 4,000 6,000 8,000 10,000 m3/hr 0 5,000 10,000 15,000
mm in 160 mm in
wg wg wg wg
15
80 140
8
0.3

120
FAN STATIC PRESSURE Pa
FAN STATIC PRESSURE Pa

60 6
100 10 0.4
8 75

875

0.2
rev/m

rev/

80
min
in

40 4
6 70

60
67
rev/m

0r

5 0.2
ev/
53

0.1
min
53
in

40
0r

0r

20 2
ev/m

ev/
mi
in

20

0 0 0.0 0 0 0.00
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 0 1 2 3 4 5
VOLUME FLOW m3/s VOLUME FLOW m3/s

12
Side Discharge DSP
Performance Data
1000 mm
ft3/min 0 5,000 10,000 15,000
m3/hr 0 10,000 20,000
mm in
wg wg

160
15 0.6
FAN STATIC PRESSURE Pa

120
710

10 0.4
rev/
mi n

80
57
0r
ev /
mi n
47

5 0.2
0
rev

40
/m
in

0 0 0.0
0 1 2 3 4 5 6 7
VOLUME FLOW m3/s

Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Speed Pressure Level at 3 m
Code 63 125 250 500 1K 2K 4K 8K dBA re 20µPa
rev/min

315 900 68 67 61 57 51 47 43 39 38
1380 73 76 75 69 64 61 58 53 47

355 900 72 71 65 61 55 51 47 43 42
1380 77 80 79 73 68 65 62 47 51
400 900 75 74 68 64 58 54 50 46 45
1360 80 83 78 72 67 64 61 56 54
450 680 72 71 65 61 55 51 47 43 42
SIDE DISCHARGE - DSP
900 79 78 72 68 62 58 54 50 49
1380 84 87 82 76 71 68 65 60 58
500 700 75 74 68 64 58 54 50 46 45
900 82 81 75 71 65 61 57 53 52
1360 87 90 85 79 74 71 68 63 61
630 560 79 77 71 66 61 57 53 49 47
700 83 82 76 72 66 62 58 54 53
920 90 89 83 79 73 69 65 61 60

710 530 81 79 73 68 63 59 55 51 49
670 86 85 79 75 69 65 61 57 56
875 92 91 85 81 75 71 67 63 62

800 530 82 80 79 75 72 61 63 56 57
670 86 87 84 80 77 74 70 62 62
875 92 93 90 86 83 80 76 68 68
1000 470 85 81 80 77 75 71 64 59 59
570 89 87 86 82 79 76 70 63 64
710 93 94 91 87 84 81 77 69 69

13
Side Discharge DSP
Electrical Data
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Full Load Starting
Motor Speed Controllers Motor Speed Controllers
Speed Current Current Current Current
Code Motor Rating Rating
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
(kW) Electronic Transformer (kW) Electronic Transfomer
(A) (A) (A) (A)
900 BT4 0.02 0.25 0.4 ME1.1 MT1.1 0.035 0.15 0.4 ME3.5S MT3.0.5
315
1380 BT4 0.065 0.5 1.0 ME1.1 MT1.1 0.10 0.35 1.3 ME3.5S MT3.0.5

900 BT4 0.035 0.35 0.6 ME1.1 MT1.1 MT3.0.5


355 0.035 0.15 0.4 ME3.5S
1380* BT4 0.10 0.8 1.5 ME1.1 MT1.1 MT3.0.5
0.10 0.45 2.0 ME3.2D
900* BT5 0.05 0.46 0.67 ME1.1 MT1.1 0.04 0.24 0.5 ME3.2D MT3.0.5
400
1380* BT5 0.18 1.4 2.6 ME1.3 MT1.5 0.15 0.58 2.4 ME3.2D MT3.1

600 BT5 0.032 0.45 0.65 ME1.1 MT1.1 0.032 0.24 0.4 ME3.5S MT3.0.5
450 900* BT5 0.083 1.0 1.8 ME1.1 MT1.1 0.075 0.37 0.80 ME3.2D MT3.0.5
1380* BT9 0.31 2.2 5.9 ME1.3 MT1.5 0.31 0.95 3.2 ME3.2D MT3.1

700* CT5 0.075 1.1 1.4 ME1.3 MT1.5 0.060 0.30 0.60 ME3.2D MT3.0.5
500 900* CT5 0.19 1.8 3.0 ME1.3 MT1.5 0.13 0.45 1.1 ME3.2D MT3.0.5
1360* CT5 0.45 2.8 6.0 ME1.6 MT1.5 0.45 1.2 4.5 ME3.2D MT3.2
560* CT9 0.08 1.2 1.6 ME1.3 MT1.5 0.10 0.55 1.0 ME3.2D MT3.1
630 700* CT9 0.16 1.9 3.4 ME1.3 MT1.5 0.16 0.75 1.7 ME3.2D MT3.1
920* CT9 0.43 3.3 7.5 ME1.6 MT1.5 0.41 1.5 5.3 ME3.2D MT3.2
530* CT9 0.12 1.8 3.0 ME1.3 MT1.5 0.12 1.10 1.7 ME3.2D MT3.2
710 670* CT9 0.21 2.3 3.7 ME1.3 MT1.5 0.21 1.25 2.6 ME3.2D MT3.2
875* CT9 0.49 3.8 8.2 ME1.6 MT1.5 0.49 1.8 4.3 ME3.2D MT3.2

560* F2265 0.30 2.8 4.0 ME1.3 MT1.5 0.3 1.75 3 ME3.2D MT3.2
800 700* F2265/9+ 0.60 4.4 11.0 ME1.6 MT1.5 0.6 2.0 6.0 ME3.2D ME3.2
920* F2269 - 1.3 3.5 16.0 ME3.5S -

470 D132/26 - 0.75 3.3 10 ME3.10S -


1000 570 D132/26 - 1.3 4.4 18 ME3.10S -
710 D132/26 - 2.5 7 32 ME3.10S -

* By connecting 3φ fans in star, a second speed will be obtained approximately 75% of the scheduled speed.
+ F2265 motor for 3φ, F2269 motor for 1φ

Flameproof Motors

220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Nominal Motor Motor
Current Current Capacitor Current Current
Code Speed Motor Rating Motor Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V) d.o.l
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
900 PENV89M 0.075 0.9 3.2 10.0 ENV89M 0.075 0.30 1.1
315
1400 PENV89M 0.30 2.1 9.4 10.0 ENV89M 0.30 0.75 3.6
900 PENV89M 0.075 0.9 3.2 10.0 ENV89M 0.075 0.30 1.1
355
1400 PENV89M 0.30 2.1 9.4 10.0 ENV89M 0.30 0.75 3.6
900 PENV89M 0.075 0.9 3.2 10.0 ENV89M 0.075 0.30 1.1
400
1400 PENV89M 0.30 2.1 9.4 10.0 ENV89M 0.30 0.75 3.6
900 PENV89M 0.075 0.9 3.2 10.0 ENV89M 0.075 0.30 1.1
450
1400 PENV89M 0.30 2.1 9.4 10.0 ENV89M 0.30 0.75 3.6
900 PENV89L 0.18 1.8 7.2 10.0 ENV89M 0.18 0.60 2.1
500
1400 PENV89L 0.50 3.1 15.0 20.0 ENV89M 0.50 1.20 6.0
700 PENV89M 0.28 2.1 4.5 20.0 ENV89M 0.28 0.92 3.2
630
940 PENV89L 0.63 6.3 17.5 20.0 ENV89M 0.63 1.95 7.8
700 PENV89M 0.28 2.1 4.5 20.0 ENV89M 0.28 0.92 3.2
710
920 PENV89L 0.63 6.3 17.5 20.0 ENV89M 0.63 1.95 7.8

800 700 - ENV89M 0.60 2.10 8.4

14
Side Discharge DSP
Dimensions & Weights

Purlin Mounting Roof Sheet


Curb Mouting Curb Mounting

A square 2 lifting lugs at opposite A square


corners 630, 710 & 800 Fan sizes.
Shutters Available in
4 lifting lugs 1000 Fan size. when required 250 - 500 curb sizes only
Isolating switch
when required. Bird guard
Not available with when required
FLP motor

C
C

Soaker sheet Screws


supplied
8

72
50

130
130

R
100
min
N
G

Soaker sheet
E incorporating curb
D square Coach bolts supplied
250-400=4 off
Sealing B square 500-760=8 off
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
to motor except when Second entry is
86mm. Double Six. for use with single
isolating switch is fitted
N

91mm. Double Six M. phase capacitor only


130

Soaker
sheet Skirt

Cable Entries:
K crs

Totally enclosed motors:


J crs

BT and CT motors fitted with


CM16 cable gland. F22 fitted
F square with CM25 cable gland.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
(at extra cost) if full details of
H square cable are stated on order.

Flameproof Motors
Fan Weight Weight Weight
Curb Size Motor A B C D E F G H J K L M N P R Unit Purlin Motor R Unit
Size DSP (kg) Box (kg)
315 BT4 600 525 310 325 75 420 200 595 550 320 2 320 272 134 135 17 8.8
325 ENV89MP 233 41 SIDE DISCHARGE - DSP
355 BT4 600 525 310 325 75 420 200 595 550 320 2 320 272 134 135 19 8.8
400 400 BT5 710 600 355 400 75 495 200 670 625 400 3 200 272 134 130 20 10.3 ENV89MP 228 43
450 BT5 820 700 400 500 75 595 230 770 725 500 3 250 302 164 120 25 16.2
ENV89MP 218 49
500 450 BT9 820 700 400 500 75 595 230 770 725 500 3 250 302 164 155 27 16.2
ENV89LP 262 56
500 CT5 820 700 400 500 75 595 230 770 725 500 3 250 302 164 141 29 16.2 218
ENV89MP 52
ENV89LP 242 69
700 630 CT9 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 161 46 22.6
ENV89MP 198 65
710 CT9 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 141 50 34.5 ENV89MP 178 70
ENV89LP 222 74
800 800 F2265 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 250 72 34.5
ENV89MP 231 77
800 F2269 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 304 85 34.5
1000 1000 D132 1700 1250 710 1000 100 1140 280 1320 1275 1000 5 250 352 214 270 125 42.7 -

All dimensions in mm

15
Side Discharge DSJ

Specification
The DSJ roof extract unit incorporates the Woods JMP (Plate mounted
JM fan) installed within a side discharge cowl. The cowl and fan are
supplied separately for simple assembly before installation.

The range comprises of five sizes with fan inlet diameters from 315mm to
500mm and air volumes of up to 1.44m3/s.

All units are available for curb or purlin mounting. Automatic anti-
backdraft shutters, pre-fabricated curbs and soaker sheets are available
as optional extras.

All motors are speed controllable with overheat protection as standard


on single phase motors.

Impellers
A unique high efficiency aerofoil section blade. All Woods JMP impellers
are high pressure die cast to offer thin aerofoil sections for low genera-
tion of noise levels. Every rotating die cast component is x-rayed using
Real Time Radiography inspection prior to assembly.

Performance Data
315 mm 355 mm
ft3/min 0 500 1,000 1,500 500 1,000 1,500
ft3/min 0
m3/hr 0 1,000 2,000 3,000 m3/hr 0 1,000 2,000 3,000
80 mm in 160 mm in
wg wg wg wg
15
70 140

60 120
6
FAN STATIC PRESSURE Pa
FAN STATIC PRESSURE Pa

50 0.2 100
10 0.4
1420 re

40 80
4
144
/minv

0 re

30 60
v/m

0.1
in

5 0.2
20 2 40

10 20

0 0 0.0 0 0 0.00
0.0 0.2 0.4 0.6 0.8 0.0 0.2 0.4 0.6 0.8
VOLUME FLOW m3/s VOLUME FLOW m3/s

16
Side Discharge DSJ
Performance Data
400 mm 450 mm
ft3/min 0 2000 ft3/min 0 2000

m3/hr 0 2000 4000 6000 m3/hr 0 2000 4000 6000


160 mm in mm in
wg wg 160
wg wg
15 15
140 140

120 120
FAN STATIC PRESSURE Pa

FAN STATIC PRESSURE Pa


100 100
10 0.4 10 0.4

1440
80 80

rev/m
1440

in
60 60
rev/m

5 0.2 5 0.2
in

40 40

20 20

0 0 0.00 0 0 0.00
0.0 0.4 0.8 1.2 1.6 0.0 0.8 1.2 1.6
0.4
VOLUME FLOW m3/s VOLUME FLOW m3/s

500 mm
ft3/min 0 2000

m3/hr 0 2000 4000 6000


160 mm in
wg wg
15
140

120
FAN STATIC PRESSURE Pa

100
10 0.4
144

80
0 re
v/m
in

60

5 0.2
40

20

0 0 0.00
0.0 0.4 0.8 1.2 1.6
VOLUME FLOW m3/s
SIDE DISCHARGE - DSJ

Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Code Speed Pressure Level at 3 m
rev/min 63 125 250 500 1K 2K 4K 8K dB(A) re 20 µPa

315 1420 69 73 70 68 64 61 58 52 49

355 1440 73 76 76 72 68 65 62 56 53

400 1440 74 74 79 76 71 68 65 60 57

450 1440 80 84 84 80 76 73 69 64 61

500 1440 84 88 87 84 79 76 73 67 64

17
Side Discharge DSJ
Electrical Data
220-240 V / 50 Hz / 1 φ 380-420 V / 50 Hz / 3 φ

Full Load Speed Controller Full Load Speed Controller


Speed Motor Current Starting Motor Current Starting
Code Motor Rating (at 200V) Current Electronic Transformer Rating (at 400V) Current Electronic Transformer
(rev/min) (kW) (kW)
(A) (A) (A) (A)

DSJ315 1420 BT4 0.13 1.0 2.0 ME1.1 MT1.1 - - - - -

DSJ355 1440 BT4 0.13 1.0 2.0 ME1.1 MT1.1 - - - - -

DSJ400 1440 BT9 0.3 2.1 5.3 ME1.3 MT1.5 - - - - -

DSJ450 1440 CT5 0.55 3.7 5.5 ME1.6 MT1.5 0.58 1.7 6.5 ME3.2D MT3.2

DSJ500 1440 CT5 0.55 3.7 5.5 ME1.6 MT1.5 0.58 1.7 6.5 ME3.2D MT3.2

Dimensions and Weights

Purlin Mounting Roof Sheet


Curb Mouting Curb Mounting
A square A square
2 lifting lugs at opposite Shutters
corners 500 Fan sizes when required
Available in
325 - 500 curb sizes only

Bird guard
when required
C

Soaker sheet Screws


C

supplied
S
8

72
130
130

R
100
min
N
G

Soaker sheet
D square E incorporating curb
Coach bolts supplied
315-400=4 off
Sealing B square 500=8 off
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
isolating switch is fitted
N

91mm. Double Six M.


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, have
tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.

H square

Fan Weight Weight


Curb Size Motor A B C D E F G H J K L M N P R S Unit Purlin
Size DSJ (kg) Box

325 315 BT4 600 525 310 325 75 420 200 595 550 320 2 320 272 134 153 3 25 8.8

400 355 BT4 710 600 355 400 75 495 200 670 625 400 3 200 272 134 146 3 28 10.3

400 400 BT9 710 600 355 400 75 495 200 670 625 400 3 200 272 134 185 13 31 10.3

500 450 CT5 820 700 400 500 75 595 230 770 725 500 3 250 302 164 158 13 39 16.2

500 500 CT5 820 700 400 500 75 595 230 770 725 500 3 250 302 164 139 13 41 16.2

All dimensions shown in mm

18
Side Discharge DSM

Specification
The DSM roof extract unit is designed to satisfy the consultants functional fabricated curbs and soaker sheets are available as optional extras.
requirement for a direct drive, mixed flow fan unit of guaranteed performance,
and the architects aesthetic need for a very low contour cowl. Most motors have excellent speed control characteristics and can be regulated
down to 20-30% of full speed. Two speed motors are available. Motors are
The result is a highly efficient fan unit for use on extract systems requiring rated for continuous running in ambient temperatures of up to 50°C (122°F).
pressure development, or in free air conditions where a low noise level is
important. DSM units are despatched completely assembled and packed.

The range comprises seven sizes with fan inlet diameters from 200 to 760 mm
with air volumes of up to 9.2 m3/s.
Impellers
All units are available for curb or purlin mounting. Automatic anti-backdraught The impeller is aluminium and of Woods patented design. Air is discharged
shutters, isolators, bird guards, burglar bars, motorised dampers, pre- radially, thus eliminating the losses which occur when a vertical airflow is
converted to a horizontal discharge by the weather cap

Performance Data

200 mm 250 mm SIDE DISCHARGE - DSM


ft3/min 0 100 200 300 400 ft3/min 0 200 400 600 800 1000

m3/hr 0 200 400 600 mm in m3/hr 0 500 1000 1500 mm in


wg wg wg wg
200

100 10 0.4

160
15 0.6
80 8
FAN STATIC PRESSURE Pa

0.3
FAN STATIC PRESSURE Pa

120
13
00

60 13 6
re

00 10 0.4
v/m

re 0.2
v/m
in

in 80
40 4
86
88 0r
0r 0.1 ev 5 0.2
ev/ /m
mi 40 65 0 in
20 n 2
rev
/m
in

0 0 0.0 0 0 0.0
0 0.04 0.08 0.12 0.16 0.20 0 0.1 0.2 0.3 0.4 0.5
VOLUME FLOW m3/s VOLUME FLOW m3/s

19
Side Discharge DSM
Performance Data
330 mm 400 mm
ft3/min 0 500 1000 1500 2000 ft3/min 0 1000 2000 3000

m3/hr 0 mm in m3/hr 0 2000 4000 6000 mm in


1000 2000 3000 wg wg
wg wg

280 500 2.0

1.0
240
400 40

FAN STATIC PRESSURE Pa


1.5
FAN STATIC PRESSURE Pa

200 20 0.8
13
13

80
300
00

re
160 v/m
re
v/m

0.6 in
1.0
in

120
200 20
88 10 0.4
0r 90
80 ev 0 rev
/m /m 0.5
in in
65 0 100 6 70
r ev 0.2 r ev
40 /m /mi
in n

0 0.0 0 0 0.0
0
0 0.2 0.4 0.6 0.8 1.0 0 0.4 0.8 1.2 1.6
VOLUME FLOW m3/s VOLUME FLOW m3/s

500 mm 630 mm
ft3/min 0 2000 4000 6000 8000 ft3/min 0 2000 4000 6000 8000 10000

m3/hr 0 5000 10000 15000 mm in m3/hr 0 5000 10000 15000 mm in


wg wg 600 wg wg

800 80
3 500 2.0
FAN STATIC PRESSURE Pa

FAN STATIC PRESSURE Pa

600 400 40
60
14

1.5
00
re

92

2
v/ m

0
re

300
in

v/m
in

400 40 1.0
69
200 0r 20
ev
87 1 /m
0r in
ev / 54
200 mi 20 0r 0.5
6 80 n 460 ev/
rev
/mi
100 rev min
540 n /mi
rev/ n
min

0 0 0 0 0 0.0
0 1 2 3 4 0 1 2 3 4 5
VOLUME FLOW m3/s VOLUME FLOW m3/s

760 mm
ft3/min 0 5000 10000 15000 20000

m3/hr 0 10000 20000 30000 mm in


wg wg
1000

800 80
3
FAN STATIC PRESSURE Pa

600 60
96
0
re

2
v/m
in

400 40
71
0r
ev
/m
56 in 1
0r
200 ev/ 20
460 mi
rev n
/ mi
n

0 0 0
0 2 4 6 8 10
VOLUME FLOW m3/s

20
Side Discharge DSM
Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Code Speed Pressure Level at 3 m
rev/min 63 125 250 500 1K 2K 4K 8K dB(A) re 20µPa

200 880 58 64 53 55 49 48 42 33 35
1300 67 73 62 64 58 57 51 42 44
250 650 63 62 54 50 52 50 46 42 35
860 67 66 58 54 56 54 50 46 39
1300 73 76 69 65 67 65 61 57 50

330 650 68 69 63 56 55 52 50 41 39
880 73 74 68 61 60 57 54 46 46
1300 78 83 78 71 71 69 64 57 57
400 670 68 69 66 61 61 58 55 46 46
900 73 74 71 66 66 63 60 51 51
1380 81 84 83 77 77 74 70 65 61

500 540 75 75 74 66 65 61 56 52 50
680 77 77 76 69 68 64 59 54 53
870 82 81 80 74 72 69 64 59 58
1400 91 93 92 88 86 83 79 74 71
630 460 78 78 77 68 66 62 57 52 52
540 81 81 80 72 70 66 61 56 56
690 85 84 83 76 75 71 66 62 60
920 90 89 89 84 81 78 74 69 67
760 460 84 84 82 75 72 68 63 59 57
560 89 86 86 81 78 73 68 64 62
710 94 90 90 86 83 80 73 69 67
960 98 95 95 94 91 88 81 76 76

Electrical Data

220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ

Full Load Starting Full Load Starting


Motor Capa- Speed Controllers Motor Speed Controllers
Speed Current Current Current Current
Code Motor Rating citor Rating
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
(kW) (µF) Electronic Transformer (kW) Electronic Transformer
(A) (A) (A) (A)

200 880 BT4 0.02 0.26 0.4 2.0 - - 0.015 0.08 0.3 - -
200 1300 BT4 0.065 0.5 1.0 2.5 ME1.1 MT1.1 0.04 0.15 0.7 ME3.5s MT3.0.5
250 650 BT5 0.02 0.35 0.48 2.5 ME1.1 MT1.1 0.02 0.22 0.6 ME3.5s MT3.0.5
250
250
860
1300
BT4
BT4
0.035
0.1
0.35
0.8
0.6
1.5
4.0
2.5
ME1.1
ME1.1
MT1.1
MT1.1
0.035
0.1
0.15
0.35
0.4
1.3
ME3.5s
ME3.5s
MT3.0.5
MT3.0.5
SIDE DISCHARGE - DSM
330 650 BT5 0.04 0.65 1.0 2.5 ME1.1 MT1.1 0.032 0.24 0.4 ME3.5s MT3.0.5
330 880 BT5 0.083 1.0 1.8 5.0 ME1.1 MT1.1 0.083 0.37 0.95 ME3.5s MT3.0.5
330 1300 BT5 0.22 1.8 2.7 8.0 ME1.3 MT1.5 0.22 0.7 2.5 ME3.5s MT3.1
400 670 BT9 0.07 0.8 1.3 5.0 ME1.1 MT1.1 0.07 0.45 0.8 ME3.5s MT3.0.5
400 900 BT9 0.14 1.25 2.3 8.0 ME1.3 MT1.1 0.18 0.8 1.8 ME3.5s MT3.1
400 1380 CT5 0.5 3.4 5.5 20.0 ME1.6 MT1.5 0.5 1.3 5.5 ME3.5s MT3.2

500 540 CT9 0.12 1.8 2.6 10.0 ME1.3 MT1.5 0.12 1.1 1.7 ME3.5s MT3.1
500 680 CT9 0.25 2.1 3.0 15.0 ME1.3 MT1.5 0.21 1.25 2.6 ME3.5s MT3.2
500 870 CT9 0.43 3.3 7.5 15.0 ME1.6 MT1.5 0.49 1.8 5.3 ME3.5s MT3.2
500 1400 F2249 2.3 14.5 50.0 100.0 - MT1.12 2.3 5.5 30.0 ME3.10s -

630 460 F2265 0.23 2.3 3.5 12.0 ME1.3 MT1.5 0.23 1.3 2.2 ME3.5s MT3.2
630 540 F2265 0.4 3.3 4.6 20.0 ME1.6 MT1.5 0.4 2.2 3.8 ME3.5s ENQ
630 690 F2265 0.75 6.0 12.0 30.0 ME1.12 MT1.8 0.75 2.5 6.0 ME3.5s ENQ
630 920 F2269 1.8 9.8 24.0 50.0 - - 1.8 4.5 16.0 - -
760 460 D132/19 - 0.7 2.9 8.0 - -
760 560 D132/19 - 1.8 5.2 16.0 - -
760 710 D132/19 - 3.0 7.7 33.0 - -
760 960 D132/26 - 6.3 13.9 77.0 - -

21
Side Discharge DSM
Flameproof Motors

220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ

Full Load Starting Full Load Starting


Motor Motor
Speed Current Current Current Current
Code Motor Rating Motor Rating
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
(kW) (kW)
(A) (A) (A) (A)

400 700 PENV89MP 0.09 1.3 2.7 ENV89MP 0.09 0.38 1.2
400 900 PENV89MP 0.18 1.8 7.2 ENV89MP 0.18 0.6 2.1
400 1400 PENV89MP 0.5 3.1 15.0 ENV89MP 0.5 1.2 6.0
500 560 -
500 700 PENV89MP ENV89MP 0.37 1.3 6.2
0.37 3.4 15.0
500 920 PENV89MP ENV89MP 0.63 1.9 7.6
0.63 6.3 17.5
500 1400 - ENV89MP 2.5 5.2 26.0

630 460 -
630 560 -
630 700 - ENV89MP 0.75 2.5 10.0
630 940 - ENV112MP 1.8 4.6 20.0

Two Speed Totally Enclosed Motors

220-240 V / 50 Hz /φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Full Load Starting
Motor Capa- Winding Change- Motor Winding Change-
Speed Current Current Current Current
Code Motor Rating citor Type over Rating Type over
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
(kW) (µf) Panel* (kW) Panel
(A) (A) (A) (A)

330 880/540 BT5 0.06/0.013 0.65/0.4 1.2/0.4 4.0 SP EDC28 -


330 1290/770 BT5 0.22/0.045 1.8/0.85 2.7/1.0 8.0 SP EDC28 -
330 1300/650 BT9 0.22/0.033 0.65/0.25 1.5/0.5 PC EDC19
330 1300/860 BT9 0.22/0.057 0.9/0.42 3.3/1.0 PC EDC19
400 670/400 BT9 0.07/0.015 0.8/0.45 1.3/0.5 5.0 SP EDC28 -
400 900/540 BT9 0.14/0.03 1.2/0.7 2.0/0.8 8.0 SP EDC28 -
400 1380/830 CT5 0.5/0.11 3.4/2.0 5.5/2.0 20.0 SP EDC28 -
400 900/670 CT5 - 0.14/0.07 0.9/0.4 1.9/0.6 PC EDC19
400 1380/670 CT9 - 0.5.0.06 1.4/0.52 5.3/1.3 PC EDC19
400 1380/900 CT5 - 0.5/0.14 1.3/0.7 4.8/1.4 PC EDC19
500 680/430 CT9 0.25/0.065 3.0/2.2 3.0/2.5 15.0 SP EDC28 -
500 870/535 CT9 0.55/0.12 5.0/2.5 7.0/3.0 25.0 SP EDC28 -
500 680/460 F2265 - 0.25/0.075 1.2/0.65 2.3/1.4 PC EDC19
500 870/460 F2265 - 0.55/0.08 1.9/0.75 6.0/1.25 PC EDC19
500 870/680 CT9 - 0.55/0.25 2.8/1.5 5.7/1.7 PC EDC19

630 460/275 F2265 0.23/0.06 2.4/1.4 3.5/1.5 15.0 SP EDC28


630 540/350 F2265 0.4/0.1 3.6/1.65 5.5/2.0 20.0 SP EDC28
630 690/460 F2269 - 0.75/0.23 2.7/1.7 7.5/3.1 PC EDC19
630 920/690 F2269 - 1.8/0.76 5.8/3.0 25.0/7.0 PC EDC19
760 710/460 D132/26 - 2.8/0.76 8.0/3.8 37.0/12.5 DW EDC22
760 970/460 D132/27 - 5.5/0.6 14.0/3.8 35.0/14.0 PC EDC19
760 970/720 D132/27 - 5.5/2.25 16.0/7.2 80.0/25.0 PC EDC19

* Key to Winding Type


SP = Series Parallel
PC = Pole Change
DW = Dual Wound

22
Side Discharge DSM
Dimensions and Weights

Purlin Mounting Roof Sheet


Curb Mouting Curb Mounting

A square 2 lifting lugs at opposite A square


corners 700 & 800 4 lugs, 1000
size Shutters Available in
when required 250 - 500 curb sizes only
Isolating switch
when required. Bird guard
when required

C
C

Soaker sheet Screws


supplied
8

72
50

130
130

R
100
min
N
G

Soaker sheet
D square E Coach bolts supplied incorporating curb
250-400=4 off
Sealing B square 500-760=8 off
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
isolating switch is fitted
N

91mm. Double Six M.


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, CT9, F22
have tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
H square (at extra cost) if full details of
cable are stated on order.

Flameproof Motors SIDE DISCHARGE - DSM


Fan Weight Weight Weight
Curb Motor A B C D E F G H J K L M N P R Unit Motor R Unit
Size Purlin
Size (kg) (kg)
DSM Box
250 200 BT4 480 450 280 250 75 345 200 520 475 250 2 250 272 134 132 16 7.2 -

325 250 BT4 600 525 310 325 75 420 200 595 550 320 2 320 272 134 127 20 8.8 -
BT5 600 525 310 325 75 420 200 595 550 320 2 320 272 134 127 22 8.8
400 330 BT5 710 600 355 400 75 495 200 670 625 400 3 200 272 134 122 24 10.3 -
BT9 710 600 355 400 75 495 200 670 625 400 3 200 272 134 157 26 10.3
500 400 BT9 820 700 400 500 75 595 230 770 725 500 3 250 302 164 127 32 16.2
CT5 820 700 400 500 75 595 230 770 725 500 3 250 302 164 118 33 16.2 ENV89MP 154 54
CT9 820 700 400 500 75 595 230 770 725 500 3 250 302 164 158 37 16.2
700 500 CT9 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 138 58 22.6 ENV89MP 107 66
F2265 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 132 64 22.6 ENV89LP 157 78
F2249 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 132 75 22.6
800 630 F2265 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 95 75 34.5
ENV89LP 113 92
F2269 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 150 85 34.5
1000 760 D132 1700 1250 710 1000 100 1140 280 1320 1275 1000 5 250 352 214 103 129 42.7
-
D160 1700 1250 710 1000 100 1140 280 1320 1275 1000 5 250 352 214 245 161 42.7

All dimensions are shown in mm

23
Side Discharge DSC

Specification
The fan is a high efficiency backward curved centrifugal developed by The type DSC roof extract unit is designed to satisfy the needs of
Woods specifically for application in this range of roof extractors. consultants, contractors and users for a compact direct-driven centrifugal
The range comprises seven sizes with fan inlet diameters from 200 to 760 roof unit with a guaranteed performance and high efficiency on extract
mm with air volumes of up to 10.6 m3/s. systems with a significant static pressure requirement.

All units are available for curb or purlin mounting. Automatic anti- The unit provides excellent resistance to atmospheric corrosion. The weather
backdraught shutters, isolators, bird guards, burglar bars, motorised cap and base are moulded in fire retardant glass fibre reinforced resin.
dampers, pre-fabricated curbs and soaker sheets are available as
optional extras.
Most motors have excellent speed control characteristics and can be
Impellers
regulated down to 20-30% of full speed. Two speed motors are available.
Motors are rated for continuous running in ambient temperatures of up High efficiency, backward curved centrifugal, designed by Woods
to 50°C (122°F). specifically for applications in this range of roof extract units.
DSC units are despatched completely assembled and packed.

Performance Data
200 mm 250 mm
ft3/min 0
ft3/min 0 200 400 600 500 1000
m3/hr
0 200 400 600 800 1000 1200 mm in m3/hr 0 1000 2000 mm in
wg wg wg wg

140 240

120
200 20 0.8
FAN STATIC PRESSURE Pa

100 0.4
FAN STATIC PRESSURE Pa

10
160
0.6
13

13
50

80
0
re

re
v/m

v/
m

120
in

in

60 10 0.4
5 0.2
90 80 90
40 0r 0r
ev ev
/m /m
670 i n in
6 70 0.2
rev 40 rev
20 /m /mi
in n

0 0 0 0 0 0.0
0.00 0.04 0.08 0.12 0.16 0.20 0.24 0.28 0.32 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
VOLUME FLOW m3/s VOLUME FLOW m3/s

24
Side Discharge DSC
Performance Data
330 mm 400 mm
ft3/min 0 1000 2000 ft3/min 0 2000 4000

m3/hr 0 2000 4000 mm in m3/hr 0 2000 4000 6000 8000 mm in


wg wg wg wg
400
600
360 60

320 500 2
30

FAN STATIC PRESSURE Pa


280
FAN STATIC PRESSURE Pa

13
50
13

1.0 400 40
240
5

re
0r

v/m
ev

in
/m

200
i

20
n

300
160 1
90
90 0.5 0r
120 0r 200 ev 20
ev /m
/m 10 in
in 6 60
80 650 rev
rev /m
/m 100 in
in
40

0 0 0.0 0 0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 0.0 0.4 0.8 1.2 1.6 2.0 2.4

VOLUME FLOW m3/s VOLUME FLOW m3/s

500 mm 630 mm
ft3/min ft3/min 0 5000 10000
0 2000 4000 6000 8000 10000
m3/hr 0 5000 10000 m3/hr 0 10000 20000 mm in
15000 mm in wg wg
wg wg 800

1000 100 4 700

600 60
800
FAN STATIC PRESSURE Pa

80
FAN STATIC PRESSURE Pa

3
500 2
14

94
00

0
re
re

v/m
v /m

600 60 400
in

40
in

2
70
300 0r
400 40 ev
93 /m 1
0r in
ev 560
/m 200 r ev 20
in /m
700 1 in
200 rev 20
/m
i n 100

0 0 0 0 0
0
0 1 2 3 4 5 0 1 2 3 4 5 6 7

VOLUME FLOW m3/s VOLUME FLOW m3/s


760 mm SIDE DISCHARGE - DSC
ft3/min 0 5000 10000 15000 20000

m3/hr 0 10000 20000 30000 mm in


wg wg

700

600 60
FAN STATIC PRESSURE Pa

500 2
72
0
re
v/ m

400 40
in

57
300 0r
ev
/m
47 in 1
0r
200 ev 20
/m
in
350
r ev
/m
100 in

0 0 0
0 2 4 6 8 10

VOLUME FLOW m3/s

25
Side Discharge DSC
Sound Levels
Open inlet Sound Power Level in dB re 1pW in Octave Bands Free Field Sound
Code Speed Pressure Level at 3 m
rev/min 63 125 250 500 1K 2K 4K 8K dB(A) re 20 µPa

200 670 54 55 53 49 45 38 38 30 29
900 61 62 60 56 52 45 40 37 36
1350 69 71 70 67 62 56 51 46 45
250 670 60 61 59 55 51 44 39 36 35
900 67 68 66 62 58 51 46 43 42
1350 75 77 76 73 68 62 57 52 51
330 650 69 67 63 59 53 48 42 38 39
900 73 74 71 67 62 57 51 46 47
1350 80 84 83 79 75 70 64 59 58
400 660 76 74 70 66 60 55 49 46 46
900 80 81 78 74 69 64 58 53 54
1350 86 90 89 85 81 76 70 65 64
500 700 82 80 76 72 66 61 55 52 52
930 88 88 84 80 75 70 64 60 60
1400 95 98 95 91 87 81 77 71 72
630 560 83 81 80 77 74 72 64 61 58
700 88 86 84 81 78 76 71 68 63
940 95 93 91 88 85 83 78 75 70
760 350 78 77 76 74 68 65 58 53 54
470 85 83 82 80 75 72 66 63 60
570 91 89 87 84 81 79 74 71 66
720 96 94 92 89 86 84 79 76 71

Electrical Data
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Speed Controller Full Load Starting Speed Controller
Motor Capa- Motor
Current Current Current Current
Code Speed Motor Rating citor Electronic Transformer Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V) Electronic Transformer
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
200 670 BT4 0.01 0.2 0.35 1.0 - - 0.01 0.17 0.35 - -
200 900 BT4 0.02 0.26 0.4 2.0 - - 0.015 0.08 0.3 - -
200 1350 BT4 0.065 0.5 1.0 2.5 ME1.1 MT1.1 0.04 0.15 0.7 ME3.5S MT3.05
250 670 BT5 0.02 0.35 0.48 2.5 ME1.1 MT1.1 0.02 0.22 0.6 ME3.5S MT3.0.5
250 900 BT5 0.04 0.45 0.7 2.5 ME1.1 MT1.1 0.05 0.25 0.65 ME3.5S MT3.0.5
250 1350 BT5 0.11 0.9 1.7 5.0 ME1.1 MT1.1 0.12 0.37 1.2 ME3.5S MT3.0.5
330 650 BT5 0.04 0.65 1.0 2.5 ME1.1 MT1.1 0.032 0.24 0.4 ME3.5S MT3.0.5
330 900 BT9 0.14 1.25 2.3 8.0 ME1.3 MT1.5 0.18 0.8 1.8 ME3.5S MT3.1
330 1350 CT5 0.45 3.1 7.5 20.0 ME1.3 MT1.5 0.5 1.3 5.5 ME3.5S MT3.2
400 660 CT9 0.16 1.9 3.4 8.0 ME1.3 MT1.5 0.18 0.7 1.7 ME3.5S MT3.1
400 900 CT9 0.43 3.3 7.5 15.0 ME1.6 MT1.5 0.49 1.8 5.3 ME3.5S MT3.2
400 1350 CT9 1.3 8.0 23.0 50.0 - MT1.8 1.3 3.3 12.0 ME3.5S AT5
500 700 F2269 0.6 4.8 11.0 25.0 ME1.6 MT1.8 0.6 2.0 6.5 ME3.5S MT3.2
500 930 F2269 1.4 9.2 24.0 50.0 ME1.12 MT1.12 1.4 4.0 16.0 ME3.10S -
500 1400 F2249 - 4.2 9.0 52.0 - -
630 560 D132/19 - 1.8 5.2 16.0 - -
630 700 D132/19 - 3.0 7.7 33.0 - -
630 940 D132/19 - 4.5 10.5 63.0 - -
760 350 D132/19 - 0.7 4.5 10.0 - -
760 470 D132/19 - 1.7 6.0 24.0 - -
760 570 D160/27 - 3.0 9.0 38.0 - -
760 720 D160/27 - 5.2 13.5 50.0 - -

26
Side Discharge DSC
Two Speed Totally Enclosed Motors

220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Motor Capa- Winding Change- Motor Winding Change-
Speed Current Current Current Current
Code Motor Rating citor Type over Rating Type over
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
Panel Panel
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
250 900/650 BT5 0.03/0.01 0.04/0.25 0.7/0.3 2.5 SP EDC28 -
250 1350/900 BT5 0.12/0.035 0.9/0.52 1.8/0.6 5.0 SP EDC28 -
330 900/600 BT9 0.11/0.035 1.0/0.6 1.7/0.7 6.0 SP EDC28 -
330 1350/900 CT5 0.36/0.11 2.5/1.4 4.0/1.5 12.0 SP EDC28 -
330 1350/700 CT5 - 0.36/0.045 0.95/0.4 2.7/0.8 PC EDC19
330 1350/900 CT5 - 0.36/0.11 1.05/0.55 3.9/1.2 PC EDC19
400 900/600 CT9 0.33/0.1 3.3/1.4 5.2/1.5 10.0 SP EDC28 -
400 1350/960 CT9 1.1/0.2 7.0/4.0 20.0/5.0 50.0 SP EDC28 -
400 1440/720 F2245 - 1.5/0.19 3.5/1.2 19.0/4.2 PC EDC19
400 1440/940 F2245 - 1.5/0.42 3.9/1.6 20.0/5.5 PC EDC19
500 950/710 F2269 - 1.3/0.55 5.0/2.4 25.0/7.0 PC EDC19

630 950/720 D132/26 - 3.6/1.5 11.0/5.7 66.0/22.0 PC EDC22

760 720/350 D160/27 - 6.0/0.75 15.5/6.5 64.0/20.0 PC EDC19

* Key to Winding Type


SP = Series Parallel
PC = Pole Change
DW = Dual Wound

Flameproof Motors
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Motor Motor
Speed Current Current Current Current
Code Motor Rating Motor Rating SIDE DISCHARGE - DSC
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
rev/min (kW) (A) (A) (kW) (A) (A)
400 700 PENV89MP 0.28 2.1 4.5 ENV112MP 0.28 0.92 3.2
400 900 PENV89MP 0.63 6.3 17.5 ENV112MP 0.63 1.95 7.8
400 1440 - ENV112MP 1.3 4.0 20.0

500 700 - ENV112MP 0.6 2.1 8.4


500 940 - ENV112LP 1.1 3.3 13.2

630 700 - ENV112MP 1.3 4.1 16.5

27
Side Discharge DSC
Dimensions & Weights

Purlin Mounting Roof Sheet


Curb Mouting Curb Mounting
A square 2 lifting lugs at opposite A square
corners 500 & 630 Fan sizes
Shutters Available in
4 lifting lugs 760 size when required 250 - 500 curb sizes only
Isolating switch
when required. Bird guard
Not available with when required
FLP motor
C

Soaker sheet Screws

C
supplied
8

72
50

130
130

R
100
min
N
G

Soaker sheet
D square E incorporating curb
Coach bolts supplied
250-400=4 off
Sealing B square 500-760=8 off
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
isolating switch is fitted
N

91mm. Double Six M.


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, CT9, F22
have tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
H square (at extra cost) if full details of
cable are stated on order.

Flameproof Motors

Curb Fan Motor Weight Weight Motor Weight


Size A B C D E F G H J K L M N P R Unit Purlin R Unit
Size DSC (kg) Box (kg)

250 200 BT4 480 450 280 250 75 345 200 520 475 250 2 250 272 134 79 17 7.2 -
325 250 BT5 600 525 310 325 75 420 200 595 550 320 2 320 272 134 71 22 8.8 -
400 330 CT5 710 600 355 400 75 495 200 670 625 400 3 200 272 134 67 25 10.3 -
BT5 710 600 355 400 75 495 200 670 625 400 3 200 272 134 122 27 10.3
BT9 710 600 355 400 75 495 200 670 625 400 3 200 272 134 157 28 10.3
500 400 CT9 820 700 400 500 75 595 230 770 725 500 3 250 302 164 106 42 16.2 ENV89MP 154 56
F2245 820 700 400 500 75 595 230 770 725 500 3 250 302 164 106 42 16.2
700 500 F2265 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 132 67 22.6 ENV89MP 107 70
F2269/49 1030 900 475 700 75 792 250 970 925 690 4 230 322 184 187 77 22.6 ENV89LP 151 82
800 630 D132 1300 1050 550 800 100 942 270 1120 1075 840 5 210 342 204 145 109 34.5 ENV89LP 113 101
1000 760 D132 1700 1250 710 1000 100 1140 280 1320 1275 1000 5 250 352 214 103 134 42.7 -
D160 1700 1250 710 1000 100 1140 280 1320 1275 1000 5 250 352 214 245 166 42.7

All dimensions are shown in mm

28
Vertical Discharge DVP

Specification
The type DVP roof extract unit is designed to satisfy the consultants Most motors have excellent speed control characteristics and can be
functional requirement for a direct drive propeller fan unit of guaranteed regulated down to 20-30% of full speed. Two speed motors are avail-
performance, and the architects aesthetic need for a very low contour able. Motors are rated for continuous running in ambient temperatures
glass fibre reinforced cowl. of up to 50°C (122°F).

The fan is of Woods 2101 GP series powered by a metric motor giving DVP units are despatched completely assembled and packed.
high efficiency in terms of airflow per Watt and consequent low running
costs. The impeller is designed to give maximum volume at minimum
noise level for minimum power consumption.
Impellers
The range comprises eight sizes with fan inlet diameters from 355 to Fan diameters 355-710 mm are of aluminium clad steel. Fan diameters
1000 mm and air volume flows of up to 9.2 m3/s. 800-1000 mm are of hot dipped galvanised steel blade with aluminium
hub.
All units are available for curb or purlin mounting. Isolators, bird guards, Balanced to BS6861 Part 1 (ISO 1940, 1986) grade G6.3. Corrosion re-
burglar bars, motorised dampers, pre-fabricated curbs and soaker sistant and suitable for continuous outside use.
sheets are available as optional extras.

Performance Data
355 mm 400 mm VERTICAL DISCHARGE - DVP
ft3/min 0 500 1000 1500 ft3/min 0 500 1000 1500 2000

m3/hr 0 1000 2000 mm in m3/hr 0 1000 2000 3000


mm in
50 wg wg 60 wg wg

50 0.20
40 4
0.15
136

40
FAN STATIC PRESSURE Pa

1380

FAN STATIC PRESSURE Pa

0 re

4
30 0.15
v/m
rev/m

in

0.10 30
in

20 2 0.10
20
2
0.05
10 0.5
10

0 0.0 0 0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.0 0.2 0.4 0.6 0.8 1.0 0.0
VOLUME FLOW m3/s VOLUME FLOW m3/s

29
Vertical Discharge DVP
Performance Data
450 mm 500 mm
ft3/min 0 1000 2000 3000 ft3/min 0 1000 2000 3000 4000

m3/hr 0 2000 4000 m3/hr 0 2000 4000 6000


mm in mm in
wg wg wg wg

80 80
8 8
0.3 0.3
136
0 re

60 60
FAN STATIC PRESSURE Pa

FAN STATIC PRESSURE Pa


6 6
v/m

13 60
in

0.2 0.2

rev/m
40 4 40 4

in
9 00
0.1 0.1

rev/
20 2 20 2

min
0 0.0 0 0.0
0.0 0.2 0.4 0.6 0.8
1.0 1.2 1.4 1.6 0.0 0.4 0.8 1.2 1.6 2.0
VOLUME FLOW m3/s VOLUME FLOW m3/s

630 mm 710 mm
ft3/min 0 2000 4000 6000 ft3/min 0 2000 4000 6000

m3/hr 0 2000 4000 6000 8000 10000 m3/hr 0 5000 10000


mm in mm in
70 wg wg wg wg
60 6
60 6
50 0.2
50 0.2
FAN STATIC PRESSURE Pa
FAN STATIC PRESSURE Pa

40 4

875 re
4
920

40
rev/m

v/m
30
30 in
in

0.1
0.1
20 2
20 2

10 10

0 0.0 0 0.0
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.0 3.2
VOLUME FLOW m3/s VOLUME FLOW m3/s

800 mm 1000 mm
ft3/min 0 2000 4000 6000 ft3/min 0 5000 10000 15000 20000

m3/hr 0 5000 10000 m3/hr 0 10000 20000 30000 mm in


mm in
wg wg wg wg

120 6 120

100 0.2 100 10 0.4


FAN STATIC PRESSURE Pa
FAN STATIC PRESSURE Pa

80 4 80
710
670 rev/

rev/
min
57

60 60
0r
670

min

0.1
ev/

0.1 5
m
rev/m

in

40 2 40
in

20 20

0 0.0 0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 0 2 4 6 8 10
VOLUME FLOW m3/s VOLUME FLOW m3/s

30
Vertical Discharge DVP
Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Speed Pressure Level at 3 m
Code 63 125 250 500 1K 2K 4K 8K dBA re 20µPa
rev/min

355 1380 77 80 79 73 68 65 62 47 51
400 1360 80 83 78 72 67 64 61 56 54
450 1380 84 87 82 76 71 68 65 60 58
500 900 82 81 75 71 65 61 57 53 52
1360 87 90 85 79 74 71 68 63 61
630 920 90 89 83 79 73 69 65 61 60
710 875 92 91 85 81 75 71 67 63 62
800 670 86 87 84 80 77 74 70 62 62
875 92 93 30 86 83 80 76 68 68
1000 570 89 87 86 82 79 76 70 63 64
710 93 94 91 87 84 81 77 69 69

Electrical Data
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Motor Speed Controllers Motor Speed Controllers
Current Current Current Current
Code Speed Motor Rating Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
rev/min (kW) (A) (A) Electronic Transformer (kW) (A) (A) Electronic Transformer

355 1380 BT4 0.1 0.8 1.5 ME1.1 MT1.1 0.10 0.40 2.0 ME3.2D MT3.0.5
400 1360 BT5 0.18 1.4 2.6 ME1.3 MT1.1 0.15 0.50 2.4 ME3.2D MT3.1
450 1360 BT9 0.31 2.2 5.9 ME1.3 MT1.5 0.31 0.95 3.2 ME3.2D MT3.1
900 CT5 0.19 1.8 3.0 ME1.3 MT1.5 0.13 0.45 1.1 ME3.2D MT3.0.5
500 1360 CT5 0.45 2.8 6.0 ME1.6 MT1.5 0.45 1.2 4.5 ME3.2D MT3.2
630 920 CT9 0.43 3.3 7.5 ME1.6 MT1.5 0.41 1.5 5.3 ME3.2D MT3.2
710 875 CT9 0.49 3.8 8.2 ME1.6 MT1.5 0.49 1.8 4.7 ME3.2D MT3.2
800 670 F2265/9+ 0.6 4.4 11.0 ME1.6 MT1.5 0.6 2.0 6.0 ME3.2D MT3.2
875 F2269 - 1.3 3.5 16.0 ME3.5s -
1000 570 D132/26 - 1.3 4.4 18.0
710 D132/26 - 2.5 7.0 32.0 ME3.10s -

+ F2265 motor for 3φ, F2269 motor for 1φ

VERTICAL DISCHARGE - DVP


Flameproof Motors
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Nominal Motor Motor
Current Current Capacitor Current Current
Code Speed Motor Rating Motor Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V) d.o.l
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
355 1400 PENV89M 0.30 2.1 9.4 10 ENV89M 0.30 0.75 3.6
400 1400 PENV89M 0.30 2.1 9.4 10 ENV89M 0.30 0.75 3.6
450 1400 PENV89M 0.30 2.1 9.4 10 ENV89M 0.30 0.75 3.6
500 900 PENV89L 0.18 1.8 7.2 10 ENV89M 0.18 0.60 2.1
1400 PENV89L 0.50 3.1 15 20 ENV89M 0.50 1.20 6.0
630 940 PENV89L 0.63 5.5 17 20 ENV89M 0.63 1.95 7.8
710 920 PENV89L 0.63 5.5 17 20 ENV89M 0.63 1.95 7.8
800 700 - - ENV89M 0.60 2.10 8.4

31
Vertical Discharge DVP
Dimensions & Weights

Purlin Mounting Curb Mounting Roof Sheet


Curb Mounting
A square

B square

Isolating switch Bird guard


when required. when required

C
C

Soaker sheet
Screws
supplied
8

72
50
130

130
R
100
min
N
G

Soaker sheet
D square E Coach bolts supplied incorporating curb
Sealing B square
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
N

91mm. Double Six M. isolating switch is fitted


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, CT9, F22
have tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
(at extra cost) if full details of
H square cable are stated on order.

Flameproof Motors
Fan Weight
Curb Size Motor A B C D E F G H J K L M N P R Weight Weight Motor R
Size Unit
DVP Unit Purlin
(kg) Box (kg)

325 355 BT4 470 525 415 325 75 420 200 595 550 320 2 320 272 134 135 19 8.8 ENV89MP 41
400 400 BT5 530 600 460 400 75 495 200 670 625 400 3 200 272 134 130 20 10.3 ENV89MP 43
450 BT9 630 700 530 500 75 595 230 770 725 500 3 250 302 164 155 27 16.2 ENV89MP 218 49
500
500 CT5 630 700 530 500 75 595 230 770 725 500 3 250 302 164 141 29 16.2 ENV89MP 218 52
700 630 CT9 780 900 630 700 75 792 250 970 925 690 4 230 322 184 161 46 22.3 ENV89MP 65
710 CT9 950 1050 750 800 100 942 270 1120 1075 840 5 210 342 204 141 50 34.5 ENV89MP 178 70
800 800 F2265 950 1050 750 800 100 942 270 1120 1075 840 5 210 342 204 250 72 34.5
ENV89MP 231 77
800 F2265 950 1050 750 800 100 942 270 1120 1075 840 5 210 342 204 304 85 34.5
1000 1000 D132 1180 1250 880 1000 100 1140 280 1320 1275 1000 6 250 352 214 270 125 42.7 -

All dimensions in mm

32
Vertical Discharge DVM

Specification
The type DVM roof extract unit combines the technical advantages of Woods in terms of air flow per Watt and consequent low running costs.
mixed flow impeller with a low contour vertical discharge cowl. All units are available for curb of purlin mounting.
The design provides the consultant /contractor with a high efficiency unit
where it is required to discharge the extracted air at high velocity away from Isolators, bird guards, burglar bars, motorised dampers, pre-fabricated curbs
roof level. and soaker sheets are available as optional extras.

The wind shield and base are moulded in fire retardant glass fibre reinforced Motors are rated for continuous running in ambient temperatures of up to
resin which provides excellent resistance to atmospheric corrosion. 50°C (122°F).

The range comprises of six fan sizes from 250 to 760 mm and air volumes DVM units are despatched completely assembled and packed.
up to 8.3m3/s.

The unit is designed to give excellent performance characteristics with high Impellers
volume flow and stable pressure development without stall. The fan is of
Woods mixed flow series powered by a metric motor giving high efficiency The impeller is aluminium and of Woods patented mixed flow design.

Performance
250mm 330 mm VERTICAL DISCHARGE - DVM
ft3/min 0 200 400 600 800 1,000 ft3/min 0 500 1,000 1,500 2,000
m3/hr 0 500 1,000 1,500 m3/hr 0 1,000 2,000 3,000
mm in 320 mm in
wg wg wg wg
30
200 0.8
20 280

1.0
240
160
FAN STATIC PRESSURE Pa

0.6
FAN STATIC PRESSURE Pa

15
200 20
13
00

120
re
v

160
/m
in
13

10 0.4
00

0.5
re

120
v/m

80
in

88 10
0
86 80
0 5 0.2
40 65
650 0
40

0 0 0 0 0 0
0.0 0.1 0.2 0.3 0.4 0.5 0.0 0.2 0.4 0.6 0.8 1.0
VOLUME FLOW m3/s VOLUME FLOW m3/s

33
Vertical Discharge DVM
Performance
400 mm 500mm
ft3/min 0 1,000 2,000 3,000 ft3/min 0 2,000 4,000 6,000 8,000
m3/hr 0
m3/hr 0 2,000 4,000 5,000 10,000
mm in 1,000 mm in
wg wg wg wg
500 2.0

800 80
3
400
40
1.5

FAN STATIC PRESSURE Pa


FAN STATIC PRESSURE Pa

600
13

14
60
80

00
300
re

re
v/m

v/m
in

in
1.0
400 40
200 20
90
0 1
0.5 87
0
100 200 20
67 68 0
0
54 0

0 0 0 0 0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6
VOLUME FLOW m3/s VOLUME FLOW m3/s

630 mm 760 mm
ft3/min 0 2,000 4,000 6,000 8,000 10,000 ft3/min 0 5,000 10,000 15,000
m3/hr 0 5,000 10,000 15,000 m3/hr 0 10,000 20,000 30,000
600 mm in 1,000 mm in
wg wg wg wg

500 2.0
800
80
3
FAN STATIC PRESSURE Pa

400
FAN STATIC PRESSURE Pa

40
1.5
600
60
96
94

0
0

re
re

300
v /m
v/

2
m

in
in

1.0
400 40
200 70 20
0 71
0
54 0.5 1
0 560
100 200 20
460
46 0

0 0 0
0 1 2 3 4 5 0 0 0
0 2 4 6 8
VOLUME FLOW m3/s
VOLUME FLOW m3/s

Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Code Speed Pressure Level at 3 m
rev/min 63 125 250 500 1K 2K 4K 8K dB(A) re 20 µPa

250 650 63 62 54 50 52 50 46 42 35
860 67 66 58 54 56 54 50 46 39
1300 73 76 69 65 67 65 61 57 50
330 650 68 69 63 56 55 52 50 41 39
880 73 74 68 61 60 57 54 46 46
1300 78 83 78 71 71 69 64 57 57
400 670 68 69 66 61 61 58 55 46 46
900 73 74 71 66 66 63 60 51 51
1380 81 84 83 77 77 74 70 65 61
500 540 75 75 74 66 65 61 56 52 50
680 77 77 76 69 68 64 59 54 53
870 82 81 80 74 72 69 64 59 58
1400 91 93 92 88 86 83 79 74 71
630 460 78 78 77 68 66 62 57 52 52
540 81 81 80 72 70 66 61 56 56
700 85 84 83 76 75 71 66 62 60
940 90 89 89 84 81 78 74 69 67
760 460 84 84 82 75 72 68 63 59 57
560 89 86 86 81 78 73 68 64 62
710 94 90 90 86 83 80 73 69 67
960 98 95 95 94 91 88 81 76 76

34
Vertical Discharge DVM
Electrical Data
220-240 V / 50 Hz / 1 φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Full Load Starting
Motor Capa- Motor
Current Current Current Current
Code Speed Motor Rating citor Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
250 650 BT5 0.02 0.35 0.48 2.5 0.02 0.22 0.6
250 860 BT4 0.035 0.35 0.6 4.0 0.035 0.15 0.4
250 1300 BT4 0.1 0.8 1.5 2.5 0.1 0.35 1.3
330 650 BT5 0.04 0.65 1.0 2.5 0.032 0.24 0.4
330 880 BT5 0.083 1.0 1.8 5.0 0.083 0.37 0.95
330 1300 BT5 0.22 1.8 2.7 8.0 0.22 0.7 2.5
400 670 BT9 0.07 0.8 1.3 5.0 0.07 0.45 0.8
400 900 BT9 0.14 1.25 2.3 8.0 0.18 0.8 1.8
400 1380 CT5 0.5 3.4 5.5 20.0 0.5 1.3 5.5
500 540 CT9 0.12 1.8 2.6 10.0 0.12 1.1 1.7
500 680 CT9 0.25 2.1 3.0 15.0 0.21 1.25 2.6
500 870 CT9 0.43 3.3 7.5 15.0 0.49 1.8 5.3
500 1400 F2249 2.3 14.5 50.0 100.0 2.3 5.5 30.0
630 460 F2265 0.23 2.3 3.5 12.0 0.23 1.3 2.2
630 540 F2265 0.4 3.3 4.6 20.0 0.4 2.2 3.8
630 700 F2265 0.75 6.0 12.0 30.0 0.75 2.5 6.0
630 940 F2269 1.8 9.8 24.0 50.0 1.8 4.5 16.0
760 460 D132/19 - 0.7 2.9 8.0
760 560 D132/19 - 1.8 5.2 16.0
760 710 D132/19 - 3.0 7.7 33.0
760 960 D132/26 - 6.3 13.9 77.0

Two Speed totally Enclosed Motors


220-240 V / 50 Hz / 1 φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Full Load Starting
Motor Capa- Change- Motor Change-
Current Current Current Current
Code Speed Motor Rating citor over Rating over
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
Panel Panel
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
330 880/540 BT5 0.06/0.013 0.65/0.4 1.2/0.4 4.0 EDC28 -
330 1290/770 BT5 0.22/0.045 1.8/0.85 2.7/1.0 8.0 EDC28 -
330 1300/650 BT9 - 0.22/0.033 0.65/0.25 1.5/0.5 EDC19
330 1300/860 BT9 - 0.22/0.057 0.9/0.42 3.3/1.0 EDC19
400 670/400 BT9 0.07/0.015 0.8/0.45 1.3/0.5 5.0 EDC28 -
400 900/540 BT9 0.14/0.03 1.2/0.7 2.0/0.8 8.0 EDC28 -
400 1380/830 CT5 0.5/0.11 3.4/2.0 5.5/2.0 20.0 EDC28 -
400 900/670 CT5 - 0.14/0.07 0.9/0.4 1.9/0.6 EDC19
400 1380/670 CT9 - 0.5/0.06 1.4/0.52 5.3/1.3 EDC19
400 1380/900 CT5 - 0.5/0.14 1.4/0.7 4.8/1.4 EDC19
500 680/430 CT9 0.25/0.065 3.0/2.2 3.5/2.5 20.0 EDC28 -
500 870/535 CT9 0.55/0.12 5.0/2.5 7.0/3.0 25.0 EDC28 -
500 680/460 F2265 - 0.25/0.075 1.2/0.85 2.3/1.4 EDC19
500 870/460 F2265 - 0.55/0.08 1.9/0.75 6.0/1.25 EDC19

VERTICAL DISCHARGE - DVM


500 870/680 CT9 - 0.55/0.25 2.8/1.5 5.7/1.7 EDC19
630 460/275 F2265 0.23/0.06 2.4/1.4 3.5/1.5 15.0 EDC28 -
630 540/350 F2265 0.4/0.1 3.6/1.65 5.5/2.0 20.0 EDC28 -
630 690/460 F2269 - 0.75/0.23 2.7/1.7 7.5/3.1 EDC19
630 920/690 F2269 - 1.8/0.76 5.8/3.0 25.0/7.0 EDC19
760 710/460 D132/26 - 2.8/0.76 8.0/3.8 37.0/12.5 EDC22
760 970/460 D160/27 - 5.5/0.6 14.0/3.8 35.0/14.0 EDC19
760 970/720 D160/27 - 5.5/2.25 16.0/7.2 80.0/25.0 EDC19

Flameproof Motors
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Motor Motor
Current Current Current Current
Code Speed Motor Rating Motor Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
rev/min (kW) (A) (A) (kW) (A) (A)
400 670 PENV89MP 0.09 1.3 2.7 ENV89MP 0.09 0.38 1.2
400 900 PENV89MP 0.18 1.8 7.2 ENV89MP 0.18 0.6 2.1
400 1380 PENV89MP 0.5 3.1 15.0 ENV89MP 0.5 1.2 6.0
500 680 PENV89LP 0.37 3.4 15.0 ENV89MP 0.37 1.3 6.2
500 870 PENV89LP 0.63 6.3 17.5 ENV89MP 0.63 1.9 7.6
500 1400 - ENV89LP 2.5 5.2 26.0
630 700 - ENV89LP 0.75 2.5 10.0
630 940 - ENV112MP 1.8 4.6 20.0

35
Vertical Discharge DVM
Dimensions and Weights

Purlin Mounting Curb Mounting Roof Sheet


Curb Mounting
A square

B square
Bird guard (top & bottom set)
when required.

Isolating switch Bird guard


when required. when required

C
C

Soaker sheet
Screws
supplied
8

72
50
130

130
R
100
min
N
G

Soaker sheet
D square E incorporating curb
Coach bolts supplied
Sealing B square
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
N

91mm. Double Six M. isolating switch is fitted


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, CT9, F22
have tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
(at extra cost) if full details of
H square cable are stated on order.

Flameproof Motors
Curb Fan
Size Motor A B C D E F G H J K L M N P R Weight Weight Motor R Weight
Size DVM Unit Purlin Unit
(kg) Box (kg)
325 250 BT4 600 525 372 325 75 420 200 595 550 320 2 320 272 134 127 22 8.8
-
BT5 600 525 372 325 75 420 200 595 550 320 2 320 272 134 127 24 8.8
400 330 BT5 710 600 420 400 75 495 200 670 625 400 3 200 272 134 122 26 10.3
-
BT9 710 600 420 400 75 495 200 670 625 400 3 200 272 134 157 28 10.3
500 400 BT9 820 700 480 500 75 595 230 770 725 500 3 250 302 164 127 35 16.2
CT5 820 700 480 500 75 595 230 770 725 500 3 250 302 164 118 36 16.2 ENV89MP 154 62
CT9 820 700 480 500 75 595 230 770 725 500 3 250 302 164 158 40 16.2
700 500 CT9 1030 900 565 700 75 792 250 970 925 690 4 230 322 184 138 62 22.6 ENV89MP 107 68
F2245 1030 900 565 700 75 792 250 970 925 690 4 230 322 184 132 68 22.6 ENV89LP 151 80
800 630 F2265 1260 1050 670 800 100 942 270 1120 1075 840 5 210 342 204 95 79 34.5
F2269 1260 1050 670 800 100 942 270 1120 1075 840 5 210 342 204 150 ENV89LP 113 100
89 34.5
1000 760 D132 560 1250 790 1000 100 1140 280 1320 1275 1000 5 250 352 214 103 134 42.7 -
D160 1560 1250 790 1000 100 1140 280 1320 1275 1000 5 250 352 214 245 166 42.7

All dimensions are shown in mm

36
Vertical Discharge DVC

Specification
The type DVC roof extract unit provides the consultant/contractor and user Motors are rated for continuous running in ambient temperatures of up to
with a high efficiency unit where it is required to discharge the extracted 50°C (122°F).
air at high velocity away from roof level. It employs a compact, direct
driven centrifugal fan with a guaranteed performance for extract systems DVC units are despatched completely assembled and packed.
with a significant static pressure requirement.
The wind shield and base are moulded in fire retardant glass fibre
reinforced resin which provides excellent resistance to atmospheric
Impellers
corrosion.
High efficiency, backward curved centrifugal, designed by Woods
The range comprises of six fan sizes from 250 to 760 mm and air volumes specifically for applications in this range of roof extract units.
up to 9.7m3/s.

All units are available for curb of purlin mounting.


Isolators bird guards, burglar bars, motorised dampers, pre-fabricated
curbs and soaker sheets are available as optional extras.

Performance Data

VERTICAL DISCHARGE - DVC


250 mm 330 mm

ft3/min 0 500 1000 ft3/min 0 1000 2000


m3/hr m3/hr
0 500 1000 1500 2000 mm in 0 1000 2000 3000 4000 mm in
240 wg wg wg wg
360

200 0.8 320


20
30
280
FAN STATIC PRESSURE Pa

FAN STATIC PRESSURE Pa

160 1.0
13
13

240
50

0.6
50

15
re
re

v /m
v/m

200 20
in

120
in

10 0.4 160

80 90 120 90 0.5
0r 0r
ev ev
/m /m 10
6 70 in 0.2 80 in
5 650
40 r ev r ev /
/m m in
in 40

0 0 0.0 0 0 0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.0 0.2 0.4 0.6 0.8 1.0 1.2
VOLUME FLOW m3/s VOLUME FLOW m3/s

37
Vertical Discharge DVC
Performance Data
400 mm 500 mm
ft3/min 0 2000 4000 6000 8000 10000
ft3/min 0 2000 4000
m3/hr
0 5000 10000 15000 mm in
m3/hr 0 2000 4000 6000 8000 mm in wg wg
wg wg

600 1000 100 4


60

500 2 800

FAN STATIC PRESSURE Pa


80
3
FAN STATIC PRESSURE Pa

13

14
400 40

00
50

600

re
60
re

v/m
v/m

in
300 2
in

1 400 40
93
200 90 20 0r
0r ev
ev /m 1
/m 700 in
660 in 200 rev 20
100 re v / mi
/ mi n
n
0 0 0
0 0 0 0 1 2 3 4 5
0.0 0.4 0.8 1.2 1.6 2.0 2.4
VOLUME FLOW m3/s
VOLUME FLOW m3/s

630 mm 760 mm
ft3/min 0 5000 10000 ft3/min 0 5000 10000 15000 20000
m3/hr m3/hr
0 5000 10000 15000 20000 mm in 0 10000 20000 30000 mm in
800 wg wg 800 wg wg

700 700
FAN STATIC PRESSURE Pa

600 60 600 60
FAN STATIC PRESSURE Pa

500 94 2 500 2
0 72
re 0
re
v/

400 400
v/

40 40
m

m
in

in

57
300 70 300 0r
0 r ev ev
1 47 /m 1
/m 0r in
200 56 in 20 200 ev/
0r mi 20
ev/ 350 n
m in rev
100 100 / mi
n

0 0 0 0 0 0
0 1 2 3 4 5 6 0 2 4 6 8 10
VOLUME FLOW m3/s VOLUME FLOW m3/s

Sound Levels
Open inlet Sound Power Level in dB re 1 pW in Octave Bands Free Field Sound
Code Speed Pressure Level at 3 m
rev/min 63 125 250 500 1K 2K 4K 8K dB(A) re 20µPa

250 670 60 61 59 55 51 44 39 36 35
900 67 68 66 62 58 51 46 43 42
1350 75 77 76 73 68 62 57 52 51

330 650 69 67 63 59 53 48 42 38 39
900 73 74 71 67 62 57 51 46 47
1350 80 84 83 79 75 70 64 59 58
400 660 76 74 70 66 60 55 49 46 46
900 80 81 78 74 69 64 58 53 54
1350 86 90 89 85 81 76 70 65 64

500 700 82 80 76 72 66 61 55 52 52
930 88 88 84 80 75 70 64 60 60
1400 95 98 95 91 87 81 77 71 72

630 560 83 81 80 77 74 72 64 61 58
700 88 86 84 81 78 76 71 68 63
940 95 93 91 88 85 83 78 75 70
760 350 78 77 76 74 68 65 58 53 54
470 85 83 82 80 75 72 66 63 60
570 91 89 87 84 81 79 74 71 66
720 96 94 92 89 86 84 79 76 71

38
Vertical Discharge DVC
Electrical Data
220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3 φ
Full Load Starting Full Load Starting
Motor Capa- Motor
Speed Current Current Current Current
Code Motor Rating citor Rating
rev/min (at 230 V) (at 230 V) (at 400 V) (at 400 V)
(kW) (µF) (kW)
(A) (A) (A) (A)
250 670 BT5 0.02 0.35 0.48 2.5 0.02 0.22 0.6
250 900 BT5 0.04 0.45 0.7 2.5 0.05 0.25 0.65
250 1350 BT5 0.11 0.9 1.7 5.0 0.12 0.37 1.2
330 650 BT5 0.04 0.65 1.0 2.5 0.032 0.24 0.4
330 900 BT9 0.14 1.25 2.3 8.0 0.18 0.8 1.8
330 1350 CT5 0.45 3.1 7.5 20.0 0.5 1.3 5.5
400 660 CT9 0.16 1.9 3.4 8.0 0.18 0.7 1.7
400 900 CT9 0.43 3.3 7.5 15.0 0.49 1.8 5.3
400 1350 CT9 1.3 8.0 23.0 50.0 1.3 3.3 12.0
500 700 F2265 0.6 4.8 9.5 20.0 0.6 2.0 6.5
500 930 F2265 1.4 9.2 27.0 50.0 1.4 4.0 16.0
500 1400 F2249 - 4.2 9.0 52.0
630 560 D132/19 - 1.8 5.2 16.0
630 700 D132/19 - 3.0 7.7 33.0
630 940 D132/19 - 4.5 10.5 63.0
760 350 D132/19 - 0.7 4.5 10.0
760 470 D132/19 - 1.7 6.0 24.0
760 570 D160/27 - 3.0 9.0 38.0
760 720 D160/27 - 5.2 13.5 50.0

Two Speed totally Enclosed Motors


220-240 V / 50 Hz / 1 φ 380-420 V / 50 Hz / φ
Full Load Starting Full Load Starting
Motor Capa- Change- Motor Change-
Speed Current Current Current Current
Code Motor Rating citor over Rating over
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
Panel Panel
rev/min (kW) (A) (A) (µF) (kW) (A) (A)
250 900/650 BT5 0.03/0.01 0.04/0.25 0.7/0.3 2.5 EDC28 -
250 1350/900 BT5 0.12/0.035 0.9/0.52 1.8/0.6 5.0 EDC28 -
330 900/600 BT9 0.11/0.035 1.0/0.6 1.7/0.7 6.0 EDC28 -
330 1350/900 CT5 0.36/0.11 2.5/1.4 4.0/1.5 12.0 EDC28 -
330 1350/700 CT5 - 0.36/0.045 0.95/0.4 2.7/0.8 EDC19
330 1350/900 CT5 - 0.36/0.11 1.05/0.55 3.9/1.2 EDC19
400 900/600 CT9 0.33/0.1 3.3/1.4 5.2/1.5 10.0 EDC28 -

VERTICAL DISCHARGE - DVC


400 1350/960 CT9 1.1/0.2 7.0/4.0 20.0/5.0 50.0 EDC28 -
400 1440/720 F2245 - 1.5/0.19 3.5/1.2 19.0/4.2 EDC19
400 1440/940 F2245 - 1.5/0.42 3.9/1.6 20.0/5.5 EDC19
500 950/710 F2269 - 1.3/0.55 5.0/2.4 25.0/7.0 EDC19

630 950/720 D132/26 - 3.6/1.5 11.0/5.7 66.0/22.0 EDC22

760 720/350 D160/27 - 6.0/0.75 15.5/6.5 64.0/20.0 EDC19

Flameproof Motors Electrical Data


220-240 V / 50 Hz / 1φ 380-420 V / 50 Hz / 3φ
Full Load Starting Full Load Starting
Motor Motor
Speed Current Current Current Current
Code Motor Rating Motor Rating
(at 230 V) (at 230 V) (at 400 V) (at 400 V)
rev/min (kW) (A) (A) (kW) (A) (A)
400 700 PENV89MP 0.28 2.1 4.5 ENV89MP 0.28 0.92 3.2
400 900 PENV89MP 0.63 6.3 17.5 ENV89MP 0.63 1.95 7.8
400 1440 - ENV89MP 1.3 4.0 20.0

500 700 - ENV89MP 0.6 2.1 8.4


500 940 - ENV89MP 1.1 3.3 13.2

630 700 - ENV89LP 1.3 4.1 16.5

39
Bergholt DVC
Dimensions and Weights

Purlin Mounting Curb Mounting Roof Sheet


Curb Mounting

A square

B square
Bird guard (top & bottom set)
when required.

Isolating switch Bird guard


when required. when required

C
C

Soaker sheet
Screws
supplied
8

72
50
130

130
R
100
min
N
G

Soaker sheet
D square E incorporating curb
Coach bolts supplied
Sealing B square
L no, of holes per side strip
8

at M pitches ø 11 Purlin box Inlet guard


48mm. Big Six, Major & Std. Six. Customers supply entry when required
86mm. Double Six. to motor except when
N

91mm. Double Six M. isolating switch is fitted


130

Soaker
sheet Skirt

Cable Entries:
K crs
J crs

Totally enclosed motors:


BT5, BT9, CT5, CT9, F22
have tapped CM 20, hole with
F square 1.5 thread. Gland is supplied.
D132/D160 have motor mounted
terminal box, knockout clear
hole for conduit/gland entry.
Flameproof Motors:
Motors have tapped CM 20 hole
with 1.5 thread but without
gland. Gland can be supplied
(at extra cost) if full details of
H square cable are stated on order.

Flameproof Motors
Curb Fan
Size Motor A B C D E F G H J K L M N P R Weight Weight Motor R Weight
Size DVC Unit Purlin Unit
(kg) Box (kg)
325 250 BT5 600 525 372 325 75 420 200 595 550 320 2 320 272 134 71 24 8.8 -

400 330 BT5 710 600 420 400 75 495 200 670 625 400 3 200 272 134 67 28 10.3
BT9 710 600 420 400 75 495 200 670 625 400 3 200 272 134 102 29 10.3 -
CT5 710 600 420 400 75 495 200 670 625 400 3 200 272 134 87 31 10.3
500 400 CT9 820 700 480 500 75 595 230 770 725 500 3 250 302 164 106 39 16.2
ENV89MP 154 64
F2245 820 700 480 500 75 595 230 770 725 500 3 250 302 164 146 46 16.2
700 500 F2265 1030 900 565 700 75 792 250 970 925 690 4 230 322 184 132 72 22.6 ENV89MP 107 73
F2269 1030 900 565 700 75 792 250 970 925 690 4 230 322 184 187 82 22.6 ENV89MP 151 85
F2249 1030 900 565 700 75 792 250 970 925 690 4 230 322 184 187 82 22.6 ENV89MP 151 85
800 630 D132/19 1260 1050 670 800 100 942 270 1120 1075 800 5 210 342 204 145 115 34.5 ENV89LP 113 106
1000 760 F3264 1560 1250 790 1000 100 1140 280 1320 1275 1000 5 250 352 214 79 134 42.7
D132/19 1560 1250 790 1000 100 1140 280 1320 1275 1000 5 250 352 214 103 141 42.7 -
D160/27 1560 1250 790 1000 100 1140 280 1320 1275 1000 5 250 352 214 245 173 42.7

All dimensions shown in mm

40
Wall Extract Units Colchester Range
Introduction Shutters
Woods Wall Units represent another part of the flexibility and family con- An attractive unit with rigid PVC vanes and aluminium frame. Operated by
cept of the Colchester Roof Unit Range. fan pressure, shutters are enclosed when fan stops. These replace the roof
unit shutters.
The DSP, DSM, DSC units are readily converted to the wall mounted
WDP, WDM, WDC by means of a wall adaptor and lourve shutters. Per- Fan performance loss is small but varies with fan type, size and duty pres-
formance data may be taken from pages 11-15 (DSP), 19-23 (DSM), and sure.
24-28 (DSC).
Shutters should only be used with the two higher fan speeds in
The adaptor has been load tested to ensure a generous structural factor each size.
of safety enabling it to withstand all normally encountered weather con-
ditions.
Performance Data
The wall unit is secured to the adaptor by stainless steel screws.
Wall Max. Volume Max. Static For Air Performance
Specification Unit m3/s Pressure Pa Data See Page
WDP 1.65 140 DSP Page 11-15
Wall Adaptor WDM 1.80 400 DSM Page 19-23
The adaptor is moulded in ultra violet stabilized polyester resin, glass rein- WDC 2.5 500 DSC Page 24-28
forced, rendered fire retarant to BS.476: Part 7.

Colourant to BS.4800:08B-21 is built in. EXTRACT UNIT TO ADAPTOR PLATE TO WALL


BIRD GUARD ADAPTOR PLATE FIXINGS (SUPPLIED) - PLATE
WHEN REQUIRED FIXINGS (SUPPLIED) SEALED TO THE WALL BY CUSTOMER
SHUTTERS
Dimensions and Weights WHEN
REQUIRED

SECOND ENTRY POINT


FOR USE WITH SINGLE
PHASE CAPACITOR ONLY

WALL EXTRACT UNIT - COLCHESTER RANGE


A AIRFLOW
10°
c

CUSTOMER SUPPLY
ENTRY POINT TO
MOTOR EXCEPT WHEN
ISOLATION SWITCH
IS FITTED

FIXING TO TIMBER FRAME

35MM SQUARE TIMBER


FRAME FIXED IN WALL
D 25 APERTURE AND
NOTE: 2 LIFTING LUGS AT
OPPOSITE CORNERS SUPPLIED BY CUSTOMER
ON 700 AND 800 SIZE
CURBS, 4 LUGS ON 1000 E MIN.
SIZE CURBS. RECESSED
E MAX.
90MM MAX. - PROJECTING
CA10 SWITCH ISOLATION SWITCH
125MM MAX - WHEN REQUIRED.
CA20 SWITCH
Weight
Fan Size A B C D E G H J (Wall Adaptor)
kg
WDP 250, WDM 200, WDC 200 480 347 285 168 45 270 600 355 2.4

WDP315/355, WDM 250,WDC 250 600 383 385 181 22 310 670 455 2.8

WDP 400, WDM 330, WDC 330 710 435 435 194 18 350 750 505 3.4

WDP 450/500, WDM 400, WDC 400 820 495 535 212 0 400 850 605 4.0

All dimensions shown in mm

41
Acoustic Curbs Colchester Range
Woods WAC Acoustic curbs have been designed for use with Woods Air Base Mounting
Movement range of Roof Extract Units.
The unit is positioned on top of the builders' roof curb with the unit
covering the timber.
They are suitable for mounting through the roof opening, with varying
projection above or below the roof structure, or for mounting directly on
Coachscrews and sealing washers are provided with both forms of mount-
top of builders' roof curb.
ing, for assembly to the builders' curb. Customers should provide
flashing where wooden curbs are exposed.
Construction
The curb consists of square section casing fabricated from pre-galva- Electrical Connection
nised steel sheet, containing a vertical assembly of acoustic splitters
Electrical connections to the roof unit fan motor terminal box may be
and liners.
taken from a junction box installed adjacent to the sound attenuating
curb via a flexible conduit led up through one of the curb airways.
The splitters have pre-galvanised steel frames and the absorbent mate-
rial is resin bonded mineral fibre with an erosion resistant facing.
Order details
An impervious moisture resistant lining is available for moist air appli- When ordering a sound attenuating curb state the WAC size and whether
cations. The use of the lining also allows the curb to be low pressure to be Recessed Mounting or Base Mounting. If for Recessed Mounting
steam cleaned. Some reduction in attenuation due to the lining will be state dimensions F - necessary for the setting of the mounting height.
experienced. See drawing opposite. When no dimension is given the maximum di-
mension F is supplied.
The skirts and flanges are also produced from galvanised sheet steel.
When required for use with roof units employing flameproof motors,
Lifing Lugs are provided on all sizes. please specify as 'WACF' plus the size. The use of flameproof motors
necessitates the rearrangement of the splitters with some loss of attenu-
Mounting ation.
The curb may be mounted on the builders' roof curb, purlin box sur-
rounding the roof opening in one of two ways.

Recessed Mounting
For this method a skirt is attached to the outside of the casing for mounting
the unit within the roof opening. The position of the skirt can be factory-
set, to offer a range of the sound attenuating curb above or below the
roof opening.

ROOF UNIT SIZE


Curb Size DVC DSC DVP DSP DVM DSM
WAC10 200 250 200
WAC11 250 250 355 315/355 250 250
WAC12 330 330 400 400 330 330
WAC13 400 400 450/500 400/500 400 400
WAC14 500 500 630 630 500 500
WAC15 630 630 710/800 710/800 630 630
WAC16 760 760 1000 1000 760 760
Table 1 Curb/Roof Unit Combination

Attenuation dB
Octave band mid-frequency Hz
Curb Volume Pressure Curb Volume Pressure
Size 63 125 250 500 1K 2K 4K 8K Size m3/s loss Pa Size m3/s loss Pa
WAC10/11 0.5 8 WAC14 3.0 17
WAC 10-12 4 7 12 16 21 22 20 13 WAC12 1.0 10 WAC15 4.3 12
WAC 13-16 5 9 12 18 23 21 17 14 WAC13 1.5 9 WAC16 5.0 8
Table 2 Attenuation Table 3 Pressure Loss

42
Acoustic Curbs Colchester Range
Dimensions and Weights

RECESS MOUNTED
DVM & DVC DSP, DSM & DSC DVP 8-COACH SCREWS-WAC 10 TO 15
12-COACH SCREWS-WAC 16
H SQUARE

CURB
N
H SQUARE H SQUARE
M
G

P SQ. OUTSIDE

INSIDE CURB
G

R CENTRES

M SQ.
E

MOUNTING
E

E
M M

PLATE
50 50 50

INSIDE CURB INSIDE CURB INSIDE CURB


F

F
D D D
S CENTRES

BASE MOUNTED RECESSED


DVM & DVC DSP, DSM & DSC DVP MOUNTING
H SQUARE
8-COACH SCREWS

L CURB
H SQUARE H SQUARE

INSIDE CURB
A
A
A

K
LIFTING BRACKETS
B

B
B

C C C 2 ON WAC 10 TO 13
K 50 K 50 K 50
4 ON WAC 14 TO 16
INSIDE CURB INSIDE CURB INSIDE CURB
J
ACOUSTIC CURBS TO SUIT
FLAMEPROOF MOTORS HAVE
SUFFIX F ADDED TO WAC SIZE
BASE MOUNTING

WAC10 WAC11 WAC12 WAC13 WAC14 WAC15 WAC16


DSP 315/355

DSP 710/800

DVP 710/800
DVP 450/500
DSP 450/500

DSP 1000

DVP 1000
DVM 330

ACOUSTIC CURBS - COLCHESTER RANGE


DVM 400
DSM 200

DSM 250

DVM 500

DSM 630

DVM 630

DSM 760

DVM 760
DVM 250

DSM 330

DSM 500
DSM 400
DVC 330

DVC 400
DSC 200

DSC 250

DVC 500

DSC 630

DVC 630

DSC 760

DVC 760
DVC 250

DSC 330

DSC 500
DSP 250

DVP 355

DSC 400
DVP 400
DSP 400

DSP 630

DVP630

DIM
A 708 813 875 918 888 953 993 943 1023 1073 1053 1143 1208 1228 1348 1428 1478 1558 1648
B 500 575 605 615 650 750 840
C 420 495 570 670 870 1020 1220
D 420 495 570 670 870 1020 1220
E 708 813 875 918 888 953 993 943 1023 1073 1053 1143 1208 1228 1348 1428 1478 1558 1648
MAX 330 405 435 446 480 580 670
F MIN 50 55 85 96 60 90 110
G MAX 658 758 820 863 803 868 908 847 927 977 993 1083 1148 1138 1258 1338 1368 1448 1538
MIN 378 408 470 513 453 518 558 497 577 627 573 663 728 648 768 848 808 888 978
H 480 600 600 470 710 710 530 820 820 630 1030 1030 780 1300 1260 950 1700 1560 1180
J 150 200 250 350 550 650 850
K 250 325 400 500 700 800 1000
L 75 75 75 75 75 100 100
M 500 600 600 700 900 1200 1500
N 75 75 75 75 100 100 100
P 684 784 784 884 1140 1440 1740
R 575 675 675 775 1000 1300 1600
S 260 320 320 360 450 800 980
Weights 18 kg 25kg 31kg 37kg 55kg 74kg 109 kg
curb
Weights 25 kg 33kg 38kg 37kg 70kg 100kg 147 kg
recess

All dimensions shown in mm

43
Soaker Sheet Colchester Range
Soaker Sheet can be supplied for the common roof profiles listed below. Mouldings are in ultra violet stabilised glass reinforced polyester resin,
rendered fire retardant to BS476 Part 7 Class 2. Colourant (built in) is to
Purlin mounted Soaker Sheets are available for all sizes and have a plain BS4800:08 B21.
upstand.

Direct mounting Soaker Sheet can also be supplied for the four smaller
sizes. These are complete with 4 x M8 fixings and 30mm wide seating.
B

These features AxA


on direct 30 30
mounting
sheets only M8 fixing
130
one per side

Profile Double Six Double Six M Bic 6

DSM DVM Length


DSP DVP DSC DVC A B C B C B C

250 200 476 1041 914 1300 1200 1086 1022 1676
315/355 250 500 1041 914 1300 1200 1086 1022 1676
400 330 576 1041 914 1300 1200 1086 1022 1676
450/500 400 676 1041 914 1300 1200 1086 1022 1676
630 500 - 1346 1219 1300 1200 1378 1314 1676
710/800 630 - 1346 1219 1300 1200 1378 1314 1676
1000 760 - 1651 1524 1300 1800 1524 1460 2100

Roof Mounting Details


Curb mounted
'A' square 'B'
Timber cill
by builder
Flashing
50
150
min

CONCRETE ROOF
Fan Size
Timber curb 'A' square 'B'
DSP DVP DSM DVM DVC A B C D
Flashing DSC
min
150

250 200 250 75 325 426


315 250 250 250 325 75 400 500
'C' square 355 355
Trimmer 400 400 330 330 330 400 75 475 576
DECKING ROOF, BUILDERS UPSTAND 450 450 400 400 400 500 75 575 676
500 500
Fabricated metal 'A' square 'B' 630 630 500 500 500 700 75 775
Flashing 710 710 630 630 630 800 100 900
800 800
150
min

250

1000 1000 760 760 760 1000 100 1100


All dimensions shown in mm
'C' square
Trimmer Purlin
DECKING ROOF, METAL UPSTAND (OPTIONAL EXTRA)
FLAT ROOFS

44
Purlin/Ancillaries Colchester Range
Purlin mounted

138
on pitched roof 48mm Big Six, Major Six and Std Six

130
86mm Double Six

min
'G'

'H'
Soaker sheet 91mm Double Six M

'G'
Flashing
CORRUGATED ROOF
USING SOAKER SHEET Glazing bars
Purlin box

138
GLAZING BARS
USING FLASHING 'E' No. of holes

'G'
Flashing 11 DIA

'H'
Corrugated
sheet

'D' CRS 'D' CRS


'C' CRS
CORRUGATED ROOF

50
'A' square
USING FLASHING
Trimmer clamp
fixed to purlins Trimmer

Betwe
Purlin box

'F'
'B' square

en
trimm
FLANGE DETAILS FOR PURLIN BOX

ers
Trimmer Additional
Lindapters supplied trimmers
with spreader plates 'F' immers on these
and nuts and bolts en t r sizes
Betwe welded or
SCRAP SECTION SHOWING 50 bolted in
PURLIN BOX FIXED TO TRIMMER DETAILS
TRIMMER WITH LINDAPTORS
SIZES 630mm to 1000mm
Fan Size

PURLIN BOXES/ANCILLARIES - COLCHESTER RANGE


DSP DVP DSM DVM DVC A B C D E F G H All dimensions are shown in millimetres
DSC
250 200 345 520 475 250 8 360 272 134
315
250 250 250 420 595 550 320 8 435 272 134
355 355
400 400 330 330 330 495 670 625 200 12 510 272 134
450 450
400 400 400 595 770 725 250 12 610 302 164
500 500
630 630 500 500 500 792 970 925 230 16 810 322 184
710 710
630 630 630 942 1120 1075 210 20 960 342 204
800 800
1000 1000 760 760 760 1140 1320 1275 250 20 1160 352 214

Ancillary Items
Anti-backdraught shutters Burglar Bars
Shutters are of aluminium and are an optional extra. Synthetic rubber Robustly manufactured in steel, with double row of steel bars for extra
buffers are provided to ensure quiet operation. Use of shutters does not security.
reduce fan unit performance, but will improve weathering under extreme
conditions.
Motorised Dampers
To meet requirements where heat loss is critical - motorised dampers
Inlet Guard mount into the ceiling opening.
A flat square wire guard can be supplied to close off the opening in a Manufactured in aluminium with opposed multileaf blades, supplied
ceiling slab. See unit drawing. Fixings not supplied. complete with motor.

Bird Guards Prefabricated Metal Upstand


Guards can be provided to prevent entry of birds via air discharge Where it is not convenient to form a timber or concrete upstand, Woods
openings. Fixings supplied. can provide a preformed pre-galvanised steel curb.

45
Speed Controllers & Changeover Panels

Speed Regulation - Vertical Discharge MT1.5,8,12 / MT3.0.5,1,2


This range of large controllers can be used as an alternative to the ME1.1,3,6,12
To maintain a high discharge velocity, speed regulation is not recom-
electronic controllers.
mended with vertical discharge units. Current Range - MT1. 5, MT1.8, MT1.12 Amp
MT3.0.5, MT3.1, MT3.2 Amp
Speed Regulation - Side Discharge Standard electric supply-
220-240 V 1 phase 50 Hz
A comprehensive range of speed controllers has been developed to work in 380-420 V 3 phase 50 Hz
conjunction with the fans which power the roof unit range, (see publication Other supplies - please enquire.
B16). Speed Control - down to 30% of full speed, approximately
Note: All speed controllers are non-flameproof.

Solid State Electronic Range


The range has two basic types of units, the Manual Speed Controller (ME.) and Changeover Panels
the Automatic Speed Controller (AE.). A complete range of changeover panels is available for all two speed motors
shown in this catalogue. These are offered in three types to complement the
ME1.1, 3, 6, 12 pole change, dual wound three phase and series/parallel single phase motors
Current range 1-3-6-12 Amp used. Note: All changeover panels are non flameproof.
Standard electrical supply -
220-240 V 1 phase 50 Hz. EDC19
Speed Control - down to 20/30% of full speed. This panel is suitable for all pole change or PAM wound motors and is a self
Mounting - surface. Enquire for flush mounting. contained, steel enclosed starter panel with manual high/low/off facility
Construction - plastic box except ME1.6 & ME1.12 (metal box) all splashproof. complete with high/low speed visual indication. The protection category is
IP54 and is suitable for all three phase supply applications.
ME3.5s, 10s
Current range 5-10 Amp EDC22
Standard electrical supply - This panel is suitable for all dual wound motors and is a self contained steel
380-420 V 3 phase 50 Hz plus neutral. enclosed starter panel with high/low/off facility complete with high/low speed
Speed Control - down to 20/30% of full speed. visual indication. Protection category is IP54 and is suitable for all three phase
Mounting - Surface mounting only. supply applications.
Construction - Metal splashproof box.
EDC28
AE1.3, 6, 12 This panel is suitable for series parallel type motors and is a self contained
The AE electronic controller through the thermistor control circuit offers a steel enclosed starter panel with high/low/off facility complete with high/low
means of speed/volume control under varying conditions thus providing an speed visual indication.
energy saving benefit. Protection category is IP54 and is suitable for all single phase supply
Current range 3-6-12 Amp
Standard electrical supply -
220-240 V 50 Hz 1 phase.
Sensor- thermistor supplied
Speed Control - down to 20/30% of full speed.
Mounting - surface mounting only.
Construction - metal splashproof box.

Auto-Transformer Range
A range of auto-transformer type regulators is available and offers regulation
without the increase in motor noise which is generally associated with all
electronic regulators.
All MT speed controllers provide 5 steps of speed plus off.

MT1.1
Current Range 1 Amp
Used with small single phase fans.
Standard supply -200-240 V 1 phase 50/60 Hz. Other voltages - enquire.
Speed Control - down to 20/30% of full speed.
Mounting - surface
Construction - totally enclosed plastic, dustproof box.

46
Other Units Available
Belt Driven Units

Fan Type - BSM Fan Type - BSC


● Side discharge. ● Side discharge.
● Powered by Woods Belt driven mixed flow fan units. ● Powered by Woods Belt driven centrifugal fan units.
● Stand by motor optional. ● Stand by motor optional.
● Five fan sizes. ● Five fan sizes.
● Air volumes up to 10.00 m3/s ● Air volumes up to 10.8 m3/s

OTHER UNITS AVAILABLE

Fan Type - BVM Fan Type - BVC

● Side discharge. ● Side discharge.


● Powered by Woods Belt driven mixed flow fan units. ● Powered by Woods Belt driven centrifugal fan units.
● Stand by motor optional. ● Stand by motor optional.
● Five fan sizes. ● Five fan sizes.
● Air volumes up to 9.6 m /s 3 ● Air volumes up to 10.3 m3/s

60 Hz Electrical Supply
A full range of both direct and belt driven roof units are also availalble suitable for 60Hz electrical supplies, please enquire for full details.

47
Other Units Available
High Temperature Units

Fan Type - DVA Fan Type - UDA


● Vertical discharge. ● Side discharge.
● 4 Unit Sizes up to 500mm to 1000mm. ● 12 Unit Sizes 315 mm to 2000 mm.
● Volume Flow up to 10m3/s. ● Volume Flow up to 45 m3/s.
● Air Pressure up to 500 Pa available. ● Air Pressure up to 1000 Pa available.
● Incorporating Woods H.T. Aerofoil Fans. ● Incorporating Woods H.T. Aerofoil Fans.

Roof Input Units

Fan Type - MF-TAF Input Units


● Mixed Flow Roof Input Unit
● Units suitable for flat roof or sloping roof.
● Bird guards are fitted as standard.
● Filters can be disposable synthetic fibre or glass fibre, washable
foam, 25mm or 50mm thickness.
● Units available without fans.
● Available for wall mounting.

Fan Type - DPI


● 2101 GP fan powered roof input unit
Fan Type - ASP Input Units ● Suitable for curb or purlin mouting.
● Basic fan details as DSP unit (Less Shutters).
● Three alternatives
● Performance offered is 90% of DSP volume flow.
● Part assembled for easy installation
● For flat or pitched roof
Fan Type - DMI
● Fresh Air Input
● Recirculation for heat recovery ● Mixed Flow roof input unit.
● Filtration ● Suitable for curb or purlin mounting.
● Heating ● Basic fan details as DSM unit (Less Shutters).
● Adjustable air distribution ● Available in 3 sizes, 500, 700 and 1000mm only.
● Performance as equivalent DSM unit

48
Useful Information
Fan Laws Air Changes Per Hour
Speed change – constant size – constant density Although no hard and fast rules can be laid down for rates of air
Volume Flow α Rotational Speed changes, the recommendations in the table below may be taken as a
Pressure (Static, Dynamic and Total) α (Rotational Speed)2 general guide.
Power Absorbed α (Rotational Speed)3
Size change – constant speed – constant density Situation Air changes
(For geometrically similar fans only) per hour
Volume Flow α (Impeller Diameter)3
Pressure (Static, Dynamic and Total) α (Impeller Diameter)2 Assembly Halls 4-6
Power Absorbed α (Impeller Diameter)5 Bakeries 15 - 30
Density change – constant speed – constant size Banks 2-4
Volume Flow = No change Bathrooms 6-8
Pressure (Static, Dynamic and Total) α Density Bars 6-8
Power Absorbed α Density Boiler Houses 15 - 30
The laws can be combined where simultaneous changes in size, speed Cafés 8 - 12
and density are required. Canteens 8 - 12
Churches 1 - 10†
Cinemas* 6 - 10
Air Density Classrooms 2-4
Standard Air density is 1.2kg/m3
Cleaners 15 - 30
One condition that gives Standard Air is:
Dance Halls 8 - 12
16°C, 100 kPa barometric pressure, 65% relative humidity.
Domestic Kitchens 10 - 15
Dyers 15 - 30
Change due to temperature
Engine Rooms 15 - 30
New Density = Old Density x
{ 273 + Old Temperature °C
273 + New Temperature °C } kg/m3
Foundries
Furnace Rooms
30 - 60
30 - 60
Change due to altitude 4.256 Garages 6 - 10
New Density = Old Density x
{ 288 - 0.00649 H
288 } kg/m3
Hospital Wards
Hospital Treatment Rooms
6-8
6-8
Kitchens for Restaurants 13 - 30
Where H = Height above sea level in metres
Laboratories 4-6
Laundries 10 - 15
Pressure Libraries 2-4
Dynamic Pressure = 0.5 (V)2 Pa Offices 4-6
Where = Air Density kg/m3 Paint Shops 30 - 60
V = Air Velocity m/s Residences 1-2
Total Pressure = Static Pressure + Dynamic Pressure Restaurants* 10 - 15
Storage Areas 1-2
Absorbed Power Swimming Baths 15 - 30
Theatres* 6 - 10
Absorbed Power =
Useful Information
{ Volume flow (m3/s x Total Pressure (Pa)
Total Efficiency x10 } kW Workshops 6 - 10 USEFUL INFORMATION
* General requirements are 28m3/h per person minimum in public
places; more if smoking is allowed.
† Dependent on height of building and number of persons.
in x 25.4 = mm
ft x 0.305 = m
ft3 x 0.028 = m3
Ib x 0.454 = kg
BTU x 1054.8 = J
HP x 0.746 = kW
k cal/h x 0.00116 = kW
Ton Refrigeration x 3.52 = kW
BTU/ft2h°F x 5.678 = J/m2s°C
or
= W/m2°C
ft3/min x 0.000472 = m3/s
in. wg x 249.1 = Pa

49
Useful Information
Conversion
ft2 m2 ft3/min m3/s in. wg Pa ft/min m/s gpm (UK) I/s BTU kJ BTU/h J/s °F °C m3/h m3/s mm wg Pa

100 10000 10 1000 5.0 100 10 10 10000 10


9
10 400
7 200 9000 90
90 9000 9 900 90 9 9 9
8 9
4.0
80 8000 8 2000 800 80 6 8 8 8000 8 80
4.0
7 8 350
70 7000 700 70 7000 2 70
7 7 7
2
7
6 5 7
3.0
60 6000 6 600 60 6000 60
3.0 6 6 300 150 6
6
5
4
50 5000 5 500 50 5 5 5000 5 50
5
250
4 2.0
40 4000 4 1000 400 40 3 4 4 4000 4 40
2.0
4 100
900 1
200
1
3 800 0.9
0.9 30
30 3000 3 300 30 3 3 3000 3
0.8
700 3 0.8 150
2
0.7
600 0.7 50

2 1.0 100 0.6


0.6
20 2000 2 500 200 1.0 20 2 2 2000 2 20
0.9 2
0.9 0.5
0.8 0.5
50
400 0.8
0
0.7
0.4
0.7 0.4
1
0.6 0
300 0.6 0.9

1 0.8 0.3
0.5
0.3
10 1000 1 100 10 1 1 -50 1000 1 10
1 ft2 1 ft3/min 1 in. wg 1 ft/min. 1 gpm (UK) 1 BTU 1 BTU/hr 1 m3/h 1 mm wg
= 0.0929 m2 = 0.00047 m3/s = 249 Pa = 0.00508 m/s = 0.0757 I/s = 1.055 kJ = 0.293 J/s = 0.000278 m3/s = 9.806 Pa

Motor Enclosures – Degrees of Protection

1st Numeral 2nd Numeral

Designation Protection against contact and ingress of foreign bodies. Protection against water.

Protection against contact with live or moving parts of tools, wires or Water splashed against the motor from any direction
other objects of thickness greater than 1mm. shall have no harmful effect.

IP44 Protection against the ingress of solid foreign bodies with a


diameter greater than 1mm.

Complete protection against contact with live or moving parts inside the Water projected by a nozzle against the motor from
enclosure. Protection against harmful deposits of dust. The ingress of any direction shall have no harmful effect.
dust is not totally prevented, but dust cannot enter in an amount
IP55 sufficient to interfere with satisfactory operation of the machine. IP55 as despatched. Drain holes are incorporated
such that by removing the appropriate plugs all-
weather protection can be provided and condensation
build-up prevented.

IP56 Motor protected against conditions on a ship’s deck.

50
51
Woods Air Movement Limited is represented in over 70 countries world-wide.
See our website for details - www.woods-fans.com

U.K.
England Wales Scotland &
South & South East Midlands & South West North of England
Woods Air Movement Limited Woods Air Movement Limited Woods Air Movement Limited
Tufnell Way Waterlinks House, Richard Street P.O. Box 142
Colchester CO4 5AR Birmingham B7 4AA Manchester M60 1AQ
Telephone: +44 (0) 1206 544122 Telephone: +44 (0)121 359 6633 Telephone: +44 (0)161 8480341
Facsimile: +44 (0) 1206 574434 Facsimile: +44 (0)121 359 1818 Facsimile: +44 (0)161 8729847
E-mail: enquiry@woods-fans.com E-mail: birmingham@woods-fans.com E-mail: manchester@woods-fans.com

Europe
Finland France Germany Italy
Woods Puhallin Oy Cie Française Woods Woods Ventilatoren GmbH Woods Italiana SpA
Ruosilantie 2b 16 Burospace Siemensstrasse 16 Via Montenero 55/57
00390 Helsinki F91772 Bièvres Cedex 40 855 Ratingen 20092 Cinisello Balsamo
Finland France Germany Milan, Italy
Telephone: +35 8 9 540 4770 Telephone: +33 (0) 1 60 19 55 94 Telephone: +49 21 02 31068 Telephone: +39 02 61 86091
Facsimile: +35 8 9 540 47754 Facsimile: +33 (0) 1 60 19 55 71 Facsimile: +49 21 02 39113 Facsimile: +39 02 61 860947
E-mail: info@woods-puhallin.fi E-mail: woodsfr@gec-france.fr E-mail: woods@t-online.de E-mail: info@woods-italiana.it

International
Canada Singapore USA
Woods Air Movement (Canada) Ltd Woods Singapore Pte American Fan Company
401 Traders Blvd Marconi Building 2933 Symmes Road
Unit #8, Mississauga 3 Tai Seng Drive Fairfield
Ontario L4Z 2H8 Singapore 535216 Ohio 45014, USA
Canada Telephone: +65 3828233 Telephone: +1 513 874 2400
Telephone: +1 905 501 0211 Facsimile: +65 3828200 Facsimile: +1 513 870 6249
Facsimile: +1 905 501 0399 E-mail: francis.tan@marconi.com.sg E-mail: af-sales@amfan-woods.com

Due to a policy of continuous development and improvement the right is reserved to Publication No: RU/DD
supply products which may differ from those illustrated and described in this publication. April 2000
Certified dimensions will be supplied on request on receipt of order.
© Copyright 2000 Woods Air Movement Limited. England